Plan Review Notes
Plan Review Notes For Permit 08090412
Permit Number 08090412
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-08 08:39:58 
 ** DENIED **
  
 1) NOTE: PLEASE SEE THERE IS A LIST OF *EXPIRED*
 PERMITS BASED ON PRIME PERMIT APPLIED FOR THIS SCOPE OF
 WORK FROM 2005. THE BASE PERMIT IS 05041896.
 THERE ARE ITEMS ON PLANS WHICH DO NOT SHOW UP ON RECORD
 PLANS SUBMITTED IN LAST 10YEARS. THE EXPIRED APPLIED
 SCOPE OF WORK AS MENTIONED SHOWS SOME OF THIS WORK TO
 BE DONE HOWEVER NO RECORD OF PERMITTING. A FIELD
 PRE-INSPECTION MAY BE NEEDED TO VERIFY ALL PERMITTED
 SCOPE OF WORK.
  
 2) NOTE: PLEASE SEE COMMENTS WHICH WILL BE FROM OTHER
 TRADES WHICH WILL HAVE AN AFFECT ON THE ELECTRICAL
 PLANS.
 PLEASE BE SURE THESE ARE ALL COORDINATED.
 PLEASE SUBMIT COMPLETED PLANS. SEE NOTES BELOW AS THERE
 ARE SEVERAL ITEMS WHICH WERE EITHER NOT SHOWN ON NOT IN
 DESIGN AT THIS TIME. THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE ON
 PLANS.
 2004 FBC W/ 2007 REVISIONS.
  
 4) NOTE: THE PLANS SUBMITTED DO NOT INCLUDE ANY
 ELECTRICAL FOR THE NEW DETACHED PARKING STRUCTURE.
 PLEASE BE SURE TO SEE 225.31-225.39, AND 250.32, 250.50
  
 5) NOTE: PLEASE PROVIDE MINIMUM LOCATIONS AND LEVELS
 FOR ALL HORN/STROBE DEVICES FOR FIRE ALARM SYSTEM
 MEETING FS 633, NFPA-72 AND FBC 11-4.28.1, 2 AND .3.
 PLEASE BE SURE TO SHOW ALL LOCATIONS AND MINIMUM LEVELS
 OF DEVICES.
  
 6) NOTE: PLEASE SEE RISER AND PANEL SCHEDULES AS THERE
 ARE SEVERAL INCONSISTENCIES. BELOW ARE SOME EXAMPLES
 HOWEVER THESE ARE ARE NOT ALL.
  
 EXAMPLE: PLEASE SEE MAIN DISTRIBUTION PANEL AS THIS
 INDICATES A FEED TO DP1 THROUGH A TRANSFORMER HOWEVER
 THE RISER DOES NOT INDICATE ANY TRANSFORMER AND BOTH
 MAIN SWITCH BOARD AND DP1 IS 277/480. PLEASE CORRECT.
  
 EXAMPLE: PLEASE SEE RISER WHICH INDICATES PANEL EK AS
 EXISTING YET THE SCHEDULE SHOWS THIS AS NEW.
  
 EXAMPLE: PLEASE SEE RISER WHICH INDICATES PANEL K AS
 EXISTING YET THE SCHEDULE SUBMITTED SHOWS THIS AS NEW.
  
 EXAMPLE: NOTES ON RISER SHEETS MENTIONS SOME
 TRANSFORMER WILL BE CHANGED TO 75 KVA YET THE RISER
 SHOWS BOTH OF THEM AS 45KVA.
  
 EXAMPLE: PLEASE SEE HU2 ON RISER WHICH INDICATES AS
 80AMP BREAKER TO THE TRANSFORMER YET THE PANEL SCHEDULE
 INDICATES 90AMP BREAKER.
  
 THESE ARE SOME EXAMPLES ONLY WHICH ELECTRICAL RISER AND
 PANELS NEED SOME COORDINATION.
  
 NEC 230,215,240,408,220, ETC
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION,
 CLARITY AND COORDINATION.
  
 7) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH
 THE PANEL SCHEDULE. THERE ARE SEVERAL INCONSISTENCIES
 WITH WHAT IS SHOWN ON THE PLANS WITH CIRCUITS WHICH ARE
 SHOWN ON SCHEDULES. SOME CIRCUITS ON PANELS WHICH ARE
 ON PLANS ARE BLANK, SOME ARE SPARES, AND MANY ARE NOTED
 FOR ELECTRICAL EQUIPMENT AND CIRCUITS WHICH ARE NOT THE
 SAME ON PLANS. BELOW ARE SOME EXAMPLES AND IS IN NO WAY
 ALL ITEMS.
  
 EXAMPLE: PLEASE SEE PLANS AS SOME CIRCUITS ARE LABELED
 WITH AN *XXX-XX* ETC
  
 EXAMPLE: PLEASE SEE CIRCUIT K-23 ON PLANS AS THIS IS
 BLANK ON SCHEDULE.
  
 EXAMPLE: PLEASE SEE K 16, AND 18 AS THESE ARE NOTED AS
 THE DISHWASHERS ON PLANS YET THE PANEL SCHEDULE
 INDICATES THESE ARE MICROWAVES.
  
 EXAMPLE: PLEASE SEE EK-23,25,27 ON PLAN AS ALL OF THESE
 ARE BLANK ON THE PANEL SCHEDULE.
  
 EXAMPLE: PLEASE SEE EK-14, 12 WHICH ARE SHOWN ON PLAN
 FOR REFRIGERATOR/FREEZER EQUIPMENT YET THE PANEL
 SCHEDULES INDICATES A BREAKER FOR LIGHTING AND THE
 OTHER IS SHOWN AS A SPARE.
  
 EXAMPLE: PLEASE SEE K-29 WHICH IS SHOWN ON PLANS
 FEEDING GFI RECEPTACLES FOR BATH ROOM ETC YET THE PANEL
 SCHEDULE INDICATES THIS AS LIGHTING.
  
 EXAMPLE: PLEASE SEE CIRCUITS EK 4, AND 6 WHICH IS SHOWN
 AS REFRIGERATOR EQUIPMENT YET THE PANEL SCHEDULE
 INDICATES A 3-POLE BREAKER FOR SUMP PUMPS.
  
 *** THESE ARE ONLY SOME OF THE EXAMPLES IN WHICH
 COORDINATION IS NEEDED. THERE ARE OTHERS HOWEVER THIS
 REVIEW IS GIVING SOME EXAMPLES AS BENEFIT TO THE
 DESIGNER OF RECORD.
 PLEASE SEE THE SECTION OF 408.4 WHICH WAS EXTRACTED
 FROM THE 2005 NEC.
  
 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL
 BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON
 THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD.
 THE REQUIREMENT TO PROVIDE AN UP-TO-DATE, ACCURATE, AND
 LEGIBLE CIRCUIT DIRECTORY APPLIES TO PANELBOARDS AND
 SWITCHBOARDS COVERED IN ARTICLE 408. THE CIRCUIT
 DIRECTORY IS AN IMPORTANT FEATURE FOR THE SAFE
 OPERATION OF AN ELECTRICAL SYSTEM UNDER NORMAL AND
 EMERGENCY CONDITIONS. THE PURPOSE OF AN ACCURATE AND
 LEGIBLE CIRCUIT DIRECTORY IN THESE TYPES OF EQUIPMENT
 IS TO PROVIDE CLEAR IDENTIFICATION OF CIRCUIT BREAKERS
 AND SWITCHES THAT MAY NEED TO BE OPERATED BY SERVICE
 PERSONNEL OR THOSE WHO NEED TO OPERATE A SWITCH OR
 CIRCUIT BREAKER IN AN EMERGENCY. THIS REQUIREMENT IS
 SPECIFIC TO SWITCHBOARDS AND PANELBOARDS; HOWEVER, THE
 IDENTIFICATION REQUIREMENTS OF 110.22 APPLY TO ALL
 DISCONNECTING MEANS.
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
 NEC 408.4, 310.16,240.4 ETC
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION,
 COORDINATION AND CLARITY OF PLANS.
  
 8) NOTE: PLEASE SEE 450.3 AS THE OVER CURRENT
 PROTECTION ON RISER FOR TRANSFORMER FEEDING PANEL *K*
 IS TOO HIGH. THE RISER DOES CONTAIN A SCHEDULE WHICH
 NOTES OVER CURRENT PROTECTION AT THE MAXIMUM OF 125%.
 HOWEVER THE RISER STILL ALSO SHOWS THIS SAME
 TRANSFORMER AS A 45KVA UNIT. IF THIS UNIT IS REVISED TO
 75KVA THEN THE 90AMP OCP WOULD BE OK.
  
 9) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2, .1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS FOR ALL NEW LIGHTING
 BEING INSTALLED. AS NO DEVICES OR SYSTEM IS BEING SHOWN
 AT THIS TIME NO REVIEW OF THESE CAN BE DONE.
  
 10) NOTE: PLEASE COMPLETE A FIXTURE LEGEND FOR SPECIFIC
 FIXTURES. PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR ALL AREAS IN SCOPE OF WORK. PLEASE SEE
 FBC 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3.
 PLEASE KNOW AS NO PERFORMANCE CALCULATIONS WERE
 SUBMITTED IT IS NOT POSSIBLE TO SUPPLY ANY REVIEW
 COMMENTS ON THOSE ITEMS.
  
 11) NOTE: PLEASE KNOW ANY LOW VOLTAGE FOR SOUND, ACCESS
 CONTROL WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT,
 WITH PLANS AND FEES BASED ON THAT SCOPE OF WORK.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717