Plan Review Notes
Plan Review Notes For Permit 08090412
Permit Number 08090412
Review Stop P
Sequence Number 1
Notes
Date Text
2008-09-22 15:31:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS ARE REVIEWED UNDER THE ADOPTED CODES WHICH ARE
 THE FBC-2004 W/2007 REVISIONS. PLEASE INDICATE CODES
 THE WORK IS DESIGNED UNDER ON THE PLANS. SECTION
 106.1.1.
  
 2. SHT A.01 FLOOR PLAN SHOWS A KITCHEN WITH PANTRY, A
 TOILET ROOM, AN OFFICE, A MECHANICAL ROOM AND UPPER
 LEVEL WORK AS WELL AS A COVERED PARKING STRUCTURE. THE
 APPLICATION INDICATES A KITCHEN ADDITION & A COVERED
 PARKING STRUCTURE. PER APPLICATION, PLEASE DESCRIBE THE
 PROJECT IN DETAIL. INDICATE ALL WORK TO BE DONE UNDER
 THIS PERMIT. SECTIONS 105.1 & 105.3.
  
 3. SHT A.04 COLUMN LINE 37 INDICATES A RAIN WATER
 LEADER IN THE COLUMN. IS THIS A NEW RWL? IF SO PLEASE
 INDICATE WHERE IT TERMINATES, THE SIZE OF THE RWL, AND
 FROM WHERE DOES THE RWL ORIGINATE. SECTIONS 106.1.2,
 1106 & 1107.
  
 4. SHT A.05 SHOW COMPLIANCE WITH SECTIONS 11-4.16.5
 FLUSH CONTROLS, 11-4.19.2 CLEARANCES, 11-4.19.4 EXPOSED
 PIPES & SURFACES & 11-4.19.5 FAUCETS.
  
 5. SHT P.01 THE LOCATION OF THE GAS WATER HEATER DOES
 NOT CORRELATE WITH THE LOCATION OF THE WATER HEATER
 SHOWN ON THE FLOOR PLAN ON SHT A.01, NOR DOES THE GAS
 PIPING SHOWN ON THE FLOOR PLAN & GAS RISER REFLECT THE
 LOCATION OF THE WATER HEATER ON EITHER SHEET. PLEASE
 CORRELATE & CLARIFY. SECTIONS 106.1.1 & 402.
  
 6. SHT P.01 FLOOR PLAN AND PLUMBING RISER. THE DISH
 WASHERS SHALL DISCHARGE INTO THE SANITARY SYSTEM, NOT
 THE GREASE SYSTEM. MUNICIPAL CODE, ARTICLE III SECTION
 90-124(7)(B).
  
 7. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. LENGHTS NOT SHOWN.
  
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). TOTAL IS 510,000 BUT IS SHOWN AS 410,000.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. FOR WATER HEATER.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 8. SHT P.01 THE GAS RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE SOLENOID VALVE ON THE FLOOR PLAN DOES
 NOT APPEAR TO CONNECT TO THE PIPING AS INDICATED ON THE
 RISER DIAGRAM AND THERE APPEARS TO BE TWO SUPPLY LINES
 ON THE STEAM POT. PLEASE CLARIFY. SECTIONS 106.1.1 &
 402.
  
 9. SHT P.01 GAS RISER DIAGRAM. PLEASE SHOW THE LOCATION
 OF THE DRIPS/SEDIMENT TRAPS AS REQUIRED IN SECTIONS
 408.2 & 408.4.
  
 10. SHTS P.02 & P.03 THE ADDRESS OF THE ENGINEERING
 BUSINESS SHALL BE INDICATED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61B15-23.002(2) & FS 471.025.
  
 11. SHT P.02 DETAIL 2 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. ONE P-6 SINK IS NOT SHOWN.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 604.
  
 12. SHT P.02 WATER HEATER DETAIL. A VACUUM RELIEF VALVE
 IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS PER
 SECTION 504.2. -- THE P/T RELIEF VALVE SHALL BE
 INSTALLED IN THE SHELL OF THE WATER HEATER TAN, PER
 SECTION 504.4.1. -- THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION SECTION 607.3.2. PLEASE INDICATE
 METHOD.
  
 13. SHT P.03 A VACUUM BREAKER IS REQUIRED ON THE HOSE
 BIBB INDICATED ON THE CAN WASH DETAIL. SECTION
 608.15.4.2.
  
 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT., INDUSTRIAL PRETREATMENT. PLEASE CONTACT
 MR. WILLIAM ROBERTS, (561) 822-2200 EXT. 2272, - FAX
 (561) 659-7458 - E-MAIL [email protected]. ARTICLE III
 SECTION 90-124. PLEASE SUBMIT WRITTEN DETERMINATION ON
 INTERCEPTOR SIZE WHEN RESUBMITTING PLANS FOR PERMIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  