2009-02-01 13:05:17REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE SYMBOL LEGEND PROVIDES NO SYMBOL TO BE USED FOR
 FIRE DAMPERS. THE INDICATION IS THAT FIRE DAMPERS ARE
 TO BE IDENTIFIED WITH "FD" BUT THERE ARE NO LOCATIONS
 INDICATED BY USING THIS DESIGNATION ON FLOOR PLANS.
 PLEASE SHOW ON PLANS WHERE EACH FIRE DAMPER IS LOCATED
 WITH THE USE OF A CLEARLY IDENTIFIED AND RECOGNIZABLE
 SYMBOL OR INDICATOR IN ACCORDANCE WITH FBCM 607.8 AND
 FBCB 106.1.1.
  
 2 THROUGH 9: OK
  
 10. DESIGNER???S RESPONSE INDICATES THERE IS A CONCERN
 REGARDING THE LACK OF A RETURN AIR INTAKE IN THE
 KITCHEN FOR WHEN THE EXHAUST FAN IS NOT RUNNING. IF
 BALANCED RETURN CAN NOT BE ACHIEVED WITH THIS
 CONFIGURATION (AS REQUIRED IN ACCORDANCE WITH FBCM
 601.4) THEN IT IS THE DESIGNER???S RESPONSIBILITY TO
 DESIGN A SYSTEM WHICH MEETS DESIGN REQUIREMENTS IN A
 CODE COMPLIANT MANNER. SOME SUGGESTED OPTIONS ARE:
 DESIGNING A RETURN FOR THIS AREA WITH A MOTORIZED OR
 BAROMETRIC DAMPER THAT WILL OPEN WHEN THE KITCHEN
 EXHAUST IS NOT OPERATIONAL. THERE MAY BE OTHER OPTIONS
 AVAILABLE AT THE DESIGNER???S DISCRETION. PLEASE CALL
 TO DISCUSS IF NECESSARY.
  
 11. OK
  
 12. NOTE ON FLOOR PLAN CLAIMS DUCTS OF 100 SQ. IN. OR
 LESS DO NOT REQUIRE FIRE DAMPERS. NO SUCH EXCEPTION
 COULD BE FOUND IN THE CODE. THERE IS A SIX-PART
 EXCEPTION FOR FIRE DAMPERS IN FIRE PARTITIONS (SEE FBCM
 607.5.3 EXCEPTION #2), BUT ALL SIX CONDITIONS MUST BE
 MET TO UTILIZE THE EXCEPTION. ALSO, FLOOR PLAN SHOWS
 FLEX DUCTS PENETRATING A WALL IDENTIFIED AS FIRE RATED
 ON ARCHITECTURAL PLANS. FLEXIBLE DUCTS AND AIR
 CONNECTORS SHALL NOT PASS THROUGH ANY
 FIRE-RESISTANCE-RATED ASSEMBLY IN ACCORDANCE WITH FBCM
 607.7. IN ANY CASE, DUCTS PENETRATING FIRE RATED
 ASSEMBLIES SHALL BE PROTECTED WITH FIRE DAMPERS OR A
 THROUGH-PENETRATION FIRESTOP SYSTEM IN ACCORDANCE WITH
 FBCM 607.1.1. IF AN EXCEPTION TO THE REQUIREMENT FOR
 FIRE DAMPERS IN DUCTS, PLEASE SEE EXCEPTION #1 UNDER
 FBCM 607.5.3 IF THIS IS A FULLY SPRINKLERED BUILDING.
  
 13 THROUGH 15: OK
  
 16. NOTE ???I??? ON M.02 IS IN CONFLICT WITH THE NOTE
 ON M.04 REGARDING DAMPER OPERATION. PLEASE COORDINATE
 NOTES SHOWING COMPLIANCE WITH FBCM 508.1.
  
 17. DETAIL FOR FAN COIL UNIT NOW SHOWS A DUCT DETECTOR
 ON THE SUPPLY AS REQUIRED BY FBCM 606.2.1. HOWEVER,
 DETAIL #15 ON PAGE M.05 SHOWS THE DUCT DETECTOR
 INSTALLED ON THE RETURN. PLEASE CORRECT.
  
 NEW COMMENTS BASED ON NEW INFORMATION AND?OR DETAILS
 PROVIDED:
  
 18. CONDENSATE DETAIL #8 ON PAGE M.05 CALLS FOR AN
 AUXILIARY DRAIN FROM AN AUXILIARY DRAIN PAN TO BE
 ROUTED TO THE "NEAREST WET COLUMN." THIS DOES NOT
 CORRESPOND WITH THE REQUIREMENTS FOR AUXILIARY DRAIN
 PROTECTION UNDER FBCM 607.2.3. PLEASE SHOW A MEANS OF
 AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH THIS
 SECTION.
 NOTE: THE DETAIL CALLS FOR A FLOAT SWITCH IN THE
 AUXILIARY DRAIN PAN. THIS WOULD BE COMPLIANT WITH NO
 AUXILIARY DRAIN LINE INSTALLED ON THE PAN.
  
 19. DETAIL #6 ON M.05 SHOWS A LOUVER INSTALLATION.
 LOUVERS ARE DEFINED AS PANEL WALLS PER FAC RULE 9B-72
 AND ARE SUBJECT TO THE FLORIDA PRODUCT APPROVAL SYSTEM.
 PROVIDE PRODUCT APPROVAL DOCUMENTATION FOR THE SPECIFIC
 LOUVERS TO BE INSTALLED WITH INSTALLATION INSTRUCTIONS.
  
 20. ENERGY CALCULATIONS ARE NOT SIGNED AND SEALED BY
 THE DESIGNER OF RECORD AND/OR OWNER-AGENT AS REQUIRED
 BY FBCB 13-103.1.1 AND 13-103.2.
  