2009-01-28 16:36:08 | DENIED |
| REFERENCE: |
| FBC-2004 FUEL GAS |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT |
| THE FOLLOWING INFORMATION: |
| |
| A. OK |
| B. OK |
| C. OK |
| |
| D. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| ****RESPONSE NOTED, BUT DELEVERY PRESSURE IS NOT |
| INDICATED. |
| |
| E. OK |
| |
| F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE GAS |
| WATER HEATER HAVE NOT BEEN SUBMITTED. |
| |
| G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| ****RESPONSE, NOTED, BUT THE MANUAL SHUT OFF VALVE AND |
| THE UNION ARE NOT INDICATED ON THE RISER DIAGRAM. THE |
| EMERGENCY SHUT OFF VALVE WILL ALSO SHUT OFF THE WATER |
| HEATER. WAS THIS THE INTENT OF THE DESIGN PROFESSIONAL? |
| PLEASE CLARIFY. |
| |
| 2. OK |
| 3. OK |
| 4. OK |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |