Date |
Text |
2008-10-08 08:39:58 | |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE SEE THERE IS A LIST OF *EXPIRED* |
| PERMITS BASED ON PRIME PERMIT APPLIED FOR THIS SCOPE OF |
| WORK FROM 2005. THE BASE PERMIT IS 05041896. |
| THERE ARE ITEMS ON PLANS WHICH DO NOT SHOW UP ON RECORD |
| PLANS SUBMITTED IN LAST 10YEARS. THE EXPIRED APPLIED |
| SCOPE OF WORK AS MENTIONED SHOWS SOME OF THIS WORK TO |
| BE DONE HOWEVER NO RECORD OF PERMITTING. A FIELD |
| PRE-INSPECTION MAY BE NEEDED TO VERIFY ALL PERMITTED |
| SCOPE OF WORK. |
| |
| 2) NOTE: PLEASE SEE COMMENTS WHICH WILL BE FROM OTHER |
| TRADES WHICH WILL HAVE AN AFFECT ON THE ELECTRICAL |
| PLANS. |
| PLEASE BE SURE THESE ARE ALL COORDINATED. |
| PLEASE SUBMIT COMPLETED PLANS. SEE NOTES BELOW AS THERE |
| ARE SEVERAL ITEMS WHICH WERE EITHER NOT SHOWN ON NOT IN |
| DESIGN AT THIS TIME. THERE MAY VERY WELL BE NEW |
| COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| AT THIS TIME. |
| |
| 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE ON |
| PLANS. |
| 2004 FBC W/ 2007 REVISIONS. |
| |
| 4) NOTE: THE PLANS SUBMITTED DO NOT INCLUDE ANY |
| ELECTRICAL FOR THE NEW DETACHED PARKING STRUCTURE. |
| PLEASE BE SURE TO SEE 225.31-225.39, AND 250.32, 250.50 |
| |
| 5) NOTE: PLEASE PROVIDE MINIMUM LOCATIONS AND LEVELS |
| FOR ALL HORN/STROBE DEVICES FOR FIRE ALARM SYSTEM |
| MEETING FS 633, NFPA-72 AND FBC 11-4.28.1, 2 AND .3. |
| PLEASE BE SURE TO SHOW ALL LOCATIONS AND MINIMUM LEVELS |
| OF DEVICES. |
| |
| 6) NOTE: PLEASE SEE RISER AND PANEL SCHEDULES AS THERE |
| ARE SEVERAL INCONSISTENCIES. BELOW ARE SOME EXAMPLES |
| HOWEVER THESE ARE ARE NOT ALL. |
| |
| EXAMPLE: PLEASE SEE MAIN DISTRIBUTION PANEL AS THIS |
| INDICATES A FEED TO DP1 THROUGH A TRANSFORMER HOWEVER |
| THE RISER DOES NOT INDICATE ANY TRANSFORMER AND BOTH |
| MAIN SWITCH BOARD AND DP1 IS 277/480. PLEASE CORRECT. |
| |
| EXAMPLE: PLEASE SEE RISER WHICH INDICATES PANEL EK AS |
| EXISTING YET THE SCHEDULE SHOWS THIS AS NEW. |
| |
| EXAMPLE: PLEASE SEE RISER WHICH INDICATES PANEL K AS |
| EXISTING YET THE SCHEDULE SUBMITTED SHOWS THIS AS NEW. |
| |
| EXAMPLE: NOTES ON RISER SHEETS MENTIONS SOME |
| TRANSFORMER WILL BE CHANGED TO 75 KVA YET THE RISER |
| SHOWS BOTH OF THEM AS 45KVA. |
| |
| EXAMPLE: PLEASE SEE HU2 ON RISER WHICH INDICATES AS |
| 80AMP BREAKER TO THE TRANSFORMER YET THE PANEL SCHEDULE |
| INDICATES 90AMP BREAKER. |
| |
| THESE ARE SOME EXAMPLES ONLY WHICH ELECTRICAL RISER AND |
| PANELS NEED SOME COORDINATION. |
| |
| NEC 230,215,240,408,220, ETC |
| FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION, |
| CLARITY AND COORDINATION. |
| |
| 7) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH |
| THE PANEL SCHEDULE. THERE ARE SEVERAL INCONSISTENCIES |
| WITH WHAT IS SHOWN ON THE PLANS WITH CIRCUITS WHICH ARE |
| SHOWN ON SCHEDULES. SOME CIRCUITS ON PANELS WHICH ARE |
| ON PLANS ARE BLANK, SOME ARE SPARES, AND MANY ARE NOTED |
| FOR ELECTRICAL EQUIPMENT AND CIRCUITS WHICH ARE NOT THE |
| SAME ON PLANS. BELOW ARE SOME EXAMPLES AND IS IN NO WAY |
| ALL ITEMS. |
| |
| EXAMPLE: PLEASE SEE PLANS AS SOME CIRCUITS ARE LABELED |
| WITH AN *XXX-XX* ETC |
| |
| EXAMPLE: PLEASE SEE CIRCUIT K-23 ON PLANS AS THIS IS |
| BLANK ON SCHEDULE. |
| |
| EXAMPLE: PLEASE SEE K 16, AND 18 AS THESE ARE NOTED AS |
| THE DISHWASHERS ON PLANS YET THE PANEL SCHEDULE |
| INDICATES THESE ARE MICROWAVES. |
| |
| EXAMPLE: PLEASE SEE EK-23,25,27 ON PLAN AS ALL OF THESE |
| ARE BLANK ON THE PANEL SCHEDULE. |
| |
| EXAMPLE: PLEASE SEE EK-14, 12 WHICH ARE SHOWN ON PLAN |
| FOR REFRIGERATOR/FREEZER EQUIPMENT YET THE PANEL |
| SCHEDULES INDICATES A BREAKER FOR LIGHTING AND THE |
| OTHER IS SHOWN AS A SPARE. |
| |
| EXAMPLE: PLEASE SEE K-29 WHICH IS SHOWN ON PLANS |
| FEEDING GFI RECEPTACLES FOR BATH ROOM ETC YET THE PANEL |
| SCHEDULE INDICATES THIS AS LIGHTING. |
| |
| EXAMPLE: PLEASE SEE CIRCUITS EK 4, AND 6 WHICH IS SHOWN |
| AS REFRIGERATOR EQUIPMENT YET THE PANEL SCHEDULE |
| INDICATES A 3-POLE BREAKER FOR SUMP PUMPS. |
| |
| *** THESE ARE ONLY SOME OF THE EXAMPLES IN WHICH |
| COORDINATION IS NEEDED. THERE ARE OTHERS HOWEVER THIS |
| REVIEW IS GIVING SOME EXAMPLES AS BENEFIT TO THE |
| DESIGNER OF RECORD. |
| PLEASE SEE THE SECTION OF 408.4 WHICH WAS EXTRACTED |
| FROM THE 2005 NEC. |
| |
| 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION |
| EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL |
| BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON |
| THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A |
| PANELBOARD, AND LOCATED AT EACH SWITCH ON A |
| SWITCHBOARD. |
| THE REQUIREMENT TO PROVIDE AN UP-TO-DATE, ACCURATE, AND |
| LEGIBLE CIRCUIT DIRECTORY APPLIES TO PANELBOARDS AND |
| SWITCHBOARDS COVERED IN ARTICLE 408. THE CIRCUIT |
| DIRECTORY IS AN IMPORTANT FEATURE FOR THE SAFE |
| OPERATION OF AN ELECTRICAL SYSTEM UNDER NORMAL AND |
| EMERGENCY CONDITIONS. THE PURPOSE OF AN ACCURATE AND |
| LEGIBLE CIRCUIT DIRECTORY IN THESE TYPES OF EQUIPMENT |
| IS TO PROVIDE CLEAR IDENTIFICATION OF CIRCUIT BREAKERS |
| AND SWITCHES THAT MAY NEED TO BE OPERATED BY SERVICE |
| PERSONNEL OR THOSE WHO NEED TO OPERATE A SWITCH OR |
| CIRCUIT BREAKER IN AN EMERGENCY. THIS REQUIREMENT IS |
| SPECIFIC TO SWITCHBOARDS AND PANELBOARDS; HOWEVER, THE |
| IDENTIFICATION REQUIREMENTS OF 110.22 APPLY TO ALL |
| DISCONNECTING MEANS. |
| SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS SECTION. |
| |
| NEC 408.4, 310.16,240.4 ETC |
| FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION, |
| COORDINATION AND CLARITY OF PLANS. |
| |
| 8) NOTE: PLEASE SEE 450.3 AS THE OVER CURRENT |
| PROTECTION ON RISER FOR TRANSFORMER FEEDING PANEL *K* |
| IS TOO HIGH. THE RISER DOES CONTAIN A SCHEDULE WHICH |
| NOTES OVER CURRENT PROTECTION AT THE MAXIMUM OF 125%. |
| HOWEVER THE RISER STILL ALSO SHOWS THIS SAME |
| TRANSFORMER AS A 45KVA UNIT. IF THIS UNIT IS REVISED TO |
| 75KVA THEN THE 90AMP OCP WOULD BE OK. |
| |
| 9) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2, .1.3 AND |
| .1.4 FOR MISSING LIGHTING CONTROLS FOR ALL NEW LIGHTING |
| BEING INSTALLED. AS NO DEVICES OR SYSTEM IS BEING SHOWN |
| AT THIS TIME NO REVIEW OF THESE CAN BE DONE. |
| |
| 10) NOTE: PLEASE COMPLETE A FIXTURE LEGEND FOR SPECIFIC |
| FIXTURES. PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS FOR ALL AREAS IN SCOPE OF WORK. PLEASE SEE |
| FBC 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3. |
| PLEASE KNOW AS NO PERFORMANCE CALCULATIONS WERE |
| SUBMITTED IT IS NOT POSSIBLE TO SUPPLY ANY REVIEW |
| COMMENTS ON THOSE ITEMS. |
| |
| 11) NOTE: PLEASE KNOW ANY LOW VOLTAGE FOR SOUND, ACCESS |
| CONTROL WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT, |
| WITH PLANS AND FEES BASED ON THAT SCOPE OF WORK. |
| |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |