Plan Review Notes For Permit 08090596 |
Permit Number |
08090596 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-01-10 10:13:17 | REVISED M1. NOTE: TRANSFER DUCTS IN SOME AREAS ARE NOT | | SIZED TO MEET THE EXCEPTIONS UNDER FBCM 601.4. THESE | | AREAS WILL REQUIRE A FIELD TEST TO VERIFY PRESSURE | | DIFFERENCES ACROSS CLOSED DOORS ARE LESS THAN 0.01" WC | | IN ACCORDANCE WITH THIS SECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|