2009-05-29 10:14:04*** NOTES/ REDLINES****
  
 1) NOTE: MANUFACTURES SPECS/CUT SHEETS WERE SUBMITTED
 FOR THREE COMPLETELY DIFFERENT TRANSFER SWITCHES.
 A) ONE AS AUTOMATIC NON SERVICE ENTRANCE RATED.
 B) ONE FOR NON-AUTOMATIC, MTS.
 C) ONE FOR SERVICE ENTRANCE RATE AUTOMATIC TRANSFER
 SWITCH.
  
 AS THE RISER INDICATES AND REQUIRES THE SWITCH TO BE
 SERVICE ENTRANCE RATED ONLY *(C) * ABOVE MEETS AND
 COORDINATES WITH RISER.
  
 THE SPECS/CUT SHEETS FOR BOTH A AND B WAS REMOVED FROM
 SETS TO ALLEVIATE ANY CONFUSION.
  
 2) NOTED FOR INFORMATION. THE NEW BUILDING OFFICIAL
 WILL BE REQUIRING THE MAINTENANCE/OPERATION BUILDING TO
 BE UNDER SEPARATE PERMIT. THE SAME PLANS WILL BE USED ,
 HOWEVER WILL NEED SEPARATE APPLICATION. PLEASE CONTACT
 DOUGLAS WISE FOR ANY QUESTIONS. 561-805-6654
  
 3) NOTE: GATE SHALL BE UNDER SEPARATE FENCE PERMIT
 ALONG WITH PLANS.
  
 4) NOTE: LOW VOLTAGE SYSTEMS SUCH AS DATE, PHONE, AND
 CAMERAS ALL SHALL BE UNDER SEPARATE PERMITS. ** MAY
 REFERENCE THESE PLANS IF NO CHANGES ARE MADE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  