2008-10-08 10:42:56***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) IS THIS PROJECT CURRENTLY PROTECTED BY AN AUTOMATIC
 FIRE SPRINKLER SYSTEM?
  
 4) PROVIDE LOCATION(S) OF REQUIRED 2A-10B,C RATED FIRE
 EXTINGUISHERS.
  
 5) THE EXIT SIGN LOCATED NEXT TO OFFICE #1 APPEARS TO
 BE DIRECTIONAL. WHAT WOULD PREVENT PERSONS FROM EXITING
 INTO THE CONFERENCE ROOM AND NOT THROUGH THE 3'-0"
 OPENING?
  
 6) PLEASE SEE OTHER REVIEW COMMENTS REGARDING FS AND
 FAC REQUIREMENTS FOR PLANS.
  
 7) PLANS INDICATE A RELOCATED FIRE ALARM AND
 THERMOSTAT, BUT DOES NOT INDICATE WHAT THE FIRE ALARM
 EQUIPMENT IS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW