 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122.
  
 2} PER 210.52(B)(2) NO OTHER OUTLETS THE TWO OR MORE
 SMALL-APPLIANCE BRANCH CIRCUITS SPECIFIED IN
 210.52(B)(1) SHALL HAVE NO OTHER OUTLETS. PER
 210.52(B)(1) CIRCUIT 35 PANEL "A", DINING ROOM IS
 REQUIRED TO BE A SMALL APPLIANCE CIRCUIT AND THEREFORE
 IS REQUIRED TO BE A 20 AMP AND THE LIGHTS CANNOT BE ON
 THAT CIRCUIT.
  
 3} CIRCUITS 37,39 PANEL "A" AH #1, 10.5KW DOES NOT
 CORRELATE WITH SHEET M-1 SCHEDULES INDICATING THAT UNIT
 TO HAVE 8KW HEAT. THE OCP IS TOO LARGE TO PROTECT THE
 UNIT- 8000/240=33.33X125%=41.6 AMPS.
  
 4} THE DISCONNECTS FOR THE CONDENSING UNITS AND POOL
 EQUIPMENT ARE IN VIOLATION OF 110.26 CLEARANCE
 REQUIREMENTS.
  
 5} RECEPTACLES NEED TO BE ADDED OR RELOCATED IN THE
 STUDY, DINING ROOM, GUEST ROOM, BEDROOMS 2 & 3, TO
 COMPLY WITH 210.52(A)(1) AND 210.52(A)(2). 2005 NEC.
 SEE REVIEWED PLAN FOR DEFICIENCIES.
  
 6} 210.52(H) HALLWAYS IN DWELLING UNITS, HALLWAYS OF
 3.0 M (10 FT) OR MORE IN LENGTH SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET. SEE "M HALL", SHEET E-2.
  
 7} THERE IS A SYMBOL IN THE LEGEND FOR A COMBINATION
 SMOKE/CARBON MONOXIDE DETECTOR, BUT IT APPEARS THE
 SPEAKER SYMBOL WAS USED IN ERROR. CHECK REQUIRED SMOKE
 ALARM AND CARBON MONOXIDE ALARM LOCATIONS AND CORRECT
 THE SYMBOLS.
 NOTE: 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.
 NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE.
  
 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.SHEET A-0 LISTS OUT OF DATE CODES.
  