Plan Review Notes
Plan Review Notes For Permit 08090593
Permit Number 08090593
Review Stop P
Sequence Number 3
Notes
Date Text
2009-03-26 08:47:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. OK
  
 ___FOR SINKS:
 A. OK
 B. OK
 C. 11-4.24.4 SINK DEPTH (PROVISO)
 D. OK
 E. OK
 F. OK
 G. OK
  
 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT
 WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS
 BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR
 OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 &
 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE
 COMMENT RESPONSES TO THESE QUESTIONS.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE SECTION OF THE COMMENT
 ABOUT WHAT WILL HAPPEN TO THE WATER, (AND NOW THE MUD),
 HAS NOT BEEN ADDRESSED. THERE IS NO INDICATION OF HOW
 THE WALLS WILL BE PROTECTED FROM THE STANDING WATER IN
 THE MAINTENANCE BUILDING, NO INDICATION OF SLOPING OF
 THE FLOORS AWAY FROM THE WALLS, NO WALL FINISH SCHEDULE
 INDICATING WATER PROOFING OF WALLS ETC. SECTION 301.2
 SYSTEM INSTALLATION. PLUMBING SHALL BE INSTALLED WITH
 DUE REGARD TO PRESERVATION OF THE STRENGHT OF
 STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE TO WALLS
 AND OTHER SURFACES THROUGH FIXTURE USAGE. PLEASE
 CLARIFY.
  
 7. OK
  
 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE
 MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS
 REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR
 OFFICE ROOM 102. SECTION 606.2(2).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST
 WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE
 PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS
 NEAR THE FIXTURES, NOT IN THE CEILING.
 ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS
 ARE STILL SHOWN IN THE CEILING AND NOT DOWN NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" AS REQUIRED.
  
 9. OK
 10. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  