Plan Review Notes
Plan Review Notes For Permit 08090596
Permit Number 08090596
Review Stop M
Sequence Number 3
Notes
Date Text
2009-01-10 10:13:17REVISED M1. NOTE: TRANSFER DUCTS IN SOME AREAS ARE NOT
 SIZED TO MEET THE EXCEPTIONS UNDER FBCM 601.4. THESE
 AREAS WILL REQUIRE A FIELD TEST TO VERIFY PRESSURE
 DIFFERENCES ACROSS CLOSED DOORS ARE LESS THAN 0.01" WC
 IN ACCORDANCE WITH THIS SECTION.
  