2008-09-30 16:53:27REVIEW #:
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE A.02: THERE ARE SEVERAL SYMBOLS ON THE
 REFLECTIVE CEILING PLAN WHICH DO NOT APPEAR ON THE
 SYMBOL LEGEND. PLEASE PROVIDE CLARIFICATION AND
 IDENTIFICATION OF EACH ITEM TO BE INSTALLED IN THE
 CEILING. THIS CEILING SPACE IS TO SERVE AS A RETURN AIR
 PLENUM AND ALL ITEMS IN THIS PLENUM MUST BE IDENTIFIED
 TO DEMONSTRATE COMPLIANCE WITH FBCM 602.2.
  
 2. PAGE A.02: NOTE ON THIS PAGE INDICATES R-19
 INSULATION TO BE INSTALLED ABOVE THE CEILING. THIS
 CEILING SERVES AS A PLENUM AND THEREFORE THE INSULATION
 AND THERMAL BARRIER MUST BE ABOVE THE PLENUM SPACE.
 CAVITIES BENEATH A ROOF DECK WHICH WILL BE USED AS
 SUPPLY OR RETURN PLENUMS SHALL HAVE AN INSULATED ROOF.
 THE INSULATION SHALL HAVE AN R-VALUE OF AT LEAST R-19
 IN ACCORDANCE WITH FBCB 13-404.1.ABC.2. ALSO, ROOF
 INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE CEILING PANELS IN ACCORDANCE
 WITH FBCB 13-404.1.ABC.1.
  
 3. KITCHEN EXHAUST SYSTEM: THERE IS NOT ENOUGH
 INFORMATION PROVIDED WITH THIS SUBMITTAL TO DO A
 THOROUGH REVIEW OF THE COMMERCIAL KITCHEN GREASE
 EXHAUST SYSTEM. SEPARATE PLANS AND PERMIT APPLICATIONS
 WILL BE REQUIRED FOR THE HOOD AND HOOD SUPPRESSION
 SYSTEMS. HOWEVER, THE FOLLOWING CONDITIONS ARE EVIDENT
 ON THESE PLANS AND SHALL BE ADDRESSED PRIOR TO PERMIT
 ISSUANCE:
  
 4. EXHAUST OUTLETS SHALL BE PERMITTED TO TERMINATE
 THROUGH EXTERIOR WALLS WHERE THE SMOKE, GREASE, GASES,
 VAPORS, AND ODORS IN THE DISCHARGE FROM SUCH
 TERMINATIONS DO NOT CREATE A PUBLIC NUISANCE OR A FIRE
 HAZARD IN ACCORDANCE WITH FBCM 506.3.12.2. SINCE THIS
 FAN DOES NOT APPEAR TO BE IN A LOCATION ACCESSIBLE TO
 THE PUBLIC, FIRE HAZARD IS THE PRIMARY CONCERN HERE,
 ALTHOUGH GREASE ACCUMULATION ON WALKING SURFACES MAY
 ALSO CREATE A HAZARD.
  
 5. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10
 FEET ABOVE THE ADJOINING GRADE LEVEL IN ACCORDANCE WITH
 FBCM 506.3.12.3. BASED ON THE HEIGHT OF THE BALCONY
 ABOVE IT DOES NOT APPEAR FEASIBLE TO INSTALL A FAN
 WHERE THE BOTTOM OF THE FAN WILL BE A MINIMUM OF 10
 FEET ABOVE GRADE.
  
 6. EXHAUST FANS SHALL BE POSITIONED SO THAT THE
 DISCHARGE WILL NOT IMPINGE ON THE ROOF, OTHER EQUIPMENT
 OR APPLIANCES OR PARTS OF THE STRUCTURE IN ACCORDANCE
 WITH FBCM 506.5.2. THE LOCATION OF THE FAN AS SHOWN ON
 THE PLANS WILL BE DIRECTLY ADJACENT TO THE ROOF/BALCONY
 ABOVE, PROMOTING GREASE ACCUMULATION ON THE STRUCTURE
 AND CREATING A FIRE HAZARD. SEE ALSO COMMENT 3A ABOVE.
  
 7. EXHAUST AIR SHALL NOT BE DIRECTED ONTO WALKWAYS IN
 ACCORDANCE WITH FBCM 401.5.2.
  
 8. DETAIL #9 ON PAGE M0.5 SHOWS THE KITCHEN EXHAUST
 DUCT SIZED AT 16X20. WITH A VOLUME OF 1930 CFM AS SHOWN
 ON THE EQUIPMENT SCHEDULE, THE VELOCITY OF THE EXHAUST
 AIR WITHIN THE GREASE DUCT WILL BE APPROXIMATELY 869
 FPM. GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL BE
 DESIGNED AND INSTALLED SO AS TO PROVIDE AN AIR VELOCITY
 WITHIN THE DUCT SYSTEM OF NOT LESS THAN 1,500 FEET PER
 MINUTE AND NOT GREATER THAN 2,500 FEET PER MINUTE IN
 ACCORDANCE WITH FBCM 506.3.4.
  
 9. THE AIR BALANCE SCHEDULE DOES NOT CORRESPOND WITH
 THE INFORMATION ON FLOOR PLANS AND SCHEDULES. EXAMPLE:
 THERE IS NO INFORMATION ON THE PLANS REGARDING THE BATH
 EXHAUST, UTILITY EXHAUST OR WATER HEATER EXHAUST. THESE
 APPLIANCES SHALL BE LISTED IN THE EQUIPMENT SCHEDULE IN
 ACCORDANCE WITH FBCB 106.3.5 AND FBCM 301.1.
  
 10. THE REFLECTIVE CEILING PLAN SHOWS A RETURN AIR
 GRILL IN THE KITCHEN ADJACENT TO THE KITCHEN HOOD. AS
 THIS UNIT PROVIDES AIR FOR STORAGE, OFFICE AND RESTROOM
 SPACES, IT IS NOT DEDICATED TO THE KITCHEN AREA
 EXCLUSIVELY. RETURN AIR INTAKE SHALL BE PROHIBITED IN
 NON-DEDICATED KITCHEN HVAC SYSTEMS IN ACCORDANCE WITH
 FBCM 407.1.
  
 11. PAGE M0.4 FLOOR PLAN SHOWS CEILING MOUNTED EXHAUST
 FANS IN BATHROOM AND UTILITY ROOM. PLAN ALSO INDICATES
 A POWER VENT TYPE SYSTEM FOR THE WATER HEATER. THESE
 SYSTEMS CAN NOT BE INSTALLED IN A RETURN AIR PLENUM
 CEILING. EXHAUST DUCTS UNDER POSITIVE PRESSURE,
 CHIMNEYS, AND VENTS SHALL NOT EXTEND INTO OR PASS
 THROUGH PLENUMS IN ACCORDANCE WITH FBCM 601.3.
  
 12. PLEASE IDENTIFY ON PLANS THE LOCATION OF EACH FIRE
 DAMPER AT EACH DUCT PENETRATION OR TRANSFER OPENING.
 THE SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH
 FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER SHALL BE
 SHOWN AND PROPERLY IDENTIFIED ON THE BUILDING PLANS BY
 THE DESIGNER IN ACCORDANCE WITH FBCM 607.8.
  
 13. MECHANICAL PLAN INDICATES GAS WATER HEATER IN THE
 UTILITY ROOM WITH POWER VENT. PLUMBING AND
 ARCHITECTURAL PLANS SHOW THIS WATER HEATER IN THE
 MECHANICAL ROOM WHICH SERVES AS A RETURN AIR PLENUM.
 WHICH IS CORRECT? COMBUSTION WATER HEATERS AND
 ATMOSPHERIC COMBUSTION FURNACES SHALL NOT BE LOCATED IN
 MECHANICAL CLOSETS USED AS RETURN AIR PLENUMS IN
 ACCORDANCE WITH FBCM 603.9.
  
 14. PLEASE INDICATE ON PLANS THE TYPE OF WALL FINISHES
 TO BE USED ON THE TYPE 1 AND TYPE 2 WALLS AT THE
 MECHANICAL ROOM. THE WALL SCHEDULE INDICATES THE TYPE 1
 WALLS FINISHED ON 1 SIDE AND THE TYPE 2 WALLS WITH NO
 FINISH. THIS ROOM IS BEING USED AS A PLENUM. THE PLENUM
 SHALL BE LINED WITH AN APPROVED AIR BARRIER AND
 INSULATED IN ACCORDANCE WITH FBCM 607.8, 607.9 AND FBCB
 TABLE 13-410.1.ABC.2.2. SEE FBCM 603.9.1 FOR A LIST OF
 APPROVED AIR BARRIERS.
  
 15. COOLING LOAD CALCULATIONS: THESE CALCULATIONS
 INDICATE TOTAL OUTSIDE AIR OF 400 CFM WHILE THE PLANS
 INDICATE THAT A MINIMUM OF 1930 CFM IS REQUIRED FOR
 KITCHEN EXHAUST MAKEUP AIR. PLEASE CLARIFY. ALSO, PAGE
 A0.1 INDICATES REMOTE CONDENSERS FOR THE REFRIGERATORS
 AND FREEZERS ARE TO BE LOCATED IN THE CLOSET. THESE ARE
 HEAT PRODUCING APPLIANCES. ARE THEY ACCOUNTED FOR IN
 THE CALCULATIONS? ARE THESE CONDENSERS APPROVED FOR
 INSTALLATION IN A PLENUM? SEE FBCB 13-407.1.ABC.1 AND
 FBCM 602.2.
  
 16. NOTE I ON FAN COIL SCHEDULE INDICATES THAT THE OA
 DAMPER IS ONLY TO BE OPEN DURING OCCUPIED HOURS AS SET
 BY THE BAS. THIS DAMPER, AND THE RELATED FAN COIL UNIT
 SHALL BE INTERLOCKED WITH THE KITCHEN HOOD EXHAUST
 SYSTEM TO ENSURE THAT THE DAMPER IS OPEN AND THE FAN
 COIL IS OPERATING DURING ALL COOKING OPERATIONS,
 REGARDLESS OF THE SETTINGS OF THE BAS. FOR MECHANICAL
 MAKEUP AIR SYSTEMS, THE EXHAUST AND MAKEUP AIR SYSTEMS
 SHALL BE ELECTRICALLY INTERLOCKED TO ENSURE THAT MAKEUP
 AIR IS PROVIDED WHENEVER THE EXHAUST SYSTEM IS IN
 OPERATION IN ACCORDANCE WITH FBCM 508.1.
  
 17. THERE IS NO INDICATION ON MECHANICAL OR ELECTRICAL
 PLANS THAT THERE IS A DUCT SMOKE DETECTOR INSTALLED ON
 THE FAN COIL UNIT. FAN SHUT DOWN BY SMOKE DETECTOR IS
 REQUIRED IN ACCORDANCE WITH FBCM 606.2. DUCT SMOKE
 DETECTORS SHALL BE CONNECTED TO THE BUILDING FIRE ALARM
 SYSTEM IN ACCORDANCE WITH FBCM 606.4.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DESCRIPTION OF HOW EACH COMMENT WAS ADDRESSED AND WHERE
 THE RELEVANT INFORMATION CAN BE FOUND. THIS WILL ASSIST
 IN FACILITATING A TIMELY REVIEW.
  