Plan Review Notes For Permit 08090412 |
Permit Number |
08090412 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-02-09 15:36:01 | *****DENIED***** | | | | THE FOLLOWING COMMENTS (NOT MARKED OK) TAKEN FROM THE | | PREVIOUS FIRE REVIEW STILL NEED TO BE ADDRESSED: | | | | 1. LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | ADD TO CODE ANALYSIS DATA SECTION OF THE SUBMITTED PLAN | | | | 2. OK | | | | 3. IN ADDITION TO 2A-10BC RATED, "K" RATED FIRE | | EXTINGUISHERIS REQUIRED FOR SMALL GREASE FIRE | | PROTECTION. COULD NOT LOCATE THE "K" EXTINGUISHER ON | | SHEET LS-1 AS INDICATED IN YOUR RESPONSE LETTER | | | | 4. | | | | 5. OK | | | | 6. OK | | | | 7. SHEET E.05 INDICATES CARD READERS AND KEYPADS. | | ACCESS CONTROL SYSTEMS SHALL COMPLY WITH NFPA 101, | | SEC.7.2.1.6.2. ADD COMMENT TO THE APPROPIATE PLAN SHEET | | | | 8. OK | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE/HOW EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|