2009-01-05 13:55:32 | ** DENIED 2ND REVIEW ** |
| |
| ** SOME NOTES FROM PREVIOUS REVIEW STILL NEED TO BE |
| ADDRESSED. |
| |
| 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND |
| PERMIT APPLICATION HAS YET TO BE MADE. PLEASE KEEP IN |
| MIND THE NEW FLORIDA BUILDING CODE IS SET TO GO INTO |
| EFFECT ON MARCH 1ST, 2009. |
| VERIFICATION OF SEVERAL ITEMS INCLUDING LICENSING WILL |
| BE DONE ONCE PERMIT APPLICATION IS MADE. |
| *** PLEASE BE SURE ALL DOCUMENTATION CONTAINS THE |
| CORRECT ADDRESS. |
| |
| 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH |
| RESPECT TO LIGHTING CONTROLS. ROOMS/AREAS 114 AND 115 |
| SHOW SWITCHES HOWEVER THESE ARE NOT THE SAME SYMBOLS AS |
| USED IN THE OTHER ROOMS. THERE IS A NOTE #2 WHICH LENDS |
| TO POSSIBLE USE OF A SINGLE OCCUPANCY SENSOR TYPE |
| DEVICE HOWEVER THIS IS NOT CLEAR AT THIS TIME. |
| PLEASE SHOW THE SAME SYMBOL AS USED ON OTHER LOCATIONS. |
| 13-415.1.ABC.1.1,.1.2 AND .1.3. |
| |
| 3) NOTE: THE PREVIOUS SUBMITTED WERE NOT SUBMITTED WITH |
| THE REQUIRED ENERGY CALCULATIONS PER FBC 13-101, |
| 13-400, 13-415.2 ETC |
| THE SPECIFIC SECTIONS WERE GIVEN HOWEVER THESE WILL BE |
| NOTED ONCE MORE. PLEASE SEE 13-400.3.A FOR VERSION |
| WHICH WAS ADOPTED ON DECEMBER 8TH, 2006. THE CURRENT |
| FLA COM VERSION AS NOTED IN THIS SECTION TO BE USED AT |
| A MINIMUM IS VERSION 2.5. THE SUBMITTED CALCULATIONS |
| ARE VERSION 2.11 WHICH IS NO LONGER AN ADOPTED VERSION |
| IN THE STATE OF FLORIDA. |
| PLEASE BE SURE ALL ITEMS ON PLANS COORDINATES WITH THE |
| SUBMITTED INPUT DATA REPORT. THIS INCLUDES OTHER TRADES |
| AS WELL. |
| 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3 FOR LIGHTING. |
| SEE THE EXTERIOR LIGHTING ON THE IDR ONLY INDICATES 4 |
| FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS SHOW A |
| CONSIDERABLE AMOUNT OF MORE FIXTURES THAN THE FOUR |
| NOTED. |
| PLEASE SEE 13-401- 13-412 FOR OTHERS. |
| ITEMS SUCH AS FLOORS WHICH ARE ALL SHOWN AS |
| CARPET/RUBBER PADDING IS NOT CORRECT AS THERE ARE |
| SEVERAL AREAS WHICH ARE NOT THIS FINISH ARE SOME WHICH |
| ARE NOT PERMITTED TO CONTAIN THIS TYPE OF FINISH. (ELEC |
| ROOM, MECH ROOM ETC). |
| SEE COMMENTS FROM OTHER TRADES. |
| |
| ** PLEASE SEE THE COVER SHEET FOR THE PLANS INDICATES |
| THE ADDRESS AS 7501 N JOG RD ALTHOUGH THE APPLIED |
| LOCATION IS 6880. PLEASE COORDINATE ALL PLANS AND |
| SUPPORTING DOCUMENTATION. |
| |
| 4) NOTE: ON THE PREVIOUS REVIEW THE PHOTO-METRIC LEVELS |
| FOR THE LIFE SAFETY EGRESS WERE REQUESTED. THE RESPONSE |
| MENTIONS TO SEE ENCLOSED PLANS. THIS INFORMATION NEEDS |
| TO BE PART OF THE PLANS, WITH TITLE BLOCKS ALONG WITH |
| BEING SIGNED, DATED AND SEALED BY THE RESPONSIBLE |
| DESIGNER. |
| NFPA-101 7.8, 7.9. |
| FS471.003, 471.025, FAC 61G15-23.002 |
| FBC 106.1.1, 106.5. ADDITIONAL INFORMATION, CLARITY ON |
| RECORD PLANS. |
| |
| 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| SHEETS ON THE GENERATOR, ATS ETC. THE ATS IS AN |
| INTEGRAL PART OF THE ELECTRICAL RISER AND COULD NOT BE |
| UNDER A SEPARATE PERMIT. |
| 110.3,90.7 |
| |
| 6) NOTE: NOW THAT THE LOADS FOR MDP-OP ARE SHOWN PLEASE |
| PROVIDE A GENERATOR WHICH WILL SERVE THE CAPACITY OR |
| PLEASE PROVIDE ALL LOAD SHEDDING WHICH WOULD BE NEEDED |
| TO DECREASE LOAD ON SYSTEM. AS SHOWN AT THIS TIME THE |
| GENERATOR WILL FEED ALL LOADS. |
| 220, 215.3, 702.5 ETC |
| |
| 7) NOTE: PLEASE PROVIDE WIND LOADS FOR LIGHT POLES PER |
| FBC TABLE 1609. RESPONSE MENTIONS THE INFORMATION WAS |
| ADDED TO SHEET E-10. HOWEVER THIS INFORMATION AS SHOWN |
| IS NOT CORRECT AND HAS BEEN CONFIRMED WITH THE BUILDING |
| REVIEWER. |
| |
| 8) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR ALL |
| ITEMS. PLEASE SEE SHEET E-7, ROLL UP DOOR FOR EXAMPLE: |
| 408.4. |
| |
| 9) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO LOAD |
| CALCULATIONS. PLEASE SUBMIT THE LOAD CALCULATIONS |
| SHOWING HOW THE LOADS WERE DERIVED. THERE ARE NO NOTES |
| ON WHETHER OR NOT THE CONTINUOUS LOADS SUCH AS THE |
| LIGHTING AND WATER HEATER WAS ALREADY FIGURED AT 125% |
| OR IF THEY STILL NEED TO BE. |
| THE TYPICAL WATER HEATER SHOWN ON PLANS INDICATE 4500 |
| VA HOWEVER NO INDICATE OF THE 125% COULD BE LOCATED. |
| 220.12,220.14,220.42,220.44, ETC CONTINUOUS LOADS PER |
| 215.3,230.42. SEE 422.13 FOR STORAGE TYPE WATER |
| HEATERS. THIS WAS A CHANGE IN THE 2005 NEC. |
| |
| 10) NOTE: PLEASE CLARIFY THE FOUNDATION STEEL BEING |
| PART OF THE GROUNDING ELECTRICAL SYSTEMS AT BOTH |
| STRUCTURES. THE PLANS NOTES *BUILDING STEEL* HOWEVER IT |
| IS NOT CLEAR IF THIS IS FOR *FOUNDATION STEEL*. |
| 250.50 |
| THIS COMMENT WAS NOT MADE ON THE PREVIOUS REVIEW. |
| |
| ** AS NOTED ON PREVIOUS REVIEW AS THERE IS SOME |
| INFORMATION NOT YET SUBMITTED A COMPLETE REVIEW FOR |
| CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |