| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK |
| MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 |
| FAC. |
| |
| 2} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE |
| 13-415.1ABC.1.1FOR TIME CLOCK REQUIREMENTS AND FOR |
| LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE |
| ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE |
| REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE |
| CALCULATION PROCEDURES, GENERAL. |
| THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED |
| INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH |
| SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR |
| LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE |
| DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE |
| SCHEDULE TO CORRELATE WITH THE ONES IN THE |
| CALCULATIONS.THE PLAN INDICATES NEW LIGHTING. |
| |
| 3} THE PANEL SCHEDULE SCHEDULE MUST COMPLY WITH 408.4 |
| AND BE ROOM SPECIFIC. |
| |
| 4} THE EMERGENCY LIGHTING MUST COMPLY WITH 700.12(F)-" |
| THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES." A NOTE ON THE PLAN WILL SATISFY THIS |
| REQUIREMENT. |
| |
| 5} THERE IS A RECEPTACLE SHOWN AT THE NEW WATER HEATER |
| LOCATION. SEE 422.16 FLEXIBLE CORDS |
| (A) GENERAL FLEXIBLE CORD SHALL BE PERMITTED (1) FOR |
| THE CONNECTION OF APPLIANCES TO FACILITATE THEIR |
| FREQUENT INTERCHANGE OR TO PREVENT THE TRANSMISSION OF |
| NOISE OR VIBRATION OR (2) TO FACILITATE THE REMOVAL OR |
| DISCONNECTION OF APPLIANCES THAT ARE FASTENED IN PLACE, |
| WHERE THE FASTENING MEANS AND MECHANICAL CONNECTIONS |
| ARE SPECIFICALLY DESIGNED TO PERMIT READY REMOVAL FOR |
| MAINTENANCE OR REPAIR AND THE APPLIANCE IS INTENDED OR |
| IDENTIFIED FOR FLEXIBLE CORD CONNECTION. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |