Plan Review Notes
Plan Review Notes For Permit 08090593
Permit Number 08090593
Review Stop P
Sequence Number 1
Notes
Date Text
2008-10-03 14:03:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT CD-6 IS NOT SIGNED, SEALED & DATED AS REQUIRED
 IN SECTION 106.1, THE FLORIDA ADMINISTRATIVE CODE &
 FLORIDA STATUTES.
  
 2. SHT A-1 BARRIER-FREE FIXTURE MOUNTING HEIGHT SHOWS
 THE GRAB BAR FOR THE W/C ON THE SIDEWALL TO BE 40".
 MINIMUM LENGTH IS 42" PER FIG 29 & SECTION 11-4.16.4.
  
 3. SHT A-3 BUILDING CODE ANALYSIS FOR OPERATIONS &
 MAINTENANCE BLDGS SHALL INCLUDE THE 2005, 2006 & 2007
 REVISIONS/AMENDMENTS. PLEASE INDICATE ON PLANS. SECTION
 106.1.1.
  
 4. SHT A-3 MAINTENANCE BUILDING FIXTURE REQUIREMENTS
 PER TABLE 403.1 ARE NOT INDICATED. IF USING THE
 EXCEPTION TO SECTION 403.4, THEN THIS MUST BE STATED ON
 THE PLANS AS WELL AS THE DISTANCE FROM THE MAINTENANCE
 BUILDING TO THE OPERATIONS BUILDING FACILITIES. SECTION
 106.1.1.
  
 5. SUBMIT DETAILS FOR THE ACCESSIBLE FIXTURES SHOWING
 COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR DRINKING FOUNTAIN:
 A. 11-4.15.5 CLEAR FLOOR SPACE
  
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 C. W/C TO BE 18" OFF THE WALL TO C/L OF FIXTURE.
 FIGURES 28 & 30E
  
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
  
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19 4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. LAVS TO BE A MINIMUM 15" OFF WALL TO C/L OF FIXTURE.
 FIG. 32.
  
 ___FOR SHOWERS:
 A. 11-4.21.2 SIZE & CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
  
 ___FOR TOILET ROOMS:
 A. 11-4.22.2 DOOR SWING
 B. 11-4.22.3 TURNING AREA
  
 ___FOR BATHROOMS:
 A. 11-4.23.2 DOOR SWING
 B. 11-4.23.3 TURNING AREA
  
 ___FOR SINKS:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT APPROVED.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 G, 11-4.2.3 AN UNOBSTRUCTED TURNING AREA
  
 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT
 WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS
 BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR
 OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 &
 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE
 COMMENT RESPONSES TO THESE QUESTIONS.
  
 7. SHT P-4 SANITARY RISER DIAGRAM. THE VENT FOR THE
 CLEANOUTS AT THE END OF EACH GANG BATH IS NOT APPROVED.
 THESE ARE HORIZONTAL DRY VENTS. SECTION 905.3. (VENTS
 ARE NOT REQUIRED FOR CLEANOUTS AND CAN BE DELETED).
  
 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE
 MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS
 REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR
 OFFICE ROOM 102. SECTION 606.2(2).
  
 9. SHT PD-1 EWH-1 WATER HEATER DETAIL STATES "EXPANSION
 TANK SEE SPECIFICATIONS". SPECIFICATIONS WERE NOT
 SUBMITTED. PLEASE SUBMIT CALCULATIONS OR MANUF. CHART
 INDICATING THE MODEL AND CORRECT SIZING OF THE
 EXPANSION TANK. SECTION 607.3.2.
  
 10. SHT PD-1 A FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR DRAIN OR HUB DRAIN IS REQUIRED
 FOR THE P&T RELIEF VALVE AND EMERGENCY PAN DRAIN LINES.
 SECTIONS 504.6.1, 504.7.2, 802.3 & 802.3.2. THE
 INDIRECT WASTE RECEPTOR SHALL BE LOCATED NEAR THE WATER
 HEATER SO THE RELIEF AND PAN DRAIN LINES DO NOT PRESENT
 A TRIPPING HAZARD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved