Plan Review Notes
Plan Review Notes For Permit 08090412
Permit Number 08090412
Review Stop B
Sequence Number 3
Notes
Date Text
2009-09-02 16:51:54BUILDING PLAN REVIEW
 PERMIT: 08090412
 ADD: 1610 PALM BEACH LAKES
 CONT: CFR COASTAL
 TEL: (954) 868-9692
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 WEDNESDAY SEPTEMBER 02/2009
 3RD REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT SURVEYS, PLANS,
 REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL
 REQUIRE A THRESHLD INSPECTOR BEING A THRESHOLD
 BUILDING, (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE
 REQUIRED FOR PERMIT ISSUANCE. 106.1* / 109.3.6, 2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.SHEET SP.01 UNDER
 BUILDING DATA DOES NOT PROVIDE AS TO WHAT CODE (YEAR)
 THIS PROJECT WAS DESIGNED.
  
 1E) PLEASE CORRECT. STRUCTURAL SHEET S.02 ALSO NEEDS TO
 BE UPDATED TO THE 2007 SUPPLEMENTS CURRENTLY READS 2006
 SUPPLEMENTS..
  
 1F) 2ND REQUEST, SP.01 CALCULATIONS THE BUILDING
 INFORMATION AND CODE SECTIONS ARE NOT TAKEN FROM THE
 2004 FBC PLEASE PROVIDE THE FOLLOWING BUILDING
 INFORMATION IN REGUARDS TO THE 2004 FBC:
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) TYPE OF OCCUPANCY, SHEET SP.01 INDICATE A A2
 OCCUPANCY, SECTION 303.1 INDICATES AN A2 OCCUPANCY IS
 RESTARAUNT, NIGHTCLUBS, BANQUET HALL, BARS AND
 NIGHTCLUBS PLEASE SEE A3 OCCUPANCY OF COMMUNITY HALLS,
 CHURCHES &AND COURT ROOMS, PLEASE REVISE.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503,
 CHAPTER 6, & TABLE 601, SP.01 CALCULATIONS INDICATE
 THIS TO BE A TYPE V-B / A-3 ASSEMBLY WITH 115373 SQ FT
 A TYPE V-B BUILDING WITH AREA INCREASESAND SPRINKLER
 THE MAXIMUM IS 28,500 SQ FT.. PLEASE CORRECT.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) SP.01- REFRENCES A 4 HR FIRE SEPERATION WALL WITH 3
 HR OPENING PROTECTIVES IS THIS AN ADDITION OR IS THIS A
 TRUE 4 HR FIRE WALL CREATING 2 SEPERATE BUILDINGS? I
 BELIEVE THE ELECTRICAL PLAN REVIEWERR HAD BROUGHT UP
 MANY PROBLEMS IN THE ELECTRICAL DESIGN IF THIS WAS TO
 BE CONSIDERED A SEPERATE BUILDING?
 .
 2) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD
 BUILDING BY DEFINTION; THRESHOLD INSPECTION PLAN FL S.
 S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) SUBMIT:SEMI-COMPLIED, SUBMITTED SPECIAL INSPECTOR
 AGREEMENT. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR
 THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY
 FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN CONRAD
 MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) COMPLIED.
  
 3A) LS.01 NO BLDG TYPE INFORMATION HAS BEEN PROVIDED AS
 REQUESTED UNDER (1F). THE PLAN INDICATES THE EXTERIROR
 WALL AS A 4 HR FIRE RATED WALL WITH AN OVERHEAD 3 HR
 RATED OPENING. THERE IS A SECOND SWING DOOR WITHIN THE
 4 HR RATED WALL AND A NOTE INDICATING ALL DOORS WITHIN
 THE HALLWAY TO BE 45 MINUTE RATED DOORS. THE OCCUPANCY
 SEPERATION INDICATED IN TABLE 302.3.2 A 3HR FIRE RATING
 AND 3 HR OPENING PROTECTIVES TABLE 715.3. THE EXISTING
 BREAK ROOM DOOR SHOULD READ 3 HR OPENING PROTECTIVE.
 LS.01 ALSO INDICATES AN EXIT LIGHT THAT LEADS YOU BACK
 INTO THE BUILDING, PLEASE PROVIDE RATIONAL .
  
 3B) COMPLIED.
  
 3C) COMMENT 3A) COVERS THIS OPENING.
  
 4) BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUIULDING PROVISO:
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE
 UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE
 WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED
 FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER
 AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO
 FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A
 LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE
 SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS
 CHAPTER.
  
 6) COMPLIED.
  
 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 3A) ROOF DECK OVER THE NEW KITHEN SHEET A.03 DETAIL 2 &
 A.06 DETAIL# 1DOES NOT PROVIDE INFORMATION AS TO TYPE
 OF ROOFING ASSEMBLIES TO BE APPLIED TO THE FLAT DECK.
  
  
 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9-15 ) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved