Date |
Text |
2009-04-13 16:44:42 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| ******FROM PREVIOUS REVIEWS: |
| |
| ********FROM PREVIOUS REVIEWS: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| |
| 5. OK |
| |
| ___FOR SINKS: |
| A. OK |
| B. OK |
| C. 11-4.24.4 SINK DEPTH (PROVISO) |
| D. OK |
| E. OK |
| F. OK |
| G. OK |
| |
| 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE |
| INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT |
| WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS |
| BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR |
| OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 & |
| 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE |
| COMMENT RESPONSES TO THESE QUESTIONS. |
| ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT THE SECTION OF THE COMMENT |
| ABOUT WHAT WILL HAPPEN TO THE WATER, (AND NOW THE MUD), |
| HAS NOT BEEN ADDRESSED. THERE IS NO INDICATION OF HOW |
| THE WALLS WILL BE PROTECTED FROM THE STANDING WATER IN |
| THE MAINTENANCE BUILDING, NO INDICATION OF SLOPING OF |
| THE FLOORS AWAY FROM THE WALLS, NO WALL FINISH SCHEDULE |
| INDICATING WATER PROOFING OF WALLS ETC. SECTION 301.2 |
| SYSTEM INSTALLATION. PLUMBING SHALL BE INSTALLED WITH |
| DUE REGARD TO PRESERVATION OF THE STRENGHT OF |
| STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE TO WALLS |
| AND OTHER SURFACES THROUGH FIXTURE USAGE. PLEASE |
| CLARIFY. |
| ********NO WRITTEN RESPONSE. COMMENT TO BE ADDRESSED |
| WITH A SIGNED, SEALED COMMENT RESPONSE TO THE ABOVE |
| COMMENT. THE FINISH SCHEDULE FOR THE MAINTENANCE |
| BUILDING INDICATE P-1 FININSH. PLEASE INDICATE WHAT P-1 |
| FINISH IS AND WHERE IN THE PLANS THIS CAN BE FOUND. THE |
| ARCHITECT OR ENGINEER OF RECORD WILL BE REQUIRED TO |
| TAKE RESPONSIBILITY FOR THE CODE SECTION 301.2. |
| |
| 7. OK |
| |
| 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS |
| SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER |
| HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE |
| MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS |
| REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR |
| OFFICE ROOM 102. SECTION 606.2(2). |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST |
| WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE |
| PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS |
| NEAR THE FIXTURES, NOT IN THE CEILING. |
| ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS |
| ARE STILL SHOWN IN THE CEILING AND NOT DOWN NEAR THE |
| FIXTURES IN AN "EFFECTIVE RANGE" AS REQUIRED. |
| ********NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 9. OK |
| 10. OK |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |