Plan Review Notes
Plan Review Notes For Permit 08090593
Permit Number 08090593
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2009-01-14 11:23:21***DENIED***
  
 MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING AND NOTE THAT THE PLANS WILL
 REMAIN IN FAILED STATUS UNTIL REVIEWED AND APPROVED FOR
 PERMIT.
  
 1) PLEASE ADD TO CODE ANALYSIS ON SHEET A-3. NFPA 1,
 2003 CHAPTER-18
  
 2) TYPICALLY DEAD END WATER LINES THAT ARE CONNECTED TO
 FIRE PROTECTION EQUIPMENT IS AN UNACCEPTABLE
 ARRANGEMENT, PARTICULARLY IF FUTURE EQUIPMENT IS
 PROPOSED. PLEASE PROVIDE FURTHER EXPLANATION.
  
 3) PLEASE PROVIDE VERIFICATION THAT EQUIPMENT
 ILLUSTRATED ON SHEET CD-5 IS A DOUBLE CHECK DETECTOR
 ASSEMBLY. THE RESPONSE SEEMS TO SUGGEST A DEVICE THAT
 IS TIED TO THE DOMESTIC WATER SUPPLY INDICATING A
 BACKFLOW DEVICE.
  
 5) OK PLEASE VERIFY THE ACTUAL DISTANCES ON THE
 DRAWINGS AS CODE ANALYSIS INDICATES THAT DISTANCES
 VARY.
  
 7) THE ADDRESS IS SHOWN ON PLANS. PLEASE INCLUDE
 INFORMATION SHOWING CODE COMPLIANCE PER THE CITY OF
 WEST PALM BEACH REQUIREMENTS FOR COMMERCIAL BUILDINGS.
  
 14) PLEASE ADD NOTE TO PLANS. NFPA 241
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756