 ** FAILED REVIEW **
  
  
 1) NOTE: NEED TO SUBMIT COMPLETE ELECTRICAL PLANS FOR
 ACCURATE SCOPE OF WORK. FBC 105.1, NEC 2005, FBC 2004
 W/2007 REVISIONS.
  
 2) NOTE: NEW SEPARATE SPACES WITH NEW FULL HEIGHT WALLS
 ARE REQUIRED TO CONTAIN NEW LIGHTING CONTROLS PER
 13-415.1.ABC .1.1,.1.2.
 ALL SEPARATE SPACES SHALL CONTAIN CONTROLS TO MEET
 PRESCRIPTIVE REQUIREMENTS.
  
  
  
  
  
  
  
  
  
  