Plan Review Notes
Plan Review Notes For Permit 08090534
Permit Number 08090534
Review Stop B
Sequence Number 2
Notes
Date Text
2008-10-17 10:23:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE PAGE 14 OF THE PRODUCT APPROVAL. A 3" EDGE
 DISTANCE REQUIRES A FACTOR OF .83.
  
 2. THE "SHUTTER CONNECTION MOUNTING TYPE" SHOULD
 CORRELATE WITH THE ANCHOR CHARTS ON THE PRODUCT
 APPROVAL. IT APPEARS THAT YOU ARE USING MOUNTING TYPES
 A, D, AND I. PLEASE NOTE THAT, IF THE ANCHOR SPACING
 WERE COMPLIANT (SEE COMMENT #1), THIS PERMIT WOULD NOT
 HAVE BEEN DENIED FOR THIS REASON ONLY.
  
 3. ACCORDION SHUTTERS ARE, TO MY KNOWLEDGE, ALWAYS
 INSTALLED VERTICALLY (NOT HORIZONTALLY AS NOTED ON THE
 INSTALLATION SCHEDULE). PLEASE REVISE. ALSO PLEASE
 REVISE SPANS. FOR INSTANCE, OPENING 4 SPECIFIES A 209"
 SPAN. THIS EXCEEDS THE SPAN ALLOWED. FOR ACCORDION
 SHUTTERS, THE SPAN EQUALS BLADE LENGTH.