2008-10-10 12:15:00 | BUILDING PLAN REVIEW |
| PERMIT: 08090593 |
| ADD: 6880 N JOG RD |
| CONT:MAJOR WORKING DRAWING REVIEW |
| TEL: (772)231-4301 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| OFFICE BUILDING TYPE II-B 1,800 SQ FT |
| S-2 MAINTENANCE BUILDING TYPE II-B 1,000 SQ FT |
| |
| OCT 10,2008 |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) BOTH THE ARCHITECTURAL AND STRUCTURAL PLANS |
| INDICATE A PAVILION NEST TO THE ADMINISTRATIVE OFFICE |
| THE PLAN REVIEW SHEET SUBMITTED ONLY INDICATES A REVIEW |
| FOR THE OPERATIONS BUILDING AND MAINTENACE BUILDING . |
| IS THIS STRUCTURE TO BE PERMITTED WITH THIS WORK? IN |
| THE MINIMUM BUILDING CLASSIFICATION TYPE, IS THIS |
| STRUCTURE TO BE CONSIDERED IN THE SQ FT OF THE |
| OPERATIONS BUILDING UNDER SECTION 503.1.3 OR TWO |
| SEPERATE STRUCTURES WHERE TABLE 602 AND 704.8 WILL NEED |
| TO BE CONSIDERED? ADDITIONAL INFORMATION REQUIRED, |
| 106.1.2. |
| |
| 1E) I PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE REVISE. |
| |
| 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 4) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| SECTION 113 OF THIS CHAPTER. |
| |
| 5) NOTE SHEET CD-6 IS NOT SIGNED NOR SEALED, PLEASE |
| CORRECT. SHEET PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| |
| 6) PLANS DO NOT ENCLUDE ENERGY CALCULATIONS 106.3.5.1.4 |
| AND INPUT ENERGY CALCULATIONS. |
| |
| 7) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| MISSILE TEST. |
| |
| 8) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS: |
| 8A) FIXED WINDOWS |
| 8B) MULLIONS |
| 8C) EXTERIOR GLAZED DOORS |
| 8D) EXTERIOR METAL DOORS |
| 8E) ROLL UP DOORS |
| 8F) WALL LOUVERS |
| 8G) TRUSS ANCHORS |
| 8H) ROOF ASSEMBLIES |
| 8I) SOFFITS |
| |
| 9) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 10) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| OFFICE BUILDING TYPEII-B |
| |
| 11A) SHEET A3 INDICATES THE CORRIDOR# 111 TO BE ONE |
| HOUR RATED, THERE IS NO DOOR BETWEEN THE CORRIDOR AND |
| LOBBY 100, PLEASE INDICATE HOW OPENING PROTECTIVE |
| (715.3) ARE ACHIEVED IN THIS AREA. |
| |
| 11B) SHEET A-11 & SHEET A-14 APPEAR TO HAVE A 2'X2' LAY |
| IN TILE CEILING, PLANS DO NOT PROVIDE HOW THE 1 HOUR |
| RATING OF WALLS IS TO OCCUR, THROUGH TO THE ROOF DECK |
| OR A 1HR RATED CEILING. 708.1. |
| |
| 11C) SHEET A-4 INDICATES WALL TYPE AS 1 HOUR RATED |
| WALLS WITH WALL TAG (AD3) WITHIN THE CORRIDORS, SHEET |
| AD-1 INDICATES WITHIN THE DOOR LEGOND 45 MINUTE OPENING |
| PROTECTION FOR THE DOORS, DOOR D114 & D115 INDICATE THE |
| WRONG TYPE OF FRAMES, PLEASE CORRECT. |
| |
| 11D) SHEET A-4 CORRIDORS ARE INDICATED AS A 1 HOUR FIRE |
| RATED CORRIDORS BUT THERE IS NO SEPERATION OF THE 1 |
| HOUR RATED CORRIDOE AND THE FILE STORAGE ROOM# 107. |
| |
| 12) SHEET A-8 PLEASE PROVIDE COMPLIANCE WITH 11-4.22.2 |
| DOORS. ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL |
| COMPLY WITH 11-4.13. DOORS SHALL NOT SWING INTO CLEAR |
| FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| SEE ROOMS 117, 120, 121, & 1124. |
| |
| 13) SHEET A-14 THE REFLECTED CEILING PLAN INDICATES A |
| LARGE SQUARE TO THERIGHT OF THE RIGHT OF THE KITCHEN |
| AND MECANICAL ROOM 24'X30' WITH 3 LIGHT FIXTURES? SHEET |
| E-5 THIS AREA APPEARS EITHER AS ANOTHER |
| BUILDING OR A OPEN PAVILION,(SHEET S2-S3) IS THIS |
| STRUCTURE TO BE PART OF THIS PERMIT? ARE THEY TO |
| REQUIRE FIRE SEPERATION BETWEEN THE TWO BUILDINGS TABLE |
| 602, OR ARE THEY TO BE CONSIDEREDAS ONE BUILDING AS |
| UNDER SECTION 503.1.3 TWO BUILDINGS ON THE SAME LOT. |
| |
| 14) SHEET A-7 INDICATES A BRICK VENNEER PLEASE PROVIDE |
| DOCUMENTATION AS HOW THE VENEERS ARE TO BE ADHERRED. |
| PLEASE SEE SECTION 2114.2 CONCRETE BEARING LEDGE. |
| BRICK, STONE OR OTHER VENEER SHALL BE SUPPORTED BY A |
| CONCRETE BEARING LEDGE AT LEAST EQUAL TO THE TOTAL |
| THICKNESS OF THE BRICK, STONE OR OTHER VENEER, WHICH IS |
| POURED INTEGRALLY WITH THE CONCRETE FOUNDATION. NO |
| SUPPLEMENTAL CONCRETE FOUNDATION POURS WHICH WILL |
| CREATE A HIDDEN COLD JOINT SHALL BE USED WITHOUT |
| SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS THERE |
| IS AN APPROVED PHYSICAL BARRIER. AN APPROVED PHYSICAL |
| BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE WALL |
| SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO EMBED |
| IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS BELOW |
| GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE APPLIED |
| TO THE CAVITY CREATED BETWEEN THE VENEER AND THE |
| FOUNDATION, IN LIEU OF A PHYSICAL BARRIER. |
| EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL |
| SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH |
| ACI 530/ASCE 5/TMS 402, PROVIDED AT LEAST A 6-INCH (152 |
| MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL |
| EXTERIOR EXIST BETWEEN THE VENEER AND THE TOP OF ANY |
| SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING |
| COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK |
| IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE. |
| |
| 15) SHEET S-2 DOES NOT INDICATE COMPLIANCE WITH 1816.1 |
| TERMITE PROTECTION. |
| |
| 16) SHEET S-3 INDICATES THE TYPE OF CONNECTION TO BE |
| USED AT EACH TRUSS LOCATION BUT THE FORCES THE |
| CONNECTION NEEDS TO RESIST IS NOT PROVIDED, VERTICAL, |
| HORIZONTAL AND LATERALL LOADS. 1609.2.1. |
| PART OF THE MAIN WINDFORCE-RESISING SYSTEM. NOTE |
| CONNECTION TYPE TS1WTCS INFORMATION COULD NOT EVEN BE |
| ACCESSED ON THE TRUSSTEEL WEBSITE. |
| |
| 17) SHEET S-3 TRUSS NOTE# 5 INDICATES TO SEE TRUSSSTEEL |
| STANDARD DETAIL TS027A FOR THE WELDING OF TRUSS |
| CONNECTION TO STEEL BEAM, NO SUCH DETAILS HAVE BEEN |
| PROVIDED. NOTE IN MANY CASES |
| THE MANUFACTURER OF THE CONNECTION STATES THAT WELDING |
| OF CONNECTIONS IS PROHIBITED, PLEASE PROVIDE |
| MANUFACTURERS APPROVAL FOR WELDING OF THIS TYPE OF |
| CONNECTION. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 18) SHEET S-4 INDICATES A FOOTING TYPE A BUT THE PLANS |
| ARE LACKING COLUMN AND BEAM INFORMATION, 1609.2.1 PART |
| OFTHE MAIN WIND FORCE-RESISTING SYSTEM. PLEASE PROVIDE |
| ADDITONAL INFORMATION, 106.1..2. |
| |
| 19) SHEET A-4 ALSO INDICATES THE ROOFING ASSEMBLY TO BE |
| A PREMANUFACTRED CANOPY, PLEASE PROVIDE PRODUCT |
| INFORMATION, WILL NEED TO MEET THE REQUIREMENTS OF |
| COMMENT NUMBER 8,9 & 10. |
| |
| 20) STRUCTURAL SHEETS S-4, S-6 AND S-8 ROOF PRESSURE |
| ZONES FAIL TO INDICATE PRESSURE ZONE 3 FAIL TO INDICATE |
| CORNER ZONE# 3 AND THE ASSOCIATED PRESSURES, PLEASE |
| REVIEW FIGURE 1609.6.2.2 COMPONENTS AND CLADDING. |
| |
| 21) GENERATOR PAD IS SHOWN ON SHEET SD-1, IS THIS PAD |
| GOING TO BE PART OF THIS PERMIT OR JUST INFORMATIONAL, |
| THE GENERATOR AND ATTACHMENT TO SLAB WILL BE REVIEWED |
| UNDER A SEPERATE PERMIT. |
| |
| 22) SD-3 PLANS INDICATE STAIRS BUT THE STAIR LOCATION |
| IS NOT SHOWN ON THE ARCHITECTURAL PLANS NOR THE |
| STRUCTURAL PLAN INDICATES THEY ARE TO BE LOCATED WITHIN |
| THE OPERATIONS AND MAINTENANCE BUILDING, WHERE / |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |