Plan Review Notes
Plan Review Notes For Permit 08090392
Permit Number 08090392
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-10-01 10:16:02***DENIED***
  
 1) PLEASE CORRELATE ALL INFORMATION. THE PERMIT
 APPLICATION INDICATES A DIFFERENT UNIT NUMBER THAN THE
 DRAWINGS.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 3) SMOKE DETECTORS ARE CALLED OUT ON DRAWINGS. IF
 DEVICES ARE NOT TIED TO THE BUILDING FIRE ALARM SYSTEM,
 THE TERM SMOKE ALARM SHOULD BE USED TO IDENTIFY THE
 EQUIPMENT.
  
 4) PLEASE SEE BUILDING COMMENT #5 REGARDING CLARITY
 REQUIREMENTS FOR PLANS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756