2008-09-30 14:33:19 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. PROVIDE A DETAIL OF THE BADU JET PUMP TWO 8" MAIN |
| DRAINS AS INDICATED ON SHEET 1. PLEASE KNOW THAT SHEET |
| 2 OF 2, PLUMBING DETAIL FOR BADU JET DOES NOT INDICATE |
| THE REQUIRED DRAINS. PER R4101.6.6.4. |
| |
| 2. SHEET 1 OF 2, INDICATES "SEE MFGR'S SPECS" FOR THE |
| BADU JET PUMP, HOWEVER NONE WERE PROVIDED. PLEASE |
| PROVIDE TWO COPIES OF MANUFACTURE SPECFICATION FOR THE |
| BADU JET PUMP CLEARLY INDICATING THE MAKE, MODEL NUMBER |
| AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| LABORATORY SUCH AS UL. PER (W.P.B. AS AMENDED) SECTION |
| 106.1.2 ADDITIOAL DATA REQUIRED. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |