Plan Review Notes
Plan Review Notes For Permit 08090593
Permit Number 08090593
Review Stop M
Sequence Number 2
Notes
Date Text
2009-01-24 15:30:58REVIEW #: 2ND ***PLAN CHECK ONLY***
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY:
  
 1. OK. SEPARATE PERMIT FOR GENERATOR REQUIRED. SUBMIT
 PLANS FOR THAT PERMIT WHICH HAVE BEEN REVIEWED AND
 APPROVED BY PBC DERM. FOR MORE INFORMATION PLEASE
 CONTACT PBC DERM AT: 561-233-2400 OR
 HTTP://WWW.PBCGOV.COM/ERM/
  
 2. *PREVIOUS COMMENT* PAGE H-1 REFERS TO FORM 400A FOR
 ENERGY CODE COMPLIANCE. NO SUCH FORM WAS PROVIDED WITH
 THIS SUBMISSION. WITHOUT SUCH FORM, AN OVERALL ENERGY
 CODE COMPLIANCE REVIEW CAN NOT BE PERFORMED. PROVIDE A
 COMMERCIAL ENERGY CODE COMPLIANCE FORM IN ACCORDANCE
 WITH FBCB 13-400.0. ALSO, COOLING LOAD CALCULATIONS
 SHALL BE APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBCM 13-407.1.ABC.1. AS A RESULT OF
 THIS INFORMATION NOT BEING PROVIDED, RELATED ADDITIONAL
 COMMENTS ARE LIKELY IN SUBSEQUENT REVIEWS.
 *PARTIALLY ADDRESSED* FORM 400A VERSION 2.11 WAS
 SUBMITTED WITH COOLING LOAD CALCULATIONS. AN ACCURATELY
 COMPLETED FORM 400A-04R (GENERATED BY THE FLA/COM-2004
 COMPUTER PROGRAM, VERSION 2.5) DEMONSTRATING THAT CODE
 COMPLIANCE HAS BEEN ACHIEVED SHALL BE SUBMITTED TO THE
 BUILDING OFFICIAL FOR METHOD A COMPLIANCE IN ACCORDANCE
 WITH FBCB 13-400.3.A. METHOD A VERSION 2.11 HAS NOT
 BEEN IN EFFECT SINCE THE DECEMBER 8, 2006 REVISIONS TO
 THE FBC. REVIEW FOR COMPLIANCE WITH FBCB CHAPTER 13 IS
 NOT POSSIBLE AT THIS TIME.
  
 3. *PREVIOUS COMMENT* PAGE H-2: MULTIPLE DUCTS ON FLOOR
 PLAN DO NOT HAVE A SIZE DESIGNATION. EXAMPLES: OUTSIDE
 AIR DUCTS IN MECHANICAL ROOMS, RETURN TRUNK AND BRANCH
 LINES. PLEASE CHECK ALL DUCTS ON FLOOR PLAN AND PROVIDE
 MISSING SIZE INFORMATION. DUCTS SHALL BE DESIGNED AND
 INSTALLED TO PROVIDE THE REQUIRED DISTRIBUTION OF AIR
 IN ACCORDANCE WITH FBCM 603.1.
 *PARTIALLY ADDRESSED* SOME DUCTS ON PLANS ARE STILL
 MISSING SIZES, SUCH AS THE OA DUCTS IN MECHANICAL ROOM
 113 AND THE RETURN BRANCH IN THE KITCHEN. PLEASE
 PROVIDE ALL MISSING INFORMATION. ALSO, PLEASE SEE FBCM
 407.1 FOR REQUIREMENTS RELATED TO RETURN AIR INTAKES IN
 KITCHENS.
  
 4. OK
  
 5. OK
  
 6. OK
  
 7. *PREVIOUS COMMENT* PAGE HD-2: THERE IS NO DETAIL
 PROVIDED FOR INSTALLATION OF GRAVITY HOOD, ASSOCIATED
 ROOF CURB OR ROOF JACKS FOR WIND RESISTANCE. MECHANICAL
 EQUIPMENT SHALL BE DESIGNED AND INSTALLED TO RESIST
 WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
 *PARTIALLY ADDRESSED* DETAIL ON HD-3 CALLS FOR EYEBOLT
 EMBEDDED 3 INCHES WITH EPOXY GROUT. HOW IS THIS
 POSSIBLE ON A METAL STANDING SEAM ROOF? THIS DETAIL
 APPEARS TO BE FOR A CONCRETE DECK, WHICH DOES NOT APPLY
 TO THIS PROJECT. PLEASE CORRECT FOR THE APPROPRIATE
 ROOF ASSEMBLY.
  
 8. OK
  
 NOTE: THE 2007 FLORIDA BUILDING CODE IS SCHEDULED TO
 BECOME EFFECTIVE ON MARCH 1, 2009. IF A PERMIT
 APPLICATION FOR THIS PROJECT IS SUBMITTED AFTER THIS
 DATE, THESE PLANS WILL NEED TO BE REVIEWED FOR
 COMPLIANCE WITH THE NEW CODE PRIOR TO PERMIT ISSUANCE.
  