Plan Review Notes For Permit 08090392 |
Permit Number |
08090392 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-10-01 10:16:02 | ***DENIED*** | | | | 1) PLEASE CORRELATE ALL INFORMATION. THE PERMIT | | APPLICATION INDICATES A DIFFERENT UNIT NUMBER THAN THE | | DRAWINGS. | | | | 2) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | 3) SMOKE DETECTORS ARE CALLED OUT ON DRAWINGS. IF | | DEVICES ARE NOT TIED TO THE BUILDING FIRE ALARM SYSTEM, | | THE TERM SMOKE ALARM SHOULD BE USED TO IDENTIFY THE | | EQUIPMENT. | | | | 4) PLEASE SEE BUILDING COMMENT #5 REGARDING CLARITY | | REQUIREMENTS FOR PLANS. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|