2009-01-06 09:03:04BUILDING PLAN REVIEW
 PERMIT: 08090593
 ADD: 6880 N JOG RD
 CONT:MAJOR WORKING DRAWING REVIEW
 TEL: (772)231-4301
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 OFFICE BUILDING TYPE II-B 1,800 SQ FT
 S-2 MAINTENANCE BUILDING TYPE II-B 1,000 SQ FT
  
 JAN 06/2009
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C-1E) COMPLIED.
  
 2) 2ND REQUEST, COMMENT RESPONSE SHEET INDICATES SOILS
 REPORTS WERE SUBMITTED, NOT IN THIS REVIEW. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) COMPLIED, BUILDING PROVISO: 109.3.10* IMPACT OF
 CONSTRUCTION.
  
 4) COMPLIED, BUILDING PROVISO: 109.3.10.1 HURRICANE
 PROTECTION.
  
 5) COMPLIED.
  
 6) ENERGY CALCULATION ARE IN THIS SUBMITTAL, BUT ARE
 THE WRONG VERSION . PLEASE REVIEW SECTION 13-400.3..A.
  
 7-10) THE COUNTY DOES NOT REQUIRE PRODUCT APPROVALS AT
 TIME OF PERMIT SUBMISSION. THE CITY OF WEST PALM DOES
 REQUIRE THE FULL PRODUCT APPROVAL PACKAGE, THERE ARE
 OLD MIAMI-DADE REPORTS THAT STILL HAVE NOT HAD THEIR
 ANCHOR CALCULATION UPDATED TO THE 2004 FBC, WHICH MEANS
 UNDER THE 2001 FBC 1.33 INCREASES WERE TAKEN IN STEEL
 FASTENERS, 1605.3.1.1. AS STATED IN COMMENT (1B)
 PRODUCT APPROVAL REPORTS ARE REQUIRED AT TIME OF
 APPLICATION. HIGHLIGHT GLAZING SYSTEM TO BE USED IF
 THERE IS MULTIPLE GLAZING UNIT TYPES.
  
 7) 2ND REQUEST,1609.1.4 PROTECTION OF OPENINGS IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE
 THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 8)2ND REQUEST, FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
 8A) FIXED WINDOWS
 8B) MULLIONS
 8C) EXTERIOR GLAZED DOORS
 8D) EXTERIOR METAL DOORS
 8E) ROLL UP DOORS
 8F) WALL LOUVERS
 8G) TRUSS ANCHORS
 8H) ROOF ASSEMBLIES
 8I) SOFFITS
  
 9) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 10) 2ND EQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 OFFICE BUILDING TYPEII-B
  
 11A) COMPLIED.
  
 11B) 2ND REQUEST, SHEET A-11 & SHEET A-14 APPEAR TO
 HAVE A 2'X2' LAY IN TILE CEILING, PLANS DO NOT PROVIDE
 HOW THE 1 HOUR RATING OF WALLS IS TO OCCUR, THROUGH TO
 THE ROOF DECK OR A 1HR RATED CEILING. 708.1.
 A) YOUR RESPONCE IS CONFUSING, SHEET AD-3, THE NOTE
 ADDED TO EXTEND DRYWALL AND INSULATION TO THE UNDER
 SIDE OF THE ROOF DECK DOES NOT TIE TO A WALL TYPE. A
 GENERIC WALL TYPE IS DEPICTED AND THE
 NOTE IS NOT LOCATED NEXT TO WALL TYPE 2A A NONRATED
 WALL NOR NEXT TO 2-1 A 1 HR RATED WALL ASSEMBLY.
  
 B) PLEASE PROVIDE THE DETAIL OF HOW THE RATED WALL WILL
 FASTEN INTO THE ROOF DECK ASSEMLBY, ALSO NOTE WHAT TYPE
 OF FLEXIBLE SEALENT SHALL BE USED.713.1 FIRE RESISTANT
 JOINT SYSTEMS.
  
 C) THIS SAME CORRIDOR 111 HAS A DOOR# 107 WHICH IS PART
 OF THE RATED CORRIDOR THE DOOR SCHEDULE DOES NOT
 INDICATE AS SUCH TABLE 1016.1.
  
 D) AD-3 LIFE SAFETY SHEET WILL ALSO NEED TO BE UPDATED
 FOR A RATED LOBBY WALL AND DOOR 107.
  
 E) THE RATING OF CORRIDOR 111 FOR 1 HOUR IS REQUIRED
 BECAUSE OF THE OCCUPANT LOAD BEING GREATER THAN 30 FOR
 TRAINING ROOM AND BREAK ROOM WHEN THE FOLDING PARTITION
 IS NOT USED. IT BECOMES AN
 ASSEMBLY OCCUPANCY REQUIRING THE CORRIDOR 111TO BE
 RATED FOR 1 HR. THIS RATING WILL CONTINUE THROUGH TO
 THE EXIT. THE LOBBY AREA WALL IS NOT INDICATED AS A
 FIRE RATED WALL. 1016.5CORRIDOR CONTINUITY
 FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS
 FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE
 INTERRUPTED BY INTERVENING ROOMS. EXCEPTION: FOYERS,
 LOBBIES OR RECEPTION ROOMS CONSTRUCTED
 AS REQUIRED FOR CORRIDORS SHALL NOT BE CONSTRUED AS
 INTERVENING ROOMS. THE LOBBY CAN BE USED AS PART OF THE
 MEANS OF EGRESS BUT THE WALL LABELED 2A WILL NEED TO BE
 RATED ONE HOUR.
  
 F) CORRIDOR 101 IS WITHIN A BUSINESS OCCUPANCY AND WILL
 NOT BE REQUIRED TO BE 1 HR RATED, IF THE DESIGNER
 WISHES TO RATE THIS CORRIDOR YOU MAY DO THAT.
  
 11C-D) COMPLIED.
  
 12)2ND REQUEST SHEET A-8 PLEASE PROVIDE COMPLIANCE WITH
 11-4.22.2 DOORS. ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. SEE ROOMS
 120,& 121.
 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES
 (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A
 PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM
 SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET
 ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE
 ROUTE.
  
 13) 2ND REQUEST, THE RESPONSE COMMENTS INDICATE THIS TO
 BE A PAVILION, TO BE PART OF THIS PERMIT WE DO NEED
 INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU
 INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS
 GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE
 STATE AND IS APPROVED AS A MANUFACTURED MODULAR
 BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL
 NEED
 PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. WITHOUT
 PLANS THIS AREA WILL BE EXEMPTED FROM THE PERMIT AND
 PLANS TO BE SUBMITTED UNDER A SEPERATE PERMIT.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 15-17) COMPLIED.
 T THE CONNECTION STATES THAT WELDING OF CONNECTIONS IS
 PROHIBITED, PLEASE PROVIDE MANUFACTURERS APPROVAL FOR
 WELDING OF THIS TYPE OF CONNECTION. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 18) 2ND REQUEST. SHEET S-4 INDICATES A FOOTING TYPE A
 BUT THE PLANS ARE LACKING COLUMN AND BEAM INFORMATION,
 1609.2.1 PART OFTHE MAIN WIND FORCE-RESISTING SYSTEM.
 PLEASE PROVIDE ADDITONAL INFORMATION, 106.1..2. 106.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 19) 2ND REQUEST, SHEET A-4 ALSO INDICATES THE ROOFING
 ASSEMBLY TO BE A PREMANUFACTRED CANOPY, PLEASE PROVIDE
 PRODUCT INFORMATION, TO BE PART OF THIS PERMIT WE DO
 NEED INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU
 INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS
 GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE
 STATE AND IS APPROVED AS A MANUFACTURED MODULAR
 BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL
 NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY.
 WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE
 PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE
 PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
  
 20)2ND REQUEST, STRUCTURAL SHEETS S-4, S-6 AND S-8 ROOF
 PRESSURE ZONES FAIL TO INDICATE PRESSURE ZONE 3 FAIL TO
 INDICATE CORNER ZONE# 3 AND THE ASSOCIATED PRESSURES,
 PLEASE REVIEW FIGURE 1609.6.2.2 COMPONENTS AND
 CLADDING. WITH THE RESPONSE FOR THIS COMMENT IT APPEARS
 THAT YOUR CODE BOOK HAS NOT BEEN UPDATED. IN 2006
 SUPPLEMENTS( BLUE PAGES) THE TABLE 1609.6C HAS BEEN
 ELIMINATED. PLEASE REVISE SHEET S-6 FOR PRESSURES IN
 ZONE 3.
  
 21) 2ND REQUEST, GENERATOR PAD IS SHOWN ON SHEET SD-1,
 IS THIS PAD GOING TO BE PART OF THIS PERMIT OR JUST
 INFORMATIONAL, THE GENERATOR AND ATTACHMENT TO SLAB
 WILL BE REVIEWED UNDER A SEPERATE PERMIT. PLEASE
 PROVIDE SIZE OF GENERATOR PAD, IF STELL REINFORCEMENT
 IS TO BE INSTALLED AND ANCHORS TO RESIST THE MOMENT OF
 OVER TURNING. 1609.1.3 ANCHORAGE AGAINST OVERTURNING,
 UPLIFT AND SLIDDING.
  
 22) STAIR DELETED, COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved