Plan Review Notes
Plan Review Notes For Permit 08090381
Permit Number 08090381
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-30 10:23:13** DENIED REVIEW **
  
 1) NOTE:
  
 2) NOTE: NO ELECTRICAL PLANS SUBMITTED AND INCLUDED.
 PLEASE SEE THE 2005 NEC FOR MINIMUM ELECTRICAL DESIGN.
 PLEASE BE SURE TO SEE 230.70,.71,72,76,79,240,250.32,25
 0.50,215.5,,225.31-225.39 ETC
 FBC 106.3.5.1.2
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13 FOR ANY MINIMUM
 DESIGNS REQUIRED.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  