Date |
Text |
2008-10-29 14:22:49 | ***DENIED*** |
| |
| 1) PROPERTY ACCESS AND WATER SUPPLY TO COMPLY WITH NFPA |
| 1, 2003, CHAPTER-18. |
| |
| 2) FIRE LINE APPEARS TO DEAD END AT FIRE HYDRANT. ARE |
| THERE ANY OTHER FIRE HYDRANTS ON THE PROPERTY? |
| |
| 3) SHEET CD-5 ILLUSTRATES A DOUBLE CHECK DETECTOR |
| ASSEMBLY. IN ADDITION TO ELECTRONIC SUPERVISION, DEVICE |
| SHALL BE SECURED WITH CHAIN AND LOCK. SUBJECT BUILDINGS |
| ARE NOT FIRE SPRINKLER PROTECTED. WHAT BUILDING IS |
| PROTECTED BY DOUBLE CHECK DETECTOR ASSEMBLY? |
| |
| 4) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE |
| SAFETY SHALL COMPLY WITH NFPA 101, 2003. |
| |
| 5) PLEASE INDICATE ACTUAL MAXIMUM TRAVEL DISTANCES ON |
| DRAWINGS. (LIFE SAFETY PLAN) |
| |
| 6) DOORS SHALL SWING IN DIRECTION OF TRAVEL WHERE |
| SERVING AREAS WITH (50) OR MORE OCCUPANTS. |
| |
| 7) ADDRESSES ARE REQUIRED ON BUILDINGS THAT SHALL BE |
| MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH |
| BACKGROUND. |
| |
| 8) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR |
| WALLS AND CEILING IN TERMS OF CLASS A,B OR C. ADD NOTE |
| TO ELEVATIONS |
| |
| 9) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED TO BE |
| MOUNTED AT LOCATIONS NOT TO EXCEED 75" TRAVEL DISTANCE |
| REQUIREMENT. OK ON SHEET A-17. |
| |
| 10) KNOX BOX ENTRY REQUIRED FOR BUILDINGS. CONTACT |
| BUREAU OF FIRE PREVENTION AT (561) 804-4724 FOR |
| ASSISTANCE. |
| |
| 11) FIRE DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE |
| WITH UL 555 REQUIREMENTS PRIOR TO FINAL INSPECTION. |
| |
| 12) MOTOR OPERATED GATES TO BE PROVIDED WITH FAIL SAFE |
| MECHANISM IN THE EVENT OF POWER LOSS. |
| |
| 13) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR |
| GENERATOR AND ASSOCIATED EQUIPMENT. |
| |
| 14) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY |
| WITH NFPA 241. |
| |
| |
| MIKE WENNERGREN, ASST. FIRE MARSHAL |
| FIRE PLAN REVIEW |
| FIRE PREVENTION (561) 804-4756 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |