Plan Review Notes
Plan Review Notes For Permit 08090591
Permit Number 08090591
Review Stop M
Sequence Number 3
Notes
Date Text
2009-01-24 13:57:15REVISED M2.1 DENIED:
  
 FLOOR PLAN SHOWS NEW AND EXISTING DUCTS PENETRATING
 FIRE RESISTANT RATED WALL WITHOUT PROTECTION. SHOW HOW
 THESE PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE
 WITH FBCM 607.5. ALSO, SHOW THE LOCATION OF EACH FIRE
 DAMPER ON THE PLANS IN ACCORDANCE WITH FBCM 607.8.
  
 NOTE: ARCHITECTURAL PLAN NOTE CALLSL FOR CONTRACTOR TO
 INSPECT AND REPAIR RATED WALLS TO MAINTAIN INTEGRITY OF
 SAME.
  