2009-01-24 15:30:58 | REVIEW #: 2ND ***PLAN CHECK ONLY*** |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY: |
| |
| 1. OK. SEPARATE PERMIT FOR GENERATOR REQUIRED. SUBMIT |
| PLANS FOR THAT PERMIT WHICH HAVE BEEN REVIEWED AND |
| APPROVED BY PBC DERM. FOR MORE INFORMATION PLEASE |
| CONTACT PBC DERM AT: 561-233-2400 OR |
| HTTP://WWW.PBCGOV.COM/ERM/ |
| |
| 2. *PREVIOUS COMMENT* PAGE H-1 REFERS TO FORM 400A FOR |
| ENERGY CODE COMPLIANCE. NO SUCH FORM WAS PROVIDED WITH |
| THIS SUBMISSION. WITHOUT SUCH FORM, AN OVERALL ENERGY |
| CODE COMPLIANCE REVIEW CAN NOT BE PERFORMED. PROVIDE A |
| COMMERCIAL ENERGY CODE COMPLIANCE FORM IN ACCORDANCE |
| WITH FBCB 13-400.0. ALSO, COOLING LOAD CALCULATIONS |
| SHALL BE APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN |
| ACCORDANCE WITH FBCM 13-407.1.ABC.1. AS A RESULT OF |
| THIS INFORMATION NOT BEING PROVIDED, RELATED ADDITIONAL |
| COMMENTS ARE LIKELY IN SUBSEQUENT REVIEWS. |
| *PARTIALLY ADDRESSED* FORM 400A VERSION 2.11 WAS |
| SUBMITTED WITH COOLING LOAD CALCULATIONS. AN ACCURATELY |
| COMPLETED FORM 400A-04R (GENERATED BY THE FLA/COM-2004 |
| COMPUTER PROGRAM, VERSION 2.5) DEMONSTRATING THAT CODE |
| COMPLIANCE HAS BEEN ACHIEVED SHALL BE SUBMITTED TO THE |
| BUILDING OFFICIAL FOR METHOD A COMPLIANCE IN ACCORDANCE |
| WITH FBCB 13-400.3.A. METHOD A VERSION 2.11 HAS NOT |
| BEEN IN EFFECT SINCE THE DECEMBER 8, 2006 REVISIONS TO |
| THE FBC. REVIEW FOR COMPLIANCE WITH FBCB CHAPTER 13 IS |
| NOT POSSIBLE AT THIS TIME. |
| |
| 3. *PREVIOUS COMMENT* PAGE H-2: MULTIPLE DUCTS ON FLOOR |
| PLAN DO NOT HAVE A SIZE DESIGNATION. EXAMPLES: OUTSIDE |
| AIR DUCTS IN MECHANICAL ROOMS, RETURN TRUNK AND BRANCH |
| LINES. PLEASE CHECK ALL DUCTS ON FLOOR PLAN AND PROVIDE |
| MISSING SIZE INFORMATION. DUCTS SHALL BE DESIGNED AND |
| INSTALLED TO PROVIDE THE REQUIRED DISTRIBUTION OF AIR |
| IN ACCORDANCE WITH FBCM 603.1. |
| *PARTIALLY ADDRESSED* SOME DUCTS ON PLANS ARE STILL |
| MISSING SIZES, SUCH AS THE OA DUCTS IN MECHANICAL ROOM |
| 113 AND THE RETURN BRANCH IN THE KITCHEN. PLEASE |
| PROVIDE ALL MISSING INFORMATION. ALSO, PLEASE SEE FBCM |
| 407.1 FOR REQUIREMENTS RELATED TO RETURN AIR INTAKES IN |
| KITCHENS. |
| |
| 4. OK |
| |
| 5. OK |
| |
| 6. OK |
| |
| 7. *PREVIOUS COMMENT* PAGE HD-2: THERE IS NO DETAIL |
| PROVIDED FOR INSTALLATION OF GRAVITY HOOD, ASSOCIATED |
| ROOF CURB OR ROOF JACKS FOR WIND RESISTANCE. MECHANICAL |
| EQUIPMENT SHALL BE DESIGNED AND INSTALLED TO RESIST |
| WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13. |
| *PARTIALLY ADDRESSED* DETAIL ON HD-3 CALLS FOR EYEBOLT |
| EMBEDDED 3 INCHES WITH EPOXY GROUT. HOW IS THIS |
| POSSIBLE ON A METAL STANDING SEAM ROOF? THIS DETAIL |
| APPEARS TO BE FOR A CONCRETE DECK, WHICH DOES NOT APPLY |
| TO THIS PROJECT. PLEASE CORRECT FOR THE APPROPRIATE |
| ROOF ASSEMBLY. |
| |
| 8. OK |
| |
| NOTE: THE 2007 FLORIDA BUILDING CODE IS SCHEDULED TO |
| BECOME EFFECTIVE ON MARCH 1, 2009. IF A PERMIT |
| APPLICATION FOR THIS PROJECT IS SUBMITTED AFTER THIS |
| DATE, THESE PLANS WILL NEED TO BE REVIEWED FOR |
| COMPLIANCE WITH THE NEW CODE PRIOR TO PERMIT ISSUANCE. |
| |