Plan Review Notes
Plan Review Notes For Permit 08090412
Permit Number 08090412
Review Stop E
Sequence Number 2
Notes
Date Text
2009-01-14 11:42:59** DENIED 2ND REVIEW **
  
  
 ** UNTIL DATE OF REVIEW THERE WAS NO SPECIFIC CONTACT
 FOR ELECTRICAL. DURING REVIEW A CALL WAS PLACED TO JOHN
 VAUGHAN. ELECTRICAL ENGINEER JAMES MAKO CALLED TO GO
 OVER COMMENTS.
 SEVERAL ITEMS WERE GONE OVER HOWEVER AS THE REVIEW WAS
 NOT COMPLETE AT THE TIME OF THE CONVERSATION A FUTURE
 CALL MAY BE NEEDED ONCE ALL REVIEW NOTES ARE POSTED.
 SOME NOTES FROM PREVIOUS REVIEW WILL REMAIN ALONG WITH
 NEW COMMENTS BASED ON THE DOCUMENTS NOW PLACED ON THE
 PLANS AND SUBMITTED WITH THE DOCUMENTS.
  
 1) NOTE: PLEASE BE AWARE THAT THE NOTICE OF
 COMMENCEMENT WHICH WAS RECORDED ON SEPTEMBER 15TH, 2008
 HAS BECOME VOID. PLEASE SEE FS 713.13(2).
 WHEN WORK HAS NOT COMMENCED WITHIN 90DAYS OF RECORDING
 SUCH NOC THE NOC BECOMES VOIDED. THIS WOULD ONLY NEED
 TO BE RE-RECORDED.
 THIS COMMENT IS GIVEN AS INFORMATION ONLY TO HELP
 AVOIDED ANY DELAYS IN THE PERMITTING AND INSPECTION
 PROCESS FOR THE OWNER AND CONTRACTOR.
  
 2) NOTE: PLEASE SEE FBC 13-101.1, 13-400.0.
 THE PREVIOUS REVIEW REQUESTED LIGHTING PERFORMANCE
 CALCULATIONS IN CONFORMANCE WITH THE FBC CHAPTER 13,
 13-415.2.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3.
 THE SUBMITTED METHOD *A* MAY BE USED WHEN YOU HAVE A
 WHOLE BUILDING OR AN ADDITION WHICH IS NOT INCLUDING
 ANY RENOVATION TO ANY EXISTING BUILDING AREAS.
 THE METHOD *A* SUBMITTED DOES NOT CONTAIN ANY
 SIGNATURE, OR DATE BY THE RESPONSIBLE DESIGNER.
 MUST CONTAIN THESE PER 13-103.1. PLEASE SEE DESIGNERS
 PERMITTED TO DO THIS UNDER FLORIDA STATUTES 471, 481
 AND 489.
 THE METHOD *A* SUBMITTED CLEARLY STATES *RENOVATION TO
 EXISTING BUILDING*. IF THIS IS NOT AN ADDITION, OR
 WHOLE BUILDING NEW CONSTRUCTION THEN THIS METHOD MAY
 NOT BE USED.
 IN ANY CASE ALL INFORMATION ON ANY INPUT DATA REPORT
 NEEDS TO COORDINATE WITH ALL INFORMATION ON PLANS.
 THERE ARE SEVERAL ITEMS ON THE IDR AS SUBMITTED WHICH
 ARE EITHER NOT COMPLETE OR THESE ITEMS ARE NOT THE SAME
 AS ON PLANS.
 EXAMPLES:
 THE METHOD OF LIGHTING CONTROLS STATE *MANUAL ON/OFF*.
 THIS IS NOT THE CASE AS ANY NEW PRESCRIPTIVE LIGHTING
 CONTROLS IN A BUILDING GREATER THAN 5K SQ FT SHALL
 COMPLY WITH 13-415.1.ABC.1, .1.1, .1.2, .1.3 AND .1.4.
 SEE THE FOLLOWING COMMENT WITH RESPECT TO LIGHTING
 CONTROLS.
 EXAMPLE:
 THE EXTERIOR LIGHTING ON THE IDR IS COMPLETELY BLANK.
 THIS IS ONE ITEM WHICH THE PLANS CLEARLY CONTAIN
 EXTERIOR LIGHTING YET THERE ARE NO FIXTURES ON THE
 IDR.??
 THE PLANS INDICATE SPACE BY SPACE FROM TABLE *B*.
 PLEASE SEE 13-415.2.ABC.1 WHICH CLEARLY STATES THAT IS
 NOTE PERMITTED TO USE MORE THAN ONE METHOD.
 THIS REVIEWER IS OK WITH USE OF SPACE BY SPACE FOR
 LIGHTING PERFORMANCE LEVELS HOWEVER WE WOULD STILL NEED
 EXTERIOR PER 13-415.2.ABC.1.3.
  
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4 FOR REQUIRED LIGHTING CONTROLS.
 ALL LIGHTING IN A BUILDING GREATER THAN 5K SQ FT SHALL
 CONTAIN SOME SORT OF AUTOMATED CONTROLS SO WHEN THE
 BUILDING IS NOT OCCUPIED THE LIGHTING. THERE ARE
 COUNTLESS ARTICLES ON THE ENERGY CODE IN THE STATE OF
 FLORIDA AS WELL AS THE REQUIREMENTS NATIONALLY IN THE
 IECC.
 THE FEDERAL CHANGES IN JULY OF 2004 IN THE INTEREST OF
 ENERGY CONSERVATION REQUIRED ALL STATES BY THEIR
 FOLLOWING CODE CYCLE TO ADOPT THE 1999 ASHAE 90.1 OR
 BETTER. SINCE OCTOBER 1ST, 2005 THE 2004 FBC HAS
 REQUIRED THIS. THIS HAS BEEN IN THE CODE FOR OVER 3 AND
 HALF YEARS. THERE HAVE ALSO BEEN SEVERAL REVISIONS TO
 THE 2004 FBC SINCE ADOPTED IN OCT.2005
 THE RESPONSE LETTER CONTAINS RESPONSES TO ALL OTHER
 COMMENTS WITH THE EXCEPTION OF THIS PREVIOUS COMMENT.
 THE RESPONSE IS BLANK?
 ** PLEASE CALL TO GO OVER IF NEEDED. THIS IS NOT A
 SEPARATE BUILDING BY DEFINITION SMALLER THAN 5K SQ FT.
 THE SWITCHING SHOWN ON PLANS IS DONE BY STANDARD SINGLE
 POLE SWITCHES ALONG WITH STANDARD 3-WAY SWITCHES. THE
 INFORMATION ON SHEET E.04.11 IS NOT ENOUGH FOR
 COMPLIANCE. THE KITCHEN IS NOT AN AREA WHICH IS EXEMPT
 PER THE FBC. PLEASE CALL TO GO OVER. THERE ARE
 SUBSTANTIAL DIFFERENCES IN MOTION SENSORS COMPARED TO
 DUAL TECHNOLOGY DEVICES AND ALSO THESE SAME TYPE OF
 DEVICES USED FOR EGRESS WHICH WOULD BE FAIL SAFE
 OPERATION.
  
 4) NOTE: PLEASE SEE PREVIOUS COMMENTS WITH RESPECT TO
 FBC 11-4.28.1, .2 AND .3 FOR ALL DEVICES FOR FA SYSTEM
 TO COMPLY WITH MINIMUM LEVELS, HEIGHTS ETC FOR ADA
 COMPLIANCE.
 THE RESPONSE MENTIONS TO SEE REVISED PLANS HOWEVER THE
 FA SHEET E.06 DOES NOT INDICATE THE MINIMUM LEVELS FOR
 STROBES AND SOUNDING DEVICES.
 PLEASE ALSO SEE THERE ARE SEVERAL NOTES WHICH THERE
 SEEMS TO HAVE BEEN SOME SORT OF MISHAP WITH THE
 PRINTING. SEE NOTES 17 UNDER FIRE ALARM NOTES, NOTES
 UNDER SEQUENCE OF OPERATION, NOTES UNDER THE SYMBOL
 LEGENDS WHICH HAS NOTES PRINTED OVER NOTES. MANY ITEMS
 CAN NOT BE READ.
 THESE HAVE BEEN HIGH-LIGHTED ON ONE OF THE SET OF
 PLANS.
 SHEET E.06.1 ALSO DOES NOT CONTAIN ANY OF THIS MONTHS
  
 5) NOTE: THE FOLLOWING ITEMS WITH RESPECT TO RISER,
 PANELS, ETC STILL NEED COORDINATION.
  
 A) PLEASE SEE PANEL HU-2 WHICH INDICATES 125AMP OVER
 CURRENT PROTECTION TO A 100AMP DISCONNECT ON THE LINE
 SIDE OF TRANSFORMER
 B) PLEASE SEE TRANSFORMER EK. RISER AND PLANS NOTE THIS
 NEW 45KVA UNIT WILL BE REPLACING THE EXISTING 30 KVA
 TRANSFORMER. THIS IS OK, HOWEVER PLEASE SEE THE
 TRANSFORMER SCHEDULE ALONG WITH THE PRIMARY OVER
 CURRENT PROTECTION.
 THE SCHEDULE SHOWS A 45KVA TRANSFORMER HOWEVER ONLY
 WITH THE AMPERAGE RATING OF THE PREVIOUS 30KVA UNIT.
 45KVA AT 480V IS 54.15AMPS NOT THE 36 AS LISTED ON
 SCHEDULE. THE 36 AS LISTED ON SCHEDULE WOULD BE A 30KVA
 UNIT AT 480V.
 THIS WILL AFFECT THE OVER CURRENT PROTECTION ON THE
 PRIMARY ALSO AS THIS IS NOTED AS 45AMPS.
 THESE ITEMS AFFECT THE POWER PANEL SCHEDULE SHEET AS
 WELL AS *BOTH* RISERS ON SHEET E.02.
 110.3,110.14,450.3,240.4,310.16,408, 240.21 ETC
  
 6) NOTE: PLEASE SEE 210.8B2 AS ALL 15/20AMP 120V
 RECEPTACLES IN KITCHEN AREAS SHALL BE GFCI/ OR GFCI
 PROTECTED. SEE CIRCUITS SUCH AS EK-9, EK-11 ARE TWO
 EXAMPLES IN WHICH NO PROTECTION IS SHOWN. THESE ARE NOT
 THE ONLY TWO.
  
 7) NOTE: AS NO LIGHTING ETC IS SHOWN FOR A COMPLETE
 HOOD SYSTEM AND HOOD MAY BE UNDER SEPARATE PERMIT
 PLEASE KNOW THAT ALL LIGHTING AND ELECTRICAL PER
 NFPA-96 SHALL BE INTERCONNECTED AND SHUT DOWN UPON
 ACTIVATION OF SYSTEM FOR FIRE SUPPRESSION.
 NO INFORMATION NOTED AT THIS TIME AND WILL NEED TO BE
 NOTED UNDER SEPARATE PERMIT.
  
 8) NOTE: SHEET E.05 CONTAINS SOME NOTES FOR POSSIBLE
 ACCESS CONTROL. THE SYMBOL LEGEND MAKES NOTE OF
 POSSIBLE MAG-LOCKS ETC.
 PLEASE SEE NFPA-101 CHAPTER 7 FOR EGRESS CONTROLS. NO
 DEVICES UNDER NORMAL OR EMERGENCY CONDITIONS SHALL
 IMPEDE THE EGRESS OUT OF ANY AREAS. SEE COMMENTS FROM
 FIRE MARSHAL.
 AS THE COMPLETE SYSTEM IS NOT DETAILED, THIS MAY BE
 UNDER SEPARATE PERMIT FOR LOW VOLTAGE ACCESS CONTROLS.
 FBC 105.1.
  
 9) NOTE: MANY OF THE FIXTURES ARE HALF SHADED AND
 SYMBOL LEGEND SEEMS TO INDICATE EMERGENCY POWER. THE
 FIXTURE LEGEND HOWEVER DOES NOT LIST ANY BATTERY BACK
 UP BALLAST AS REQUIRED.
 PLEASE ADJUST. NFPA-101 7.8, 7.9, FBC 1006.1
 PLEASE ALSO KNOW AS NOTED ABOVE, ANY EGRESS LIGHTING
 BEING CONTROL BY OCCUPANCY SENSOR TYPES DEVICES PER FBC
 13-415.1.ABC.1, SHALL BE FAIL SAFE TYPE CONTROL DEVICES
 PER FBC 1006.1.2, NFPA-101 7.8.1.2.2.
  
 10) NOTE: PLEASE COMPLETE ALL LIGHTING CIRCUITS ON
 PLANS AND COORDINATE WITH THE PANEL SCHEDULES.
 BE SURE TO SEE 7..12F FOR CIRCUITING FOR EMERGENCY AND
 EXIT LIGHTS.
 408.4, FBC 106.1.1, 106.5.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  