Plan Review Notes For Permit 08090593 |
Permit Number |
08090593 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-01-14 11:23:21 | ***DENIED*** | | | | MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED. | | PLEASE SEE THE FOLLOWING AND NOTE THAT THE PLANS WILL | | REMAIN IN FAILED STATUS UNTIL REVIEWED AND APPROVED FOR | | PERMIT. | | | | 1) PLEASE ADD TO CODE ANALYSIS ON SHEET A-3. NFPA 1, | | 2003 CHAPTER-18 | | | | 2) TYPICALLY DEAD END WATER LINES THAT ARE CONNECTED TO | | FIRE PROTECTION EQUIPMENT IS AN UNACCEPTABLE | | ARRANGEMENT, PARTICULARLY IF FUTURE EQUIPMENT IS | | PROPOSED. PLEASE PROVIDE FURTHER EXPLANATION. | | | | 3) PLEASE PROVIDE VERIFICATION THAT EQUIPMENT | | ILLUSTRATED ON SHEET CD-5 IS A DOUBLE CHECK DETECTOR | | ASSEMBLY. THE RESPONSE SEEMS TO SUGGEST A DEVICE THAT | | IS TIED TO THE DOMESTIC WATER SUPPLY INDICATING A | | BACKFLOW DEVICE. | | | | 5) OK PLEASE VERIFY THE ACTUAL DISTANCES ON THE | | DRAWINGS AS CODE ANALYSIS INDICATES THAT DISTANCES | | VARY. | | | | 7) THE ADDRESS IS SHOWN ON PLANS. PLEASE INCLUDE | | INFORMATION SHOWING CODE COMPLIANCE PER THE CITY OF | | WEST PALM BEACH REQUIREMENTS FOR COMMERCIAL BUILDINGS. | | | | 14) PLEASE ADD NOTE TO PLANS. NFPA 241 | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|