Plan Review Notes
Plan Review Notes For Permit 08090682
Permit Number 08090682
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-09 14:45:06 
 ** DENIED **
  
 1) NOTE: PLEASE SEE FS 471.023, FAC 61G15-23.002. THE
 SCOPE OF WORK AS SHOWN IS REQUIRED TO BE DONE BY AN
 ENGINEER. ANY FIRMS PROVIDING THAT SERVICE IS REQUIRED
 TO HAVE AN ENGINEERING BUSINESS LICENSE NUMBER ALSO
 KNOWN AS A CERTIFICATE OF AUTHORIZATION NUMBER. THIS IS
 THE SAME AS AN ARCHITECTURAL FIRM PROVIDING
 ARCHITECTURAL SERVICES. METRO DESIGN GROUP NOW SHOWS
 THE ARCHITECTURAL FIRM LICENSE NUMBER ON PLANS HOWEVER
 NOT INDICATE THE ENGINEERING BUSINESS LICENSE NUMBER.
 PLEASE INCLUDE AS REQUIRED.
 ** THIS WAS CONFIRMED WITH THE STATE BOARD OF ENGINEER
 WHEN PROVIDING ENGINEERING SERVICES.
  
 2) NOTE: PLEASE SEE THE RISER SHOWS A NEUTRAL FROM
 PANEL *H* TO TRANSFORMER WHICH IS NOT PERMITTED AS THIS
 IS A SEPARATELY DERIVED SYSTEM.
 250.6.250.24, 250.20, 250.30, 250.50, 250.66 ETC
  
 3) NOTE: PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM
 AND ATTACHMENT FOR NEW TRANSFORMER PER THE SAME CODE
 SECTIONS NOTED IN NOTE #2 ABOVE.
  
 4) NOTE: PLEASE 450.13 AS THE 75KVA TRANSFORMER AS
 SHOWN IS NOT PERMITTED ABOVE THE CEILING AS NOTED ON
 RISER.
  
 5) NOTE: PLEASE INDICATE THE SIZE OF THE EXISTING
 SERVICE WITH THE CURRENT EXISTING LOADS WITH NEW LOADS
 BEING ADDED.
 NEC 220.87, 220 PART II, III, IV.
  
 6) NOTE: PLEASE SEE 220.43A FOR SHOWS WINDOWS AND THE
 AMOUNT OF LOAD REQUIRED FOR SERVICE. THE LOAD SHOWN ON
 PANEL SCHEDULE IS THE LOADS PER 220.14G WHICH IS THE
 BRANCH CIRCUIT.
  
 7) NOTE: PLEASE COMPLETE PLANS/PANEL SCHEDULE FOR
 SHUNT/SHUT DOWN OF ALL ELECTRICAL UNDER HOOD. NFPA-96
 FOR EXAMPLE: PLEASE SEE THE HOOD LIGHTS DO NOT INDICATE
 SHUNT BREAKER?
  
 8) NOTE: PLEASE SUBMIT A COMPLETE LIGHTING CONTROL
 SYSTEM SHOWING ALL OVER RIDE LOCATIONS AND ALL OVER
 RIDE DEVICES FOR GENERAL LIGHTING AS WELL AS OTHER
 ACCENT/DECRETIVE LIGHTING ETC.
 PLEASE BE SURE TO ALSO SEE THE SECTION FOR EXTERIOR
 LIGHTING CONTROLS.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 EXTERIOR PER 13-415.1.ABC.1.4.
  
 9) NOTE: PLEASE SUBMIT A COMPLETED LIGHTING FIXTURE
 LEGEND. PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE KNOW THE FIXTURE SCHEDULE MUST BE COMPLETE AT
 THIS TIME FOR LIGHTING PERFORMANCE VERIFICATION.
 ** AREAS AND ROOMS NOTED ON THE LIGHTING CONTROL PANEL
 DOES NOT COORDINATE WITH ANY ROOMS DESIGNATED ON PLANS.
  
 10) NOTE: PLEASE SEE THE CODES NOTED ON PLANS SHALL BE
 CODES ADOPTED BY THE FBC 2004 W/2007 REVISION PER FS
 553.73.
 PLEASE SEE THE JURISDICTION FOR EXAMPLE NOTES ROYAL
 PALM BEACH HOWEVER JOB LOCATION IS IN THE CITY OF WEST
 PALM BEACH. (MISPRINT).
  
 11) NOTE: PLEASE SEE THE APPLIED VALUE SHALL INCLUDE
 ALL LABOR, MATERIALS, EQUIPMENT, DEISGN COSTS ETC PER
 FBC 108.3 EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. THE VALUE FOR SCOPE OF WORK AS SHOWN IS LOW.
  
  
  
 ** IT IS IMPORTANT TO UNDERSTAND AS THERE ARE SOME
 ITEMS NOT YET SUBMITTED OR SHOWN FOR REVIEW THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  