Plan Review Notes
Plan Review Notes For Permit 08090594
Permit Number 08090594
Review Stop G
Sequence Number 1
Notes
Date Text
2008-10-06 09:11:58GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-2 GAS ISOMETRIC RISER DIAGRAM: SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL CUT SECTIONS
 OF PIPE AND CORRESPONDING LENGTHS PER FBC-2004 FUEL GAS
 CODE SECTION 401.1 SCOPE AND THE CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS.
 *NOTE: THE SUBMITTED GAS ISOMETRIC ON SHEET P-2, DOES
 NOT INDICATE CORRESPONDING LENGTHS TO ALL CUT SECTION
 OF PIPE. PLEASE KNOW THE THE INDICATED LONGEST RUN FOR
 THE 0.5 PSI SYSTEM IS 70' HOWEVER THE ADDED SUM OF THE
 INDICATED CORRESPONDING LENGTHS IS 64' AND THAT NOT ALL
 CORRESPONDING LENGTHS ARE BEING INDICATED. THIS IS ALSO
 TRUE FOR THE 2 PSI SYSTEM, THE ADDED SUM OF THE
 INDICATED CORRESPONDING LENGTHS IS 125' AND THIS ALSO
 DOES NOT HAVE ALL CORRESPONDING LENGTHS BEING
 INDICATED. PLEASE KNOW IF THERE IS A CUT SECTION OF
 PIPE IT MUST HAVE A CORRESPONDING LENGTH INDICATED FOR
 IT. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT
 SECTIONS WITH NO CORRESPONDING LENGTH BEING INDICATED
 FOR THEM.
  
 2. SHEET P-2 GAS RISER DIAGRAM: PLEASE KNOW THAT TABLE
 402.4 (4) IS THE WRONG TABLE FOR A 0.5 PSI NATURAL GAS
 DELIVERY PRESSURE. PLEASE KNOW THAT GAS TABLE 402.4 (4)
 IS FOR A 5 PSI NATURAL GAS DELIVERY PRESSURE NOT A 0.5
 PSI NATURAL GAS DELIVERY PRESSURE. PLEASE KNOW THAT THE
 CORRECT TABLE FOR A 0.5 NATURAL GAS DELIVERY PRESSURE
 THAT NEEDS TO BE INDICATED ON THE RESUBMITTAL IS TABLE
 402.4 (2).
  
 3. SHEET A-2 PROPOSED FIRST FLOOR PLAN: THE 48" GAS
 RANGE IS INCORRECTLY BEING INDICATED AS A 48" REF.
 PLEASE CORRECT THIS ON THE RESUBMITTAL PER FBC-2004
 FUEL GAS SECTION 401.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved