Plan Review Notes For Permit 08090412 |
Permit Number |
08090412 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-10-23 13:30:04 | ***DENIED*** | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | 2) RAMPS TO COMPLY WITH 101, SEC. 7.2.5. PROVIDE | | PRESCRIPTIVE STRENGTH REQUIREMENTS FOR HANDRAILS AND | | GUARDRAILS. | | | | 3) IN ADDITION TO 2A-10 B,C RATED, "K" RATED FIRE | | EXTINGUISHER IS REQUIRED IN KITCHEN FOR SMALL GREASE | | FIRE PROTECTION. | | | | 4) IT DOES NOT APPEAR THAT ENOUGH AUDIBLE FIRE ALARM | | EQUIPMENT IS ILLUSTRATED IN KITCHEN AND SURROUNDING | | AREA. | | | | 5) IS THE KITCHEN AREA CONSIDERED A SEPARATE STRUCTURE | | AS A RESULT OF THE EXISTING (4) HOUR RATED FIRE WALL? | | | | 6) HOOD/SUPPRESSION SYSTEM TO COMPLY WITH THE | | REQUIREMENTS OF NFPA 96 AND SHALL BE TIED INTO THE | | BUILDING FIRE ALARM SYSTEM. SEPARATE SHOP DRAWINGS AND | | PERMITS ARE REQUIRED FOR HOOD/SUPPRESSION SYSTEM. | | | | 7) SHEET E.05 INDICATES CARD READERS. ACCESS CONTROL | | SYSTEMS SHALL COMPLY WITH 101, SEC. 7.2.1.6.2. SEPARATE | | SHOP DRAWINGS AND PERMIT REQUIRED PRIOR TO INSTALLATION | | OF EQUIPMENT. | | | | 8) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|