Plan Review Notes
Plan Review Notes For Permit 08090617
Permit Number 08090617
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-09 14:13:41RESIDENTIAL (R3) SCREEN ENCLOSURE, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- A) ENGINEER'S DRAWING FOR THE SKYLIGHT ATTACHMENT TO
 THE ROOF PANEL NEEDS TO HAVE ORIGINAL ENGINEER'S SEAL
 AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE AND SEC. 61G15-23.002 OF FLORIDA ENGINEERS
 ADMINISTRATIVE CODE. THIS DRAWING IS NOT PART OF THE
 PRODUCT APPROVAL SUBMITTED. THEREFORE, ORIGINAL
 SIGNATURE AND SEAL IS REQUIRED.
  
 B) PLEASE MAKE SURE ENGINEER INFORMATION, INCLUDING
 LICENSE NUMBER IS LEGIBLE.
  
 2- ACCORDING TO SKYLIGHT PRODUCT APPROVAL FL2442
 SKYLIGHT MODELS SF ARE REQUIRED TO HAVE A MINIMUM ROOF
 PITH OF 3:12.. SKYLIGHT FL2442.13 SPECIFIED BY THE
 ENGINEER IS A SF MODEL. SPECIFY ROOF PITCH ON PLANS TO
 VERIFY COMPLIANCE WITH THIS PRODUCT APPROVAL
 REQUIREMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712