Date |
Text |
2009-01-28 16:18:00 | DENIED |
| REFERENCE: |
| FBC-2004 FUEL GAS |
| |
| 1. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT |
| THE FOLLOWING INFORMATION: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. LENGHTS NOT SHOWN. |
| |
| B. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). TOTAL IS 510,000 BUT IS SHOWN AS 410,000. |
| |
| C. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. FOR WATER HEATER. |
| |
| D. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| E. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| |
| F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| |
| 2. SHT P.01 THE GAS RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN. THE SOLENOID VALVE ON THE FLOOR PLAN DOES |
| NOT APPEAR TO CONNECT TO THE PIPING AS INDICATED ON THE |
| RISER DIAGRAM AND THERE APPEARS TO BE TWO SUPPLY LINES |
| ON THE STEAM POT. PLEASE CLARIFY. SECTIONS 106.1.1 & |
| 402. |
| |
| 3. SHT P.01 GAS RISER DIAGRAM. PLEASE SHOW THE LOCATION |
| OF THE DRIPS/SEDIMENT TRAPS AS REQUIRED IN SECTIONS |
| 408.2 & 408.4. |
| |
| 4. SHTS P.02 & P.03 THE ADDRESS OF THE ENGINEERING |
| BUSINESS SHALL BE INDICATED IN THE TITLE BLOCK OF EACH |
| SHEET. FAC 61B15-23.002(2) & FS 471.025. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |