2009-04-06 14:29:56 | BUILDING PLAN REVIEW |
| PERMIT: 08090593 |
| ADD: 6880 N JOG RD |
| CONT:MAJOR WORKING DRAWING REVIEW |
| TEL: (772)231-4301 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 08090593 6880 N. JOG RD. OFFICE BUILDING TYPE II-B |
| 1,800 SQ FT |
| 6890 N. JOG RD. S-2 MAINTENANCE BUILDING TYPE II-B |
| 1,000 SQ FT |
| 6882 N JOG RD. PAVILION TYPE II-B 728 SQ FT. |
| |
| THE BUILDING OFFICIAL HAS REQUESTED THAT 3 SEPERATE |
| PERMIT APPLICATIONS WITH SEPERATE TRACKING NUMBERS AND |
| ADDREESSES BE ASIGNED TO ALLOW FOR THE MULTIPLE |
| INSPECTIONS THAT WILL BE REQUIRED FOR EACH BUILDING, |
| AND SEPERATE TRACKING OF INSPECTIONS. |
| |
| THE TWO SETS OF PLANS AND BACK UP DOCUMENTATION WILL BE |
| ALL THAT IS NEEDED, THE (MASTER 08090593)) PERMIT |
| NUMBER WILL HAVE ALL THE REVIEW DOCUMENTATION. |
| |
| 1-12) COMPLIED. |
| |
| 13) THIRD REQUEST, 1ST UNDER PERMIT APPLICATION. THE |
| RESPONSE COMMENTS INDICATE THIS TO BE A PAVILION, TO BE |
| PART OF THIS PERMIT WE DO NEED INFORMATION AS FAR AS |
| COMPONENTS AND CLADDING YOU INDICATE THIS IS A |
| PRE-ENGINEERED CANOPY, EITHER IT HAS GONE THROUGH THE |
| MANUFACTURED BUILDING PROGRAM WITH THE STATE AND IS |
| APPROVED AS A MANUFACTURED MODULAR BUILDING PROGRAM |
| WITH STATE APPROVED PLANS OR IT WILL NEED PRODUCT |
| APPROVALS FOR THE ROOFING ASSEMBLY. WITHOUT PLANS THIS |
| AREA WILL BE EXEMPTED FROM THE PERMIT AND PLANS TO BE |
| SUBMITTED UNDER A SEPERATE PERMIT. |
| 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| YOUR RESPONCE AS TO SECTION 503.1.1 DEALS WITH SQUARE |
| FOOTAGE OF FIRE AREA AND THERE NOT BEING REQUIREMENTS |
| FOR RATED WALLS BEING BUILDINGS AND OPENING |
| PROTECTIVES. ONE ISSUE THAT WE HAVE IS WITH NO PLANS, |
| NO STRUCTURAL COLUMNS, BEAMS NOR ROOF SHEATHING IS |
| PROVIDED. THE ROOFING PRODUCT APPROVAL SUBMITTED 2004 |
| FL 3778-R1 |
| IS FOR NON-STRUCTURAL ROOF METAL, REQUIRING |
| SUBSHEATHING DECK. 1507.4.1. |
| |
| 14-17) COMPLIED. |
| |
| 18) 3RD REQUEST. SHEET S-4 INDICATES A FOOTING TYPE A |
| BUT THE PLANS ARE LACKING COLUMN AND BEAM INFORMATION, |
| 1609.2.1 PART OFTHE MAIN WIND FORCE-RESISTING SYSTEM. |
| PLEASE PROVIDE ADDITONAL INFORMATION, 106.1..2. 106.3.5 |
| MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| |
| 19) 3 RD REQUEST, SHEET A-4 ALSO INDICATES THE ROOFING |
| ASSEMBLY TO BE A PREMANUFACTRED CANOPY, PLEASE PROVIDE |
| PRODUCT INFORMATION, TO BE PART OF THIS PERMIT WE DO |
| NEED INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU |
| INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS |
| GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE |
| STATE AND IS APPROVED AS A MANUFACTURED MODULAR |
| BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL |
| NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. |
| WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE |
| PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE |
| PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| |
| 20)2 COMPLIED. |
| |
| 21)INFORMATIONAL: GENERATOR PAD IS SHOWN ON SHEET SD-1, |
| IS THIS PAD AND GENERATOR AND ATTACHMENT TO SLAB WILL |
| BE REVIEWED UNDER A SEPERATE PERMIT. 1609.1.3 ANCHORAGE |
| AGAINST OVERTURNING, UPLIFT AND SLIDDING. ANCHORAGE |
| AGAINST OVERTURNING IS NOT THE RESPONSIBILITY OF THE |
| GENERATOR MANUFACTURER BUT THE DESIGNER OF RECORD. |
| |
| 22) STAIR DELETED, COMPLIED. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |