Date |
Text |
2009-01-28 16:46:10 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| CITY WPB MUNICIPAL CODE |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| |
| 7. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT |
| THE FOLLOWING INFORMATION: |
| |
| A. OK |
| B. OK |
| C. OK |
| |
| D. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| ****RESPONSE NOTED, PRESSURE NOT INDICATED. |
| |
| E. OK |
| |
| F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT MANUF SHEETS FOR THE WATER |
| HEATER NOT SUBMITTED. |
| |
| G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE AND |
| THE UNION ARE NOT INDICATED ON THE RISER DIAGRAM. THE |
| EMERGENCY SHUT OFF VALVE WILL ALSO SHUT OFF THE WATER |
| HEATER. WAS THIS THE INTENT OF THE DESIGN PROFESSIONAL? |
| PLEASE CLARIFY. |
| |
| 8. OK |
| 9. OK |
| 10. OK |
| |
| 11. SHT P.02 DETAIL 2 WATER RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN. ONE P-6 SINK IS NOT SHOWN. |
| PLEASE CORRELATE. SECTIONS 106.1.1 & 604. |
| ****RESPONSE NOTED. BUT THE PIPING TO THE P-6 SINK |
| STILL DOES NOT REFLECT THE FLOOR PLAN AS INDICATED. |
| PLEASE CORRELATE. ALSO THE WATER HAMMER ARRESTORS SHALL |
| BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", |
| NOT IN THE CEILING AS SOME ARE SHOWN. PDI-WH 201. |
| |
| 12. OK |
| 13. OK |
| |
| 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| UTILITY DEPT., INDUSTRIAL PRETREATMENT. PLEASE CONTACT |
| MR. WILLIAM ROBERTS, (561) 822-2200 EXT. 2272, - FAX |
| (561) 659-7458 - E-MAIL [email protected]. ARTICLE III |
| SECTION 90-124. PLEASE SUBMIT WRITTEN DETERMINATION ON |
| INTERCEPTOR SIZE WHEN RESUBMITTING PLANS FOR PERMIT. |
| ****RESPONSE NOTED, BUT THE REQUIREMENT IS FOR A 1250 |
| GAL INTERCEPTOR AND THE PLANS SHOW A 750 GAL |
| INTERCEPTOR. PLEASE SHOW REQUIRED SIZE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |