2008-10-03 09:24:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C EQUIPMENT
 SCHEDULE ARE FOR AMERICAN STANDARD SYSTEMS NOT TRANE
 AND ARE 13 SEER NOT 17 SEER PLEASE SEE ARI DIRECTORY
 WEB-SITE AND ATTACHED PRINT OUTS, PLEASE CORRECT PLANS
 AND OR ENERGY CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.3.1.1.
  
 2) PLEASE PROVIDE COMBUSTION AIR OR MAKE UP AIR FOR THE
 GAS CLOTHES DRYER IN THE LAUNDRY ROOM AS IT APPEARS TO
 BE A CONFINED SPACE, SEE 2004 FBC/R G2407.1, G2407.4
 AND G2407.5.1.
  
 3) PLEASE SHOW ON PLAN M-1 THE SUPPLY AIR DUCT (FLEX)
 SIZE FROM AH-1 TO THE FOYER, THE TWO DUCTS IN THE
 LIVING ROOM AND THE DUCT TO THE POWER ROOM. ON PLAN M-2
 THE SUPPLY AIR DUCT FROM THE MIXING BOX TO THE MASTER
 CLOSET (SEE YELLOW HIGH LIGHT ON PLAN), PER 2004 FBC/R
 M1601.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]