Plan Review Notes
Plan Review Notes For Permit 08090593
Permit Number 08090593
Review Stop P
Sequence Number 2
Notes
Date Text
2009-01-27 10:44:07DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SUBMIT DETAILS FOR THE ACCESSIBLE FIXTURES SHOWING
 COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR DRINKING FOUNTAIN:
 A. OK
  
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOW IN TOILET ROOMS 120 & 121.
 B. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT NO INDICATION OF THE
 REQUIREMENT FOR CONTROLS TO THE WIDE SIDE OF THE
 TOILET.
 C. W/C TO BE 18" OFF THE WALL TO THE C/L OF THE
 FIXTURE. FIGURES 28 AND 30E.
 ****RESPONSE NOTED, BUT THE W/C'S IN TOILET ROOMS 120 &
 121 NOT ADDRESSED.
  
 ___FOR URINALS:
 A. OK
 B. OK
  
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOW IN TOILET ROOMS 120 & 121.
 B. 11-4.19 4 EXPOSED PIPES & SURFACES
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 C. OK
 D. LAVS TO BE A MINIMUM 15" OFF WALL TO C/L OF FIXTURE.
 FIG. 32.
 ****RESPONSE NOTED, BUT THE LAV'S IN TOILET ROOMS 120 &
 121 NOT ADDRESSED.
  
 ___FOR SHOWERS:
 A. 11-4.21.2 SIZE & CLEARANCES
 ****NO RESPONSE, COMMENT NOT ADDRESSED
 B. 11-4.21.3 SEAT
 ****HEIGHT NOT INDICATED.
 C. 11-4.21.4 GRAB BARS
 ****NOT SHOWN AS REQUIRED IN FIGURE 37. ALSO SHOW THE
 HEIGHT.
 D. 11-4.21.5 CONTROLS
 ****THE LOCATION OF THE CONTROLS NOT SHOWN.
 E. 11-4.21.6 SHOWER UNIT
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 F. 11-4.21.7 CURBS
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ___FOR TOILET ROOMS:
 A. 11-4.22.2 DOOR SWING
 ****NO RESPONSE, COMMENT NOT ADDRESSED FOR TOILET ROOMS
 120 & 121.
 B. 11-4.22.3 TURNING AREA
 ****NO RESPONSE, COMMENT NOT ADDRESSED FOR TOILET ROOMS
 120 & 121.
  
 ___FOR BATHROOMS:
 A. OK
 B. OK
  
  
 ********** NOTE: PER SECTION 11-4.1.3(11) IF TOILET
 ROOMS ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE
 TOILET ROOM SHALL COMPLY WITH SECTION 11-4.22. COMMENT
 RESPONSE "IT SHOULD BE NOTED THAT TOILET ROOMS 120 &
 121 ARE NOT INTENDED TO ACCOMMODATE THE PHYSICALLY
 DISABLED" IS NOT ACCEPTABLE. PLEASE SHOW COMPLIANCE.
  
 ___FOR SINKS:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT APPROVED.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 G, 11-4.2.3 AN UNOBSTRUCTED TURNING AREA
 ****NO RESPONSE TO A THRU G AND COMMENTS NOT ADDRESSED.
 THIS IS FOR THE KITCHEN/BREAK ROOM. SUBMIT AN ELEVATION
 DETAIL SHOWING ALL INFORMATION REQUIRED.
  
 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT
 WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS
 BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR
 OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 &
 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE
 COMMENT RESPONSES TO THESE QUESTIONS.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 7. OK
  
 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE
 MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS
 REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR
 OFFICE ROOM 102. SECTION 606.2(2).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST
 WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE
 PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS
 NEAR THE FIXTURES, NOT IN THE CEILING.
  
 9. SHT PD-1 EWH-1 WATER HEATER DETAIL STATES "EXPANSION
 TANK SEE SPECIFICATIONS". SPECIFICATIONS WERE NOT
 SUBMITTED. PLEASE SUBMIT CALCULATIONS OR MANUF. CHART
 INDICATING THE MODEL AND CORRECT SIZING OF THE
 EXPANSION TANK. SECTION 607.3.2.
 ****RESPONSE NOTED, BUT THE ATTACHED MANUFACTURER'S
 SIZING GUIDELINES WERE NOT FOUND. PLEASE INDICATE WHERE
 THE GUIDELINES WERE ATTACHED AND CAN BE LOCATED.
  
 10. SHT PD-1 A FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED
 FOR THE P&T RELIEF VALVE AND EMERGENCY PAN DRAIN LINES.
 SECTIONS 504.6.1, 504.7.2, 802.3 & 802.3.2. THE
 INDIRECT WASTE RECEPTOR SHALL BE LOCATED NEAR THE WATER
 HEATER SO THE RELIEF AND PAN DRAIN LINES DO NOT PRESENT
 A TRIPPING HAZARD.
 ****RESPONSE NOTED, BUT THE FLOOR DRAIN IS STILL NOT AN
 APPROVED INDIRECT WASTE RECEPTOR. COMMENT NOT COMPLETLY
 ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS