2009-01-27 10:44:07 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| |
| 5. SUBMIT DETAILS FOR THE ACCESSIBLE FIXTURES SHOWING |
| COMPLIANCE WITH THE FOLLOWING: |
| |
| ___FOR DRINKING FOUNTAIN: |
| A. OK |
| |
| ___FOR W/C'S: |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| SHOW IN TOILET ROOMS 120 & 121. |
| B. 11-4.16.5 FLUSH CONTROLS |
| ****RESPONSE NOTED, BUT NO INDICATION OF THE |
| REQUIREMENT FOR CONTROLS TO THE WIDE SIDE OF THE |
| TOILET. |
| C. W/C TO BE 18" OFF THE WALL TO THE C/L OF THE |
| FIXTURE. FIGURES 28 AND 30E. |
| ****RESPONSE NOTED, BUT THE W/C'S IN TOILET ROOMS 120 & |
| 121 NOT ADDRESSED. |
| |
| ___FOR URINALS: |
| A. OK |
| B. OK |
| |
| ___FOR LAVS: |
| A. 11-4.19.3 CLEAR FLOOR SPACE |
| ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| SHOW IN TOILET ROOMS 120 & 121. |
| B. 11-4.19 4 EXPOSED PIPES & SURFACES |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| C. OK |
| D. LAVS TO BE A MINIMUM 15" OFF WALL TO C/L OF FIXTURE. |
| FIG. 32. |
| ****RESPONSE NOTED, BUT THE LAV'S IN TOILET ROOMS 120 & |
| 121 NOT ADDRESSED. |
| |
| ___FOR SHOWERS: |
| A. 11-4.21.2 SIZE & CLEARANCES |
| ****NO RESPONSE, COMMENT NOT ADDRESSED |
| B. 11-4.21.3 SEAT |
| ****HEIGHT NOT INDICATED. |
| C. 11-4.21.4 GRAB BARS |
| ****NOT SHOWN AS REQUIRED IN FIGURE 37. ALSO SHOW THE |
| HEIGHT. |
| D. 11-4.21.5 CONTROLS |
| ****THE LOCATION OF THE CONTROLS NOT SHOWN. |
| E. 11-4.21.6 SHOWER UNIT |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| F. 11-4.21.7 CURBS |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| ___FOR TOILET ROOMS: |
| A. 11-4.22.2 DOOR SWING |
| ****NO RESPONSE, COMMENT NOT ADDRESSED FOR TOILET ROOMS |
| 120 & 121. |
| B. 11-4.22.3 TURNING AREA |
| ****NO RESPONSE, COMMENT NOT ADDRESSED FOR TOILET ROOMS |
| 120 & 121. |
| |
| ___FOR BATHROOMS: |
| A. OK |
| B. OK |
| |
| |
| ********** NOTE: PER SECTION 11-4.1.3(11) IF TOILET |
| ROOMS ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE |
| TOILET ROOM SHALL COMPLY WITH SECTION 11-4.22. COMMENT |
| RESPONSE "IT SHOULD BE NOTED THAT TOILET ROOMS 120 & |
| 121 ARE NOT INTENDED TO ACCOMMODATE THE PHYSICALLY |
| DISABLED" IS NOT ACCEPTABLE. PLEASE SHOW COMPLIANCE. |
| |
| ___FOR SINKS: |
| A. 11-4.24.2 HEIGHT |
| B. 11-4.24.3 KNEE CLEARANCE |
| C. 11-4.24.4 SINK DEPTH |
| D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH |
| REQUIRED. CABINET DOORS NOT APPROVED. |
| E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| F. 11-4.24.7 FAUCETS |
| G, 11-4.2.3 AN UNOBSTRUCTED TURNING AREA |
| ****NO RESPONSE TO A THRU G AND COMMENTS NOT ADDRESSED. |
| THIS IS FOR THE KITCHEN/BREAK ROOM. SUBMIT AN ELEVATION |
| DETAIL SHOWING ALL INFORMATION REQUIRED. |
| |
| 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE |
| INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT |
| WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS |
| BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR |
| OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 & |
| 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE |
| COMMENT RESPONSES TO THESE QUESTIONS. |
| ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| |
| 7. OK |
| |
| 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS |
| SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER |
| HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE |
| MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS |
| REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR |
| OFFICE ROOM 102. SECTION 606.2(2). |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST |
| WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE |
| PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS |
| NEAR THE FIXTURES, NOT IN THE CEILING. |
| |
| 9. SHT PD-1 EWH-1 WATER HEATER DETAIL STATES "EXPANSION |
| TANK SEE SPECIFICATIONS". SPECIFICATIONS WERE NOT |
| SUBMITTED. PLEASE SUBMIT CALCULATIONS OR MANUF. CHART |
| INDICATING THE MODEL AND CORRECT SIZING OF THE |
| EXPANSION TANK. SECTION 607.3.2. |
| ****RESPONSE NOTED, BUT THE ATTACHED MANUFACTURER'S |
| SIZING GUIDELINES WERE NOT FOUND. PLEASE INDICATE WHERE |
| THE GUIDELINES WERE ATTACHED AND CAN BE LOCATED. |
| |
| 10. SHT PD-1 A FLOOR DRAIN IS NOT AN APPROVED INDIRECT |
| WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED |
| FOR THE P&T RELIEF VALVE AND EMERGENCY PAN DRAIN LINES. |
| SECTIONS 504.6.1, 504.7.2, 802.3 & 802.3.2. THE |
| INDIRECT WASTE RECEPTOR SHALL BE LOCATED NEAR THE WATER |
| HEATER SO THE RELIEF AND PAN DRAIN LINES DO NOT PRESENT |
| A TRIPPING HAZARD. |
| ****RESPONSE NOTED, BUT THE FLOOR DRAIN IS STILL NOT AN |
| APPROVED INDIRECT WASTE RECEPTOR. COMMENT NOT COMPLETLY |
| ADDRESSED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |