2008-10-03 12:06:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. SEE FBC R301.1 WHICH STATES THAT BUILDINGS AND
 STRUCTURES AND "ALL PARTS THEREOF" SHALL BE CONSTRUCTED
 TO SAFELY SUPPORT ALL LOADS, INCLUDING WIND. PLEASE
 DEMONSTRATE WHERE IN EITHER FBC R301 OR FBC CHAPTER 20
 A DESIGN CAN PERMIT SCREEN TO 'BLOW OUT' IN 75MPH
 WINDS. THERE ARE REFERENCES TO 75MPH AND 50MPH IN
 VARIOUS PLACES ON THE PLAN AND IN THE CALCULATIONS. THE
 CITY OF WEST PALM BEACH LIES ENTIRELY WITHIN THE 140MPH
 WIND ZONE, FBC R301. REVISE THE DESIGN AND PLANS
 ACCORDINGLY OR SHOW EXCEPTION IN THE CODE. IT APPEARS
 THAT THE ENGINEER IS USING AN EXCEPTION IN THE CODE
 WHICH IS FOR REMOVABLE ACRYLIC OR VINYL PANELS. FAILURE
 OF A STRUCTURE COMPONENT AS DESIGN INTENT, EVEN AN ITEM
 SUCH AS SCREEN, IS NOT PERMITTED IN THE FLORIDA
 BUIDLING CODE.
  
 ALSO, BASED ON NOTES AND SPECIFICATIONS ITEM 6 ON PAGE
 3 OF 3, IT APPEARS THAT THE STRUCTURE WILL FAIL AT
 50MPH, BEFORE THE SCREEN WILL "BLOW OUT" AT 75MPH.
  
 2. THERE IS A CONFLICT IN THE PLAN REGARDING THE SCREEN
 DESIGN. PAGE 1 STATES THIS IS INSTALLED WITH SPLINE AND
 IS DESIGNED TO "BLOW OUT", BUT PAGE 3 STATES SCREEN IS
 TO BE REMOVED. CLARIFY CONSTRUCTION, FBC*106, FBC R301.
  
 3. THE PLANS MAKE REFERENCE TO FBC CHAPTER 20. THE
 DESIGN IS TO COMPLY WITH FLORIDA BUILDING CODE,
 RESIDENTIAL. PLEASE REVISE PLANS TO INCLUDE CORRECT
 CODE REFERENCES.
  
 4. ONLY ONE SET OF CALCULATIONS WAS SUBMITTED. TWO
 COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FOR PERMIT
 ISSUANCE. HOWEVER, ONE SET OF STRUCTURAL PLANS WILL BE
 RETAINED. WHEN RESUBMITTING, PLEASE PROVIDE TWO
 COMPLETE NEW SETS. THE SITE PLAN WILL BE RETURNED TO
 THE CONTRACTOR AS ONLY STRUCTURALS WILL BE RETAINED.
  
 5. PLANS INDICATE "PREFAB PANELS BY AQUA SHIELD";
 ANOTHER NOTE STATES "END PANEL PROFILE". NO DETAILS
 WERE PROVIDED IN THE PLAN LABELED AS SUCH. AS THE
 NATURE OF THE PREFAB PANELS IS NOT CLEAR, COMPLIANCE
 REQUIREMENTS WITH FAC9B72 CANNOT BE DETERMINED. FLORIDA
 STATE OR LOCAL PRODUCT APPROVAL MAY BE REQUIRED,
 FAC9B72. SECTION 1 DOES NOT PROVIDE DETAILS OF A PANEL.
  
 6. PROVIDE INFORMATION REGARDING THE EXISTING SLAB AND,
 IF NO FOOTINGS EXIST, PROVIDE CALCULATIONS TO SHOW HOW
 THIS WILL RESIST WIND LOADS FBC301.1. NOTE THAT THIS
 SPAN EXCEEDS THE SPANS ALLOWED FOR SLAB ONLY WITHOUT
 FOOTING IN THE AAF GUIDE. PAGE 1 STATES THAT THIS
 DESIGN IS IN ACCORDANCE WITH THE AAF GUIDE.
  
 7. SHOW PURLIN LOCATIONS AND SPANS, FBC R301. SOME
 INFORMATION IS ADDED IN A NOTE ON SHEET 3, BUT AAF
 GUIDE TREATS PURLINS AS A STRUCTURAL COMPONENT. PURLINS
 ARE SHOWN ON SIDES; ARE THESE THE ONLY PURLINS ON THIS
 STRUCTURE? NOTE THAT IN THE AAF GUIDE, THE SECONDARY
 SUPPORTS ON WALLS ARE GIRTS, PURLINS ARE ON THE ROOF.
  
 8. THE SURVEY SHOWS A 24X36 CONCRETE POOL DECK; THE
 PROPOSED SCREEN ENCLOSURE IS 35X20. IT APPEARS THAT THE
 INTENTION IS TO USE THE EXISTING AS THE STRUCTURAL
 SUPPORT FOR THE ENCLOSURE. REVISE THE SITE PLAN TO
 CLEARLY SHOW THE PROPOSED IMPROVEMENT.
  
 9. GOVERNING CODE SHOULD INCLUDE 2007
 REVISIONS/SUPPLEMENTS; PLEASE REVISE PLAN.
  
 10. STRUCTURAL INFORMATION WAS PROVIDED FOR THE PURLIN
 AND MOUNTING ANGLE, MOUNTING CHANNEL. PROVIDE
 STRUCTURAL INFORMATION FOR THE BEAMS AND COLUMNS. SHEET
 1 SHOWS THE ROOF BEAMS AT 1.5"X2"; IS THIS CORRECT? THE
 MINIMUM SIZE IN THE AAF GUIDE FOR 140MPH EXPOSURE B IS
 2X4, YET CALCULATIONS STATE THIS WAS DESIGNED TO 146
 EXPOSURE C.
  
 11. PROVIDE A GIRT TO POST DETAIL, FBC R301, FBC*106.
  
 12. CALCULATIONS REFER TO FBC1613. THIS SECTION IS HIGH
 VELOCITY; CITY OF WEST PALM BEACH IS NOT WITHIN THE
 HVHZ. DESIGN MUST BE IN ACCORDANCE WITH NON-HVHZ
 REQUIREMENTS. ALSO, FBC RESIDENTIAL IS TO BE USED FOR
 THIS R3 STRUCTURE.
  
 13. COLUMN SIZES NOT SPECIFIED. FBC*106, FBC R301.
  
 14. PROVIDE INFORMATION REGARDING THE HOST STRUCTURE.
 IS THE ATTACHMENT, SECTION 1 ON PAGE 2, CONNECTING TO
 THE WALL, UNDER THE FASCIA?
  
 15. PROVIDE A CONNECTION DETAIL, COLUMN TO TRACK AT
 BOTTOM. FBC R301.
  
 16. PROVIDE A CONNECTION DETAIL, COLUMN TO BEAM, FBC
 R301.
  
  
  
  
  
  
  
  
  