Date |
Text |
2008-10-06 09:11:58 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET P-2 GAS ISOMETRIC RISER DIAGRAM: SUBMIT AN |
| ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL CUT SECTIONS |
| OF PIPE AND CORRESPONDING LENGTHS PER FBC-2004 FUEL GAS |
| CODE SECTION 401.1 SCOPE AND THE CITY OF WEST PALM |
| BEACH GAS PERMIT APPLICATION REQUIREMENTS. |
| *NOTE: THE SUBMITTED GAS ISOMETRIC ON SHEET P-2, DOES |
| NOT INDICATE CORRESPONDING LENGTHS TO ALL CUT SECTION |
| OF PIPE. PLEASE KNOW THE THE INDICATED LONGEST RUN FOR |
| THE 0.5 PSI SYSTEM IS 70' HOWEVER THE ADDED SUM OF THE |
| INDICATED CORRESPONDING LENGTHS IS 64' AND THAT NOT ALL |
| CORRESPONDING LENGTHS ARE BEING INDICATED. THIS IS ALSO |
| TRUE FOR THE 2 PSI SYSTEM, THE ADDED SUM OF THE |
| INDICATED CORRESPONDING LENGTHS IS 125' AND THIS ALSO |
| DOES NOT HAVE ALL CORRESPONDING LENGTHS BEING |
| INDICATED. PLEASE KNOW IF THERE IS A CUT SECTION OF |
| PIPE IT MUST HAVE A CORRESPONDING LENGTH INDICATED FOR |
| IT. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT |
| SECTIONS WITH NO CORRESPONDING LENGTH BEING INDICATED |
| FOR THEM. |
| |
| 2. SHEET P-2 GAS RISER DIAGRAM: PLEASE KNOW THAT TABLE |
| 402.4 (4) IS THE WRONG TABLE FOR A 0.5 PSI NATURAL GAS |
| DELIVERY PRESSURE. PLEASE KNOW THAT GAS TABLE 402.4 (4) |
| IS FOR A 5 PSI NATURAL GAS DELIVERY PRESSURE NOT A 0.5 |
| PSI NATURAL GAS DELIVERY PRESSURE. PLEASE KNOW THAT THE |
| CORRECT TABLE FOR A 0.5 NATURAL GAS DELIVERY PRESSURE |
| THAT NEEDS TO BE INDICATED ON THE RESUBMITTAL IS TABLE |
| 402.4 (2). |
| |
| 3. SHEET A-2 PROPOSED FIRST FLOOR PLAN: THE 48" GAS |
| RANGE IS INCORRECTLY BEING INDICATED AS A 48" REF. |
| PLEASE CORRECT THIS ON THE RESUBMITTAL PER FBC-2004 |
| FUEL GAS SECTION 401.1 SCOPE. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |