Plan Review Notes
Plan Review Notes For Permit 08090593
Permit Number 08090593
Review Stop E
Sequence Number 2
Notes
Date Text
2009-01-05 13:55:32** DENIED 2ND REVIEW **
  
 ** SOME NOTES FROM PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
  
 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND
 PERMIT APPLICATION HAS YET TO BE MADE. PLEASE KEEP IN
 MIND THE NEW FLORIDA BUILDING CODE IS SET TO GO INTO
 EFFECT ON MARCH 1ST, 2009.
 VERIFICATION OF SEVERAL ITEMS INCLUDING LICENSING WILL
 BE DONE ONCE PERMIT APPLICATION IS MADE.
 *** PLEASE BE SURE ALL DOCUMENTATION CONTAINS THE
 CORRECT ADDRESS.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO LIGHTING CONTROLS. ROOMS/AREAS 114 AND 115
 SHOW SWITCHES HOWEVER THESE ARE NOT THE SAME SYMBOLS AS
 USED IN THE OTHER ROOMS. THERE IS A NOTE #2 WHICH LENDS
 TO POSSIBLE USE OF A SINGLE OCCUPANCY SENSOR TYPE
 DEVICE HOWEVER THIS IS NOT CLEAR AT THIS TIME.
 PLEASE SHOW THE SAME SYMBOL AS USED ON OTHER LOCATIONS.
 13-415.1.ABC.1.1,.1.2 AND .1.3.
  
 3) NOTE: THE PREVIOUS SUBMITTED WERE NOT SUBMITTED WITH
 THE REQUIRED ENERGY CALCULATIONS PER FBC 13-101,
 13-400, 13-415.2 ETC
 THE SPECIFIC SECTIONS WERE GIVEN HOWEVER THESE WILL BE
 NOTED ONCE MORE. PLEASE SEE 13-400.3.A FOR VERSION
 WHICH WAS ADOPTED ON DECEMBER 8TH, 2006. THE CURRENT
 FLA COM VERSION AS NOTED IN THIS SECTION TO BE USED AT
 A MINIMUM IS VERSION 2.5. THE SUBMITTED CALCULATIONS
 ARE VERSION 2.11 WHICH IS NO LONGER AN ADOPTED VERSION
 IN THE STATE OF FLORIDA.
 PLEASE BE SURE ALL ITEMS ON PLANS COORDINATES WITH THE
 SUBMITTED INPUT DATA REPORT. THIS INCLUDES OTHER TRADES
 AS WELL.
 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3 FOR LIGHTING.
 SEE THE EXTERIOR LIGHTING ON THE IDR ONLY INDICATES 4
 FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS SHOW A
 CONSIDERABLE AMOUNT OF MORE FIXTURES THAN THE FOUR
 NOTED.
 PLEASE SEE 13-401- 13-412 FOR OTHERS.
 ITEMS SUCH AS FLOORS WHICH ARE ALL SHOWN AS
 CARPET/RUBBER PADDING IS NOT CORRECT AS THERE ARE
 SEVERAL AREAS WHICH ARE NOT THIS FINISH ARE SOME WHICH
 ARE NOT PERMITTED TO CONTAIN THIS TYPE OF FINISH. (ELEC
 ROOM, MECH ROOM ETC).
 SEE COMMENTS FROM OTHER TRADES.
  
 ** PLEASE SEE THE COVER SHEET FOR THE PLANS INDICATES
 THE ADDRESS AS 7501 N JOG RD ALTHOUGH THE APPLIED
 LOCATION IS 6880. PLEASE COORDINATE ALL PLANS AND
 SUPPORTING DOCUMENTATION.
  
 4) NOTE: ON THE PREVIOUS REVIEW THE PHOTO-METRIC LEVELS
 FOR THE LIFE SAFETY EGRESS WERE REQUESTED. THE RESPONSE
 MENTIONS TO SEE ENCLOSED PLANS. THIS INFORMATION NEEDS
 TO BE PART OF THE PLANS, WITH TITLE BLOCKS ALONG WITH
 BEING SIGNED, DATED AND SEALED BY THE RESPONSIBLE
 DESIGNER.
 NFPA-101 7.8, 7.9.
 FS471.003, 471.025, FAC 61G15-23.002
 FBC 106.1.1, 106.5. ADDITIONAL INFORMATION, CLARITY ON
 RECORD PLANS.
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE GENERATOR, ATS ETC. THE ATS IS AN
 INTEGRAL PART OF THE ELECTRICAL RISER AND COULD NOT BE
 UNDER A SEPARATE PERMIT.
 110.3,90.7
  
 6) NOTE: NOW THAT THE LOADS FOR MDP-OP ARE SHOWN PLEASE
 PROVIDE A GENERATOR WHICH WILL SERVE THE CAPACITY OR
 PLEASE PROVIDE ALL LOAD SHEDDING WHICH WOULD BE NEEDED
 TO DECREASE LOAD ON SYSTEM. AS SHOWN AT THIS TIME THE
 GENERATOR WILL FEED ALL LOADS.
 220, 215.3, 702.5 ETC
  
 7) NOTE: PLEASE PROVIDE WIND LOADS FOR LIGHT POLES PER
 FBC TABLE 1609. RESPONSE MENTIONS THE INFORMATION WAS
 ADDED TO SHEET E-10. HOWEVER THIS INFORMATION AS SHOWN
 IS NOT CORRECT AND HAS BEEN CONFIRMED WITH THE BUILDING
 REVIEWER.
  
 8) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR ALL
 ITEMS. PLEASE SEE SHEET E-7, ROLL UP DOOR FOR EXAMPLE:
 408.4.
  
 9) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO LOAD
 CALCULATIONS. PLEASE SUBMIT THE LOAD CALCULATIONS
 SHOWING HOW THE LOADS WERE DERIVED. THERE ARE NO NOTES
 ON WHETHER OR NOT THE CONTINUOUS LOADS SUCH AS THE
 LIGHTING AND WATER HEATER WAS ALREADY FIGURED AT 125%
 OR IF THEY STILL NEED TO BE.
 THE TYPICAL WATER HEATER SHOWN ON PLANS INDICATE 4500
 VA HOWEVER NO INDICATE OF THE 125% COULD BE LOCATED.
 220.12,220.14,220.42,220.44, ETC CONTINUOUS LOADS PER
 215.3,230.42. SEE 422.13 FOR STORAGE TYPE WATER
 HEATERS. THIS WAS A CHANGE IN THE 2005 NEC.
  
 10) NOTE: PLEASE CLARIFY THE FOUNDATION STEEL BEING
 PART OF THE GROUNDING ELECTRICAL SYSTEMS AT BOTH
 STRUCTURES. THE PLANS NOTES *BUILDING STEEL* HOWEVER IT
 IS NOT CLEAR IF THIS IS FOR *FOUNDATION STEEL*.
 250.50
 THIS COMMENT WAS NOT MADE ON THE PREVIOUS REVIEW.
  
 ** AS NOTED ON PREVIOUS REVIEW AS THERE IS SOME
 INFORMATION NOT YET SUBMITTED A COMPLETE REVIEW FOR
 CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  