Date |
Text |
2008-09-19 14:39:51 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE |
| VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL |
| COST OF LABOR AND MATERIALS (THIS INCLUDES THE COST OF |
| THE FIRE PLACE EVEN IF OWNER SUPPLIED). VALUATION |
| REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF A |
| NATIONAL CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, |
| MEANS, ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S |
| DESK AND PAY THE DIFFERENCE IN FEES PRIOR TO |
| RESUBMITTING. PER (W.P.B. AS AMENDED) SECTION 108.3 |
| BUILDING PERMIT VALUATION. |
| |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE SECTION 401.1 SCOPE. |
| *NOTE: SUBMITTED ISOMETRIC DOES NOT INDICATE |
| CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| |
| 3. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| *NOTE: NOT ALL CUT SECTIONS OF PIPE INDICATE PIPE |
| MATERIAL. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| *NOTE: THE EXISTING BTU LOAD NEEDS TO BE INDICATED ON |
| THE PLANS. PLEASE REFERENCE THE PERMIT INFORMATION |
| SHEET OF SAID ADDRESS ATTACHED TO THESE COMMENTS |
| INDICATING EXISTING GAS AND COMPLY. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| *NOTE: THE EXISTING SYSTEMS LONGEST LENGTH NEEDS TO BE |
| INDICATED ON THE PLANS. |
| |
| 6. SUBMITTED PLANS ARE INDICATING A DELIVERY PRESSURE |
| OF 5 PSI, HOWEVER PLANS ARE ALSO INDICATING TABLES |
| 402.4(2) AND 402.4(14) WHICH ARE FOR 0.5 PSI DELIVERY |
| PRESSURE. PLEASE CORRECT AND CORRELATE PLANS AND IF |
| NEEDED CLEARLY INDICATE THE REQUIRED LINE PRESSURE |
| REGULATORS LOCATION (MP REGULATOR) ON THE RESUBMITTAL. |
| PLEASE KNOW THAT WITH ALL THE EXISTING APPLIANCES ON |
| THE SYSTEM THE EXISTING METER MIGHT HAVE A 2 PSI |
| DELIVERY PRESSURE. PER FBC-2004 FUEL GAS SECTION 410.1 |
| PRESSURE REGULATORS AND SECTION 401.1 SCOPE. |
| |
| 7. SUBMIT CALCULATIONS FOR THE FIRE PLACE COMBUSTION |
| AIR. PER FBC-2004 FUEL GAS CODE SECTION 304. |
| |
| 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| *NOTE: NEED MANUFACTURE SHEETS FOR THE FOLOWING |
| APPLIANCES AND EQUIPMENT. |
| |
| A} FIRE PLACE: CLEARLY INDICATE THE MAKE, MODEL NUMBER, |
| BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY |
| RECOGNIZED TESTING LABORATORY (LISTING EXAMPLES= CSA, |
| AGA,UL) |
| |
| B} MP REGULATOR: (SAME REQUIREMENTS REQUIRED FOR MP |
| REGULATORS AS WAS REQUESTED FOR THE FIRE PLACE). |
| |
| 9. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |