Plan Review Notes
Plan Review Notes For Permit 08090593
Permit Number 08090593
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-10 12:15:00BUILDING PLAN REVIEW
 PERMIT: 08090593
 ADD: 6880 N JOG RD
 CONT:MAJOR WORKING DRAWING REVIEW
 TEL: (772)231-4301
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 OFFICE BUILDING TYPE II-B 1,800 SQ FT
 S-2 MAINTENANCE BUILDING TYPE II-B 1,000 SQ FT
  
 OCT 10,2008
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) BOTH THE ARCHITECTURAL AND STRUCTURAL PLANS
 INDICATE A PAVILION NEST TO THE ADMINISTRATIVE OFFICE
 THE PLAN REVIEW SHEET SUBMITTED ONLY INDICATES A REVIEW
 FOR THE OPERATIONS BUILDING AND MAINTENACE BUILDING .
 IS THIS STRUCTURE TO BE PERMITTED WITH THIS WORK? IN
 THE MINIMUM BUILDING CLASSIFICATION TYPE, IS THIS
 STRUCTURE TO BE CONSIDERED IN THE SQ FT OF THE
 OPERATIONS BUILDING UNDER SECTION 503.1.3 OR TWO
 SEPERATE STRUCTURES WHERE TABLE 602 AND 704.8 WILL NEED
 TO BE CONSIDERED? ADDITIONAL INFORMATION REQUIRED,
 106.1.2.
  
 1E) I PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE REVISE.
  
 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 4) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 5) NOTE SHEET CD-6 IS NOT SIGNED NOR SEALED, PLEASE
 CORRECT. SHEET PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 6) PLANS DO NOT ENCLUDE ENERGY CALCULATIONS 106.3.5.1.4
 AND INPUT ENERGY CALCULATIONS.
  
 7) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 8) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 8A) FIXED WINDOWS
 8B) MULLIONS
 8C) EXTERIOR GLAZED DOORS
 8D) EXTERIOR METAL DOORS
 8E) ROLL UP DOORS
 8F) WALL LOUVERS
 8G) TRUSS ANCHORS
 8H) ROOF ASSEMBLIES
 8I) SOFFITS
  
 9) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 OFFICE BUILDING TYPEII-B
  
 11A) SHEET A3 INDICATES THE CORRIDOR# 111 TO BE ONE
 HOUR RATED, THERE IS NO DOOR BETWEEN THE CORRIDOR AND
 LOBBY 100, PLEASE INDICATE HOW OPENING PROTECTIVE
 (715.3) ARE ACHIEVED IN THIS AREA.
  
 11B) SHEET A-11 & SHEET A-14 APPEAR TO HAVE A 2'X2' LAY
 IN TILE CEILING, PLANS DO NOT PROVIDE HOW THE 1 HOUR
 RATING OF WALLS IS TO OCCUR, THROUGH TO THE ROOF DECK
 OR A 1HR RATED CEILING. 708.1.
  
 11C) SHEET A-4 INDICATES WALL TYPE AS 1 HOUR RATED
 WALLS WITH WALL TAG (AD3) WITHIN THE CORRIDORS, SHEET
 AD-1 INDICATES WITHIN THE DOOR LEGOND 45 MINUTE OPENING
 PROTECTION FOR THE DOORS, DOOR D114 & D115 INDICATE THE
 WRONG TYPE OF FRAMES, PLEASE CORRECT.
  
 11D) SHEET A-4 CORRIDORS ARE INDICATED AS A 1 HOUR FIRE
 RATED CORRIDORS BUT THERE IS NO SEPERATION OF THE 1
 HOUR RATED CORRIDOE AND THE FILE STORAGE ROOM# 107.
  
 12) SHEET A-8 PLEASE PROVIDE COMPLIANCE WITH 11-4.22.2
 DOORS. ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL
 COMPLY WITH 11-4.13. DOORS SHALL NOT SWING INTO CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SEE ROOMS 117, 120, 121, & 1124.
  
 13) SHEET A-14 THE REFLECTED CEILING PLAN INDICATES A
 LARGE SQUARE TO THERIGHT OF THE RIGHT OF THE KITCHEN
 AND MECANICAL ROOM 24'X30' WITH 3 LIGHT FIXTURES? SHEET
 E-5 THIS AREA APPEARS EITHER AS ANOTHER
 BUILDING OR A OPEN PAVILION,(SHEET S2-S3) IS THIS
 STRUCTURE TO BE PART OF THIS PERMIT? ARE THEY TO
 REQUIRE FIRE SEPERATION BETWEEN THE TWO BUILDINGS TABLE
 602, OR ARE THEY TO BE CONSIDEREDAS ONE BUILDING AS
 UNDER SECTION 503.1.3 TWO BUILDINGS ON THE SAME LOT.
  
 14) SHEET A-7 INDICATES A BRICK VENNEER PLEASE PROVIDE
 DOCUMENTATION AS HOW THE VENEERS ARE TO BE ADHERRED.
 PLEASE SEE SECTION 2114.2 CONCRETE BEARING LEDGE.
 BRICK, STONE OR OTHER VENEER SHALL BE SUPPORTED BY A
 CONCRETE BEARING LEDGE AT LEAST EQUAL TO THE TOTAL
 THICKNESS OF THE BRICK, STONE OR OTHER VENEER, WHICH IS
 POURED INTEGRALLY WITH THE CONCRETE FOUNDATION. NO
 SUPPLEMENTAL CONCRETE FOUNDATION POURS WHICH WILL
 CREATE A HIDDEN COLD JOINT SHALL BE USED WITHOUT
 SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS THERE
 IS AN APPROVED PHYSICAL BARRIER. AN APPROVED PHYSICAL
 BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE WALL
 SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO EMBED
 IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS BELOW
 GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE APPLIED
 TO THE CAVITY CREATED BETWEEN THE VENEER AND THE
 FOUNDATION, IN LIEU OF A PHYSICAL BARRIER.
 EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL
 SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH
 ACI 530/ASCE 5/TMS 402, PROVIDED AT LEAST A 6-INCH (152
 MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL
 EXTERIOR EXIST BETWEEN THE VENEER AND THE TOP OF ANY
 SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING
 COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK
 IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE.
  
 15) SHEET S-2 DOES NOT INDICATE COMPLIANCE WITH 1816.1
 TERMITE PROTECTION.
  
 16) SHEET S-3 INDICATES THE TYPE OF CONNECTION TO BE
 USED AT EACH TRUSS LOCATION BUT THE FORCES THE
 CONNECTION NEEDS TO RESIST IS NOT PROVIDED, VERTICAL,
 HORIZONTAL AND LATERALL LOADS. 1609.2.1.
 PART OF THE MAIN WINDFORCE-RESISING SYSTEM. NOTE
 CONNECTION TYPE TS1WTCS INFORMATION COULD NOT EVEN BE
 ACCESSED ON THE TRUSSTEEL WEBSITE.
  
 17) SHEET S-3 TRUSS NOTE# 5 INDICATES TO SEE TRUSSSTEEL
 STANDARD DETAIL TS027A FOR THE WELDING OF TRUSS
 CONNECTION TO STEEL BEAM, NO SUCH DETAILS HAVE BEEN
 PROVIDED. NOTE IN MANY CASES
 THE MANUFACTURER OF THE CONNECTION STATES THAT WELDING
 OF CONNECTIONS IS PROHIBITED, PLEASE PROVIDE
 MANUFACTURERS APPROVAL FOR WELDING OF THIS TYPE OF
 CONNECTION. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 18) SHEET S-4 INDICATES A FOOTING TYPE A BUT THE PLANS
 ARE LACKING COLUMN AND BEAM INFORMATION, 1609.2.1 PART
 OFTHE MAIN WIND FORCE-RESISTING SYSTEM. PLEASE PROVIDE
 ADDITONAL INFORMATION, 106.1..2.
  
 19) SHEET A-4 ALSO INDICATES THE ROOFING ASSEMBLY TO BE
 A PREMANUFACTRED CANOPY, PLEASE PROVIDE PRODUCT
 INFORMATION, WILL NEED TO MEET THE REQUIREMENTS OF
 COMMENT NUMBER 8,9 & 10.
  
 20) STRUCTURAL SHEETS S-4, S-6 AND S-8 ROOF PRESSURE
 ZONES FAIL TO INDICATE PRESSURE ZONE 3 FAIL TO INDICATE
 CORNER ZONE# 3 AND THE ASSOCIATED PRESSURES, PLEASE
 REVIEW FIGURE 1609.6.2.2 COMPONENTS AND CLADDING.
  
 21) GENERATOR PAD IS SHOWN ON SHEET SD-1, IS THIS PAD
 GOING TO BE PART OF THIS PERMIT OR JUST INFORMATIONAL,
 THE GENERATOR AND ATTACHMENT TO SLAB WILL BE REVIEWED
 UNDER A SEPERATE PERMIT.
  
 22) SD-3 PLANS INDICATE STAIRS BUT THE STAIR LOCATION
 IS NOT SHOWN ON THE ARCHITECTURAL PLANS NOR THE
 STRUCTURAL PLAN INDICATES THEY ARE TO BE LOCATED WITHIN
 THE OPERATIONS AND MAINTENANCE BUILDING, WHERE /
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  