Plan Review Notes
Plan Review Notes For Permit 08090412
Permit Number 08090412
Review Stop G
Sequence Number 1
Notes
Date Text
2009-01-28 16:18:00DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 1. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. LENGHTS NOT SHOWN.
  
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). TOTAL IS 510,000 BUT IS SHOWN AS 410,000.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. FOR WATER HEATER.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 2. SHT P.01 THE GAS RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE SOLENOID VALVE ON THE FLOOR PLAN DOES
 NOT APPEAR TO CONNECT TO THE PIPING AS INDICATED ON THE
 RISER DIAGRAM AND THERE APPEARS TO BE TWO SUPPLY LINES
 ON THE STEAM POT. PLEASE CLARIFY. SECTIONS 106.1.1 &
 402.
  
 3. SHT P.01 GAS RISER DIAGRAM. PLEASE SHOW THE LOCATION
 OF THE DRIPS/SEDIMENT TRAPS AS REQUIRED IN SECTIONS
 408.2 & 408.4.
  
 4. SHTS P.02 & P.03 THE ADDRESS OF THE ENGINEERING
 BUSINESS SHALL BE INDICATED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61B15-23.002(2) & FS 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved