Plan Review Notes For Permit 08090593 |
Permit Number |
08090593 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2009-05-29 10:14:04 | *** NOTES/ REDLINES**** | | | | 1) NOTE: MANUFACTURES SPECS/CUT SHEETS WERE SUBMITTED | | FOR THREE COMPLETELY DIFFERENT TRANSFER SWITCHES. | | A) ONE AS AUTOMATIC NON SERVICE ENTRANCE RATED. | | B) ONE FOR NON-AUTOMATIC, MTS. | | C) ONE FOR SERVICE ENTRANCE RATE AUTOMATIC TRANSFER | | SWITCH. | | | | AS THE RISER INDICATES AND REQUIRES THE SWITCH TO BE | | SERVICE ENTRANCE RATED ONLY *(C) * ABOVE MEETS AND | | COORDINATES WITH RISER. | | | | THE SPECS/CUT SHEETS FOR BOTH A AND B WAS REMOVED FROM | | SETS TO ALLEVIATE ANY CONFUSION. | | | | 2) NOTED FOR INFORMATION. THE NEW BUILDING OFFICIAL | | WILL BE REQUIRING THE MAINTENANCE/OPERATION BUILDING TO | | BE UNDER SEPARATE PERMIT. THE SAME PLANS WILL BE USED , | | HOWEVER WILL NEED SEPARATE APPLICATION. PLEASE CONTACT | | DOUGLAS WISE FOR ANY QUESTIONS. 561-805-6654 | | | | 3) NOTE: GATE SHALL BE UNDER SEPARATE FENCE PERMIT | | ALONG WITH PLANS. | | | | 4) NOTE: LOW VOLTAGE SYSTEMS SUCH AS DATE, PHONE, AND | | CAMERAS ALL SHALL BE UNDER SEPARATE PERMITS. ** MAY | | REFERENCE THESE PLANS IF NO CHANGES ARE MADE. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|