Plan Review Notes
Plan Review Notes For Permit 08090596
Permit Number 08090596
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-03 10:34:47 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1ABC.1.1FOR TIME CLOCK REQUIREMENTS AND FOR
 LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE
 ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.THE PLAN INDICATES NEW LIGHTING.
  
 3} THE PANEL SCHEDULE SCHEDULE MUST COMPLY WITH 408.4
 AND BE ROOM SPECIFIC.
  
 4} THE EMERGENCY LIGHTING MUST COMPLY WITH 700.12(F)-"
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES." A NOTE ON THE PLAN WILL SATISFY THIS
 REQUIREMENT.
  
 5} THERE IS A RECEPTACLE SHOWN AT THE NEW WATER HEATER
 LOCATION. SEE 422.16 FLEXIBLE CORDS
 (A) GENERAL FLEXIBLE CORD SHALL BE PERMITTED (1) FOR
 THE CONNECTION OF APPLIANCES TO FACILITATE THEIR
 FREQUENT INTERCHANGE OR TO PREVENT THE TRANSMISSION OF
 NOISE OR VIBRATION OR (2) TO FACILITATE THE REMOVAL OR
 DISCONNECTION OF APPLIANCES THAT ARE FASTENED IN PLACE,
 WHERE THE FASTENING MEANS AND MECHANICAL CONNECTIONS
 ARE SPECIFICALLY DESIGNED TO PERMIT READY REMOVAL FOR
 MAINTENANCE OR REPAIR AND THE APPLIANCE IS INTENDED OR
 IDENTIFIED FOR FLEXIBLE CORD CONNECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  