2008-10-03 16:36:00 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET P-1, LAUNDRY PROPOSED FIRST FLOOR PLUMBING |
| PLAN AND SANITARY RISER DIAGRAM: THE WASHING MACHINE |
| CAN NOT DRAIN INTO THE WET VENTED BATHROOM GROUP OF |
| BATH 1 IT MUST DRAIN DOWNSTREAM OF THE BATHROOM GROUP. |
| PER FBC-2004 PLUMBING SECTION 909.1 WET VENT PERMITTED. |
| |
| 2. SHEET P-1, KITCHEN SANITARY RISER DIAGRAM: THE |
| DISHWASHER REQUIRES A DRAIN. THE DISHWASHER SHALL |
| DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF |
| THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD |
| WASTE GRINDER. PER FBC-2004 PLUMBING SECTION 802.1.6 |
| DOMESTIC DISHWASHING MACHINES. |
| |
| 3. SHEET P-1, SANITARY RISER DIAGRAM: A CLEANOUT IS |
| REQUIRED AT THE BASE OF THE SOIL STACK TO THE SECOND |
| FLOOR PROPOSED PLUMBING. PER FBC-2004 PLUMBING SECTION |
| 708.3.4 BASE OF STACK. |
| |
| 4. SHEET P-2, BATH 4, PROPOSED SECOND FLOOR PLUMBING |
| PLAN AND SANITARY RISER DIAGRAM: THE BATH TUB IS NOT |
| VENTED AND REQUIRES A VENT. PER FBC-2004 PLUMBING |
| SECTION 901.2.1 VENTING REQUIRED. |
| |
| 5. SHEET P-2, MASTER BATH PROPOSED SECOND FLOOR |
| PLUMBING PLAN AND SANITARY RISER DIAGRAM: THE SHOWER |
| REQUIRES A VENT. PLEASE KNOW THAT THE SHOWER IS 9'-6" |
| FROM THE VENT. PER FBC-2004 PLUMBING TABLE 906.1, A 2" |
| TRAP WITH A 2" FIXTURE DRAIN CAN ONLY BE 6' FROM THE |
| VENT. |
| |
| 6. NOTE: PLEASE KNOW THAT ALL SINKS AND LAVATORIES ON |
| SHEET P-1 AND P-2 SANITARY RISER DIAGRAMS ARE BEING |
| INDICATED WITH AN 1/2" WATER-SEAL TRAP. PLEASE KNOW |
| THAT PER FBC-2004 PLUMBING TABLE 709.1 MINIMUM SIZE OF |
| WATER SEAL TRAPS FOR A LAVATORY IS 1-1/4" AND A SINK IS |
| 1-1/2". |
| |
| 7. SHEET P-1 SANITARY RISER DIAGRAM: CLEARLY INDICATE |
| THE CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND |
| BUILDING SEWER AS BEING A TWO-WAT CLEANOUT. PER |
| FBC-2004 PLUMBING SECTION 708.3.5 BUILDING DRAIN AND |
| BUILDING SEWER JUNCTION. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |