Plan Review Notes
Plan Review Notes For Permit 08090381
Permit Number 08090381
Review Stop E
Sequence Number 2
Notes
Date Text
2008-11-17 15:41:57 
  
  
 ** FAILED 2ND REVIEW **
  
  
 1) NOTE: IF EACH PERMITTED SHELTER IS GOING TO BE UNDER
 SEPARATE PERMIT PLEASE SUBMIT THE PLANS WITH ELECTRICAL
 DETAIL FOR EACH. THE ELECTRICAL FOR SITE AND BATH ROOM
 BUILDING WAS OK FOR FEEDS TO SHELTERS.
 PLEASE SUBMIT THE DETAILS FROM THOSE PLANS WITH TITLE
 BLOCKS, SIGNED DATED AND SEALED OR SUBMIT ELECTRICAL
 SHEETS FROM THOSE SETS FOR EACH PERMITTED PACKAGE.
 ELECTRICAL FOR EACH REQUIRED. 225.31-225.39, 250.32,
 250.50 ETC
  
 2) NOTE: PLEASE SEE SHEET A-6 IS A PHOTO-COPY OF
 SIGNED, DATED AND SEALED PLANS WHICH ARE NOT PERMITTED.
 FS481.221
  
 3) NOTE: PLANS NEED TO INDICATE LOCATION/ADDRESS OF
 PROJECT.
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.5
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  