Plan Review Notes
Plan Review Notes For Permit 08090455
Permit Number 08090455
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-30 15:12:51 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 106.1 SUBMITTABLE DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH APPLICATION FOR A PERMIT. *** ONE PLAN COPIED
 MARKED 1ST AND 2ND FLOOR WAS SUBMITTED FOR REVIEW. THE
 PENCIL SET MUST BE COPIED AS PENCIL IS NOT ACCEPTABLE
 FOR RETENTION. SUBMIT TWO SETS FOR EACH FLOOR.
  
 2} VERIFY THAT THE A/C UNITS ARE RATED AT 1500 WATTS.
  
 3} 220.84 MULTIFAMILY DWELLING
 (A) FEEDER OR SERVICE LOAD IT SHALL BE PERMISSIBLE TO
 CALCULATE THE LOAD OF A FEEDER OR SERVICE THAT SUPPLIES
 THREE OR MORE DWELLING UNITS OF A MULTIFAMILY DWELLING
 IN ACCORDANCE WITH TABLE 220.84 INSTEAD OF PART III OF
 THIS ARTICLE-----" THE CALCULATION GIVEN TOOK THE
 DEMAND FROM 220.42 AND THEN AN ADDITIONAL DEMAND FROM
 220.84, ONLY ONE DEMAND CAN BE TAKEN.SEE "INSTEAD OF".
  
 4} 220.84 (B) HOUSE LOADS HOUSE LOADS SHALL BE
 CALCULATED IN ACCORDANCE WITH PART III OF THIS ARTICLE
 AND SHALL BE IN ADDITION TO THE DWELLING UNIT LOADS
 CALCULATED IN ACCORDANCE WITH TABLE 220.84.*** NO LOAD
 FOR THE HOUSE WAS GIVEN.
  
 5} 220.52(B) LAUNDRY CIRCUIT LOAD A LOAD OF NOT LESS
 THAN 1500 VOLT-AMPERES SHALL BE INCLUDED FOR EACH
 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED AS REQUIRED BY
 210.11(C)(2). THIS LOAD SHALL BE PERMITTED TO BE
 INCLUDED WITH THE GENERAL LIGHTING LOAD AND SUBJECTED
 TO THE DEMAND FACTORS PROVIDED IN TABLE 220.42.*** THIS
 MAY BE WITH THE HOUSE CIRCUIT CALCULATION.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 6} 210.11(C)(2) LAUNDRY BRANCH CIRCUITS IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY
 RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F).*** THE
 HOUSE PANEL HAS THE LAUNDRY ON A 15 AMP CIRCUIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  