Date |
Text |
2008-10-08 16:57:18 | BUILDING PLAN REVIEW |
| PERMIT: 08090412 |
| ADD: 1610 PALM BEACH LAKES |
| CONT: CFR COASTAL |
| TEL: (954) 868-9692 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT SURVEYS, PLANS, |
| REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL |
| REQUIRE A THRESHLD INSPECTOR BEING A THRESHOLD |
| BUILDING, (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE |
| REQUIRED FOR PERMIT ISSUANCE. 106.1* / 109.3.6, 2004 |
| SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE |
| CODE. |
| |
| 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS.SHEET SP.01 UNDER |
| BUILDING DATA DOES NOT PROVIDE AS TO |
| WHAT CODE (YEAR) THIS PROJECT WAS DESIGNED. |
| |
| 1E) SP.01 BUILDING DATA, THE PLANS ALSO NEGLECT TO |
| IDENTIFY THE 2004 FBC, EXISTING BUILDING CODE, CHAPTER |
| 9 THAT DEALS WITH ADDITIONS, PLEASE CORRECT. STRUCTURAL |
| SHEET S.01 ALSO NEEDS TO BE UPDATED TO THE 2007 |
| SUPPLEMENTS. |
| |
| 1F) SP.01 CALCULATIONS THE BUILDING INFORMATION AND |
| CODE SECTIONS ARE NOT TAKEN FROM THE 2004 FBC PLEASE |
| PROVIDE THE FOLLOWING BUILDING INFORMATION IN REGUARDS |
| TO THE 2004 FBC: |
| 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF |
| OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| DESIGNED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, |
| CHAPTER 6, & TABLE 601. |
| D) THE OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| BUILDING PERMIT |
| . |
| 2) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD |
| BUILDING BY DEFINTION; THRESHOLD INSPECTION PLAN FL S. |
| S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING |
| WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, |
| OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| 500 PERSONS. |
| 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 2B) SUBMIT: THRESHOLD INSPECTOR: WPB AMENDMENT |
| 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN |
| CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT |
| (561)805-6666 FOR FURTHER INFORMATION |
| BEFORE THE PERMIT MAY BE ISSUED. |
| |
| 2C) REQUIRED STATEMENT ON PLANS: THRESHOLD BLDG, W.P.B. |
| AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 3A) LS.01 NO BLDG TYPE INFORMATION HAS BEEN PROVIDED AS |
| REQUESTED UNDER (1F). THE PLAN INDICATES THE EXTERIROR |
| WALL AS A 4 HR FIRE RATED WALL WITH AN OVERHEAD 3 HR |
| RATED OPENING. IS THE INTENT TO MAKE |
| THIS KITCHEN NOT AN DDITION BUT A SPERATE SINGLE STORY |
| BUILDING THAT WOULD NOT MEET THE THRESHOLD |
| REQUIREMENTS? |
| |
| 3B) LS.01 THIS PLAN INDICATES ON THE EXISTING BUILDING |
| A PARTIAL BREAK ROOM, AND THE DOOR# 5 FROM THE BREAK |
| ROOM INTO THE NEW HALLWAY NOT PART OF A REQUIRED |
| EGRESS. SHEET A.01 PROVIDES ENOUGH |
| WALLS TO CALCULATE THE AREA OF THE BREAK ROOM AS 827 SQ |
| FT/ /15 = 56 AS AN OCCUPANT LOAD. THIS WOULD REQUIRE |
| TWO MEANS OF EGRESS PLEASE PROVIDE DETAILS ENOUGH ON |
| THE EXISTING BREAK ROOM PROVIDING |
| 2 EGRESS PATHS. TABLE 1014.1. |
| |
| 3C) LS.01 THIS DOOR# 5 IT WOULD ALSO APPEAR TO NEED 3 |
| HR OPENING PROTECTION IF THE OVERHEAD DOOR WITHIN THE |
| SAME BREAK ROOM REQUIRES IT? ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 4) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 5) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| SECTION 113 OF THIS CHAPTER. |
| |
| 6) 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES, |
| 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| 3A) ROOF DECK OVER THE NEW KITHEN SHEET A.03 DETAIL 2 |
| DOES NOT PROVIDE INFORMATION AS TO TYPE OF ROOFING |
| ASSEMBLIES. |
| 3B) METAL ROOF DECK PARKING GARAGE |
| |
| 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 9) A.01 THE KITCHEN EXTERIOR WALLS INDICATE |
| WATERPROOFING TO BE APPLIED, PLEASE PROVIDE PRODUCT |
| INFORMATION . 1807.3.2.1 & 1807.3.2. |
| |
| 10) SHEET S.02 NOTE # 5 FOR WIND INFORMATION IS |
| MISSING: |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7-02. |
| |
| 2. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| 3. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED |
| DESIGN PROFESSIONAL. |
| |
| 11) SHEET PA.01 PARKING GARAGE PLEASE PROVIDE THE |
| FOLLOWING INFORMATION IN REGUARDS TO THE 2004 FBC: |
| 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF |
| OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| DESIGNED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, |
| CHAPTER 6, & TABLE 601. |
| D) THE OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| BUILDING PERMIT |
| |
| 12) PA.02 INDICATES RAMPED DRIVE TO BACK UP AGAINST |
| BACK WALL OF OPEN PARKING GARAGE, PLEASE PROVIDE |
| WATERPROOFING DETAILS 1807.3.2.1 & 1807.3.2. |
| |
| 13) PA.02 / PS.02 OPEN WALL SECTION INDICATES THE METAL |
| DECKING TO BE FASTENED TO METAL TRUSSES PER |
| MANUFACTURERS SPEC, PLEASE PROVIDE |
| 1609.6.2.2.COMPONENTS AND CLADDING. |
| |
| 14) PA.02/ PS.02 OPEN WALL SECTION DOES NOT PROVIDE |
| METAL HI-HAT CONNECTION TO THE METAL TRUSS, PLEASE |
| PROVIDE 1609.2.2 COMPONENTS AND CLADDING. |
| |
| 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |