Plan Review Notes For Permit 08090534 |
Permit Number |
08090534 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-10-17 10:23:37 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. SEE PAGE 14 OF THE PRODUCT APPROVAL. A 3" EDGE | | DISTANCE REQUIRES A FACTOR OF .83. | | | | 2. THE "SHUTTER CONNECTION MOUNTING TYPE" SHOULD | | CORRELATE WITH THE ANCHOR CHARTS ON THE PRODUCT | | APPROVAL. IT APPEARS THAT YOU ARE USING MOUNTING TYPES | | A, D, AND I. PLEASE NOTE THAT, IF THE ANCHOR SPACING | | WERE COMPLIANT (SEE COMMENT #1), THIS PERMIT WOULD NOT | | HAVE BEEN DENIED FOR THIS REASON ONLY. | | | | 3. ACCORDION SHUTTERS ARE, TO MY KNOWLEDGE, ALWAYS | | INSTALLED VERTICALLY (NOT HORIZONTALLY AS NOTED ON THE | | INSTALLATION SCHEDULE). PLEASE REVISE. ALSO PLEASE | | REVISE SPANS. FOR INSTANCE, OPENING 4 SPECIFIES A 209" | | SPAN. THIS EXCEEDS THE SPAN ALLOWED. FOR ACCORDION | | SHUTTERS, THE SPAN EQUALS BLADE LENGTH. |
|