Date |
Text |
2008-10-03 14:03:52 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT CD-6 IS NOT SIGNED, SEALED & DATED AS REQUIRED |
| IN SECTION 106.1, THE FLORIDA ADMINISTRATIVE CODE & |
| FLORIDA STATUTES. |
| |
| 2. SHT A-1 BARRIER-FREE FIXTURE MOUNTING HEIGHT SHOWS |
| THE GRAB BAR FOR THE W/C ON THE SIDEWALL TO BE 40". |
| MINIMUM LENGTH IS 42" PER FIG 29 & SECTION 11-4.16.4. |
| |
| 3. SHT A-3 BUILDING CODE ANALYSIS FOR OPERATIONS & |
| MAINTENANCE BLDGS SHALL INCLUDE THE 2005, 2006 & 2007 |
| REVISIONS/AMENDMENTS. PLEASE INDICATE ON PLANS. SECTION |
| 106.1.1. |
| |
| 4. SHT A-3 MAINTENANCE BUILDING FIXTURE REQUIREMENTS |
| PER TABLE 403.1 ARE NOT INDICATED. IF USING THE |
| EXCEPTION TO SECTION 403.4, THEN THIS MUST BE STATED ON |
| THE PLANS AS WELL AS THE DISTANCE FROM THE MAINTENANCE |
| BUILDING TO THE OPERATIONS BUILDING FACILITIES. SECTION |
| 106.1.1. |
| |
| 5. SUBMIT DETAILS FOR THE ACCESSIBLE FIXTURES SHOWING |
| COMPLIANCE WITH THE FOLLOWING: |
| |
| ___FOR DRINKING FOUNTAIN: |
| A. 11-4.15.5 CLEAR FLOOR SPACE |
| |
| ___FOR W/C'S: |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.5 FLUSH CONTROLS |
| C. W/C TO BE 18" OFF THE WALL TO C/L OF FIXTURE. |
| FIGURES 28 & 30E |
| |
| ___FOR URINALS: |
| A. 11-4.18.3 CLEAR FLOOR SPACE |
| B. 11-4.18.4 FLUSH CONTROLS |
| |
| ___FOR LAVS: |
| A. 11-4.19.3 CLEAR FLOOR SPACE |
| B. 11-4.19 4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| D. LAVS TO BE A MINIMUM 15" OFF WALL TO C/L OF FIXTURE. |
| FIG. 32. |
| |
| ___FOR SHOWERS: |
| A. 11-4.21.2 SIZE & CLEARANCES |
| B. 11-4.21.3 SEAT |
| C. 11-4.21.4 GRAB BARS |
| D. 11-4.21.5 CONTROLS |
| E. 11-4.21.6 SHOWER UNIT |
| F. 11-4.21.7 CURBS |
| |
| ___FOR TOILET ROOMS: |
| A. 11-4.22.2 DOOR SWING |
| B. 11-4.22.3 TURNING AREA |
| |
| ___FOR BATHROOMS: |
| A. 11-4.23.2 DOOR SWING |
| B. 11-4.23.3 TURNING AREA |
| |
| ___FOR SINKS: |
| A. 11-4.24.2 HEIGHT |
| B. 11-4.24.3 KNEE CLEARANCE |
| C. 11-4.24.4 SINK DEPTH |
| D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH |
| REQUIRED. CABINET DOORS NOT APPROVED. |
| E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| F. 11-4.24.7 FAUCETS |
| G, 11-4.2.3 AN UNOBSTRUCTED TURNING AREA |
| |
| 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE |
| INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT |
| WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS |
| BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR |
| OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 & |
| 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE |
| COMMENT RESPONSES TO THESE QUESTIONS. |
| |
| 7. SHT P-4 SANITARY RISER DIAGRAM. THE VENT FOR THE |
| CLEANOUTS AT THE END OF EACH GANG BATH IS NOT APPROVED. |
| THESE ARE HORIZONTAL DRY VENTS. SECTION 905.3. (VENTS |
| ARE NOT REQUIRED FOR CLEANOUTS AND CAN BE DELETED). |
| |
| 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS |
| SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER |
| HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE |
| MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS |
| REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR |
| OFFICE ROOM 102. SECTION 606.2(2). |
| |
| 9. SHT PD-1 EWH-1 WATER HEATER DETAIL STATES "EXPANSION |
| TANK SEE SPECIFICATIONS". SPECIFICATIONS WERE NOT |
| SUBMITTED. PLEASE SUBMIT CALCULATIONS OR MANUF. CHART |
| INDICATING THE MODEL AND CORRECT SIZING OF THE |
| EXPANSION TANK. SECTION 607.3.2. |
| |
| 10. SHT PD-1 A FLOOR DRAIN IS NOT AN APPROVED INDIRECT |
| WASTE RECEPTOR. A FLOOR DRAIN OR HUB DRAIN IS REQUIRED |
| FOR THE P&T RELIEF VALVE AND EMERGENCY PAN DRAIN LINES. |
| SECTIONS 504.6.1, 504.7.2, 802.3 & 802.3.2. THE |
| INDIRECT WASTE RECEPTOR SHALL BE LOCATED NEAR THE WATER |
| HEATER SO THE RELIEF AND PAN DRAIN LINES DO NOT PRESENT |
| A TRIPPING HAZARD. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |
| |