2008-09-22 15:31:02 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| CITY WPB MUNICIPAL CODE |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. PLANS ARE REVIEWED UNDER THE ADOPTED CODES WHICH ARE |
| THE FBC-2004 W/2007 REVISIONS. PLEASE INDICATE CODES |
| THE WORK IS DESIGNED UNDER ON THE PLANS. SECTION |
| 106.1.1. |
| |
| 2. SHT A.01 FLOOR PLAN SHOWS A KITCHEN WITH PANTRY, A |
| TOILET ROOM, AN OFFICE, A MECHANICAL ROOM AND UPPER |
| LEVEL WORK AS WELL AS A COVERED PARKING STRUCTURE. THE |
| APPLICATION INDICATES A KITCHEN ADDITION & A COVERED |
| PARKING STRUCTURE. PER APPLICATION, PLEASE DESCRIBE THE |
| PROJECT IN DETAIL. INDICATE ALL WORK TO BE DONE UNDER |
| THIS PERMIT. SECTIONS 105.1 & 105.3. |
| |
| 3. SHT A.04 COLUMN LINE 37 INDICATES A RAIN WATER |
| LEADER IN THE COLUMN. IS THIS A NEW RWL? IF SO PLEASE |
| INDICATE WHERE IT TERMINATES, THE SIZE OF THE RWL, AND |
| FROM WHERE DOES THE RWL ORIGINATE. SECTIONS 106.1.2, |
| 1106 & 1107. |
| |
| 4. SHT A.05 SHOW COMPLIANCE WITH SECTIONS 11-4.16.5 |
| FLUSH CONTROLS, 11-4.19.2 CLEARANCES, 11-4.19.4 EXPOSED |
| PIPES & SURFACES & 11-4.19.5 FAUCETS. |
| |
| 5. SHT P.01 THE LOCATION OF THE GAS WATER HEATER DOES |
| NOT CORRELATE WITH THE LOCATION OF THE WATER HEATER |
| SHOWN ON THE FLOOR PLAN ON SHT A.01, NOR DOES THE GAS |
| PIPING SHOWN ON THE FLOOR PLAN & GAS RISER REFLECT THE |
| LOCATION OF THE WATER HEATER ON EITHER SHEET. PLEASE |
| CORRELATE & CLARIFY. SECTIONS 106.1.1 & 402. |
| |
| 6. SHT P.01 FLOOR PLAN AND PLUMBING RISER. THE DISH |
| WASHERS SHALL DISCHARGE INTO THE SANITARY SYSTEM, NOT |
| THE GREASE SYSTEM. MUNICIPAL CODE, ARTICLE III SECTION |
| 90-124(7)(B). |
| |
| 7. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT |
| THE FOLLOWING INFORMATION: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. LENGHTS NOT SHOWN. |
| |
| B. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). TOTAL IS 510,000 BUT IS SHOWN AS 410,000. |
| |
| C. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. FOR WATER HEATER. |
| |
| D. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| E. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| |
| F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| |
| 8. SHT P.01 THE GAS RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN. THE SOLENOID VALVE ON THE FLOOR PLAN DOES |
| NOT APPEAR TO CONNECT TO THE PIPING AS INDICATED ON THE |
| RISER DIAGRAM AND THERE APPEARS TO BE TWO SUPPLY LINES |
| ON THE STEAM POT. PLEASE CLARIFY. SECTIONS 106.1.1 & |
| 402. |
| |
| 9. SHT P.01 GAS RISER DIAGRAM. PLEASE SHOW THE LOCATION |
| OF THE DRIPS/SEDIMENT TRAPS AS REQUIRED IN SECTIONS |
| 408.2 & 408.4. |
| |
| 10. SHTS P.02 & P.03 THE ADDRESS OF THE ENGINEERING |
| BUSINESS SHALL BE INDICATED IN THE TITLE BLOCK OF EACH |
| SHEET. FAC 61B15-23.002(2) & FS 471.025. |
| |
| 11. SHT P.02 DETAIL 2 WATER RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN. ONE P-6 SINK IS NOT SHOWN. |
| PLEASE CORRELATE. SECTIONS 106.1.1 & 604. |
| |
| 12. SHT P.02 WATER HEATER DETAIL. A VACUUM RELIEF VALVE |
| IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS PER |
| SECTION 504.2. -- THE P/T RELIEF VALVE SHALL BE |
| INSTALLED IN THE SHELL OF THE WATER HEATER TAN, PER |
| SECTION 504.4.1. -- THERMAL EXPANSION CONTROL IS |
| REQUIRED PER SECTION SECTION 607.3.2. PLEASE INDICATE |
| METHOD. |
| |
| 13. SHT P.03 A VACUUM BREAKER IS REQUIRED ON THE HOSE |
| BIBB INDICATED ON THE CAN WASH DETAIL. SECTION |
| 608.15.4.2. |
| |
| 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| UTILITY DEPT., INDUSTRIAL PRETREATMENT. PLEASE CONTACT |
| MR. WILLIAM ROBERTS, (561) 822-2200 EXT. 2272, - FAX |
| (561) 659-7458 - E-MAIL [email protected]. ARTICLE III |
| SECTION 90-124. PLEASE SUBMIT WRITTEN DETERMINATION ON |
| INTERCEPTOR SIZE WHEN RESUBMITTING PLANS FOR PERMIT. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |