Plan Review Notes
Plan Review Notes For Permit 08090375
Permit Number 08090375
Review Stop P
Sequence Number 2
Notes
Date Text
2008-10-17 14:35:02PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE
 VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR, MATERIALS AND DESIGN (WHICH NOW INCLUDES
 A NEW BATHROOM).
 PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT
 VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED.
  
 2. SHEET A-1 "GENERAL BUILDING CODE ANALISIS" THE
 "PLUMBING FIXTURE REQUIREMENTS" MINIMUM FIXTURE
 REQUIREMENTS PER TABLE 403.1 INDICATED ON THE PLAN
 SHEET IS WRONG FOR A BUSSINESS OCCUPANCY. PLEASE
 CORRECT MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
 FOR A BUSSINESS OCCUPANCY PER FBC-2004 PLUMBING TABLE
 403.1 TO BE THE FOLLOWING.
  
 WATER CLOSETS, MALE/FEMALE = 1 PER 25 FOR THE FIRST 50
 AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50.
  
 LAVATORIES, MALE/FEMALE = 1 PER 40 FOR THE FIRST 50 AND
 1 PER 80 FOR THE REMAINDER EXCEEDING 50.
  
 DRINKING FOUNTAINS = 1 PER 100.
  
 3. SHEET A-1 PROPOSED FLOOR PLAN DOES NOT CLEARLY
 INDICATE THE REQUIERED DRINKING FOUNTAIN FOR A
 BUSSINESS OCCUPANCY. PER FBC-2004 PLUMBING TABLE 403.1
 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES FOR A
 BUSSINESS OCCUPANCY IS 1 PER 100 AND IT SHALL BE
 ACCESSIBLE PER THE FOLLOWING FBC-2004 CHAPTER 11,
 FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **SECTION 11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 SECTION 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO
 OUTLET MAXIMUM.
  
 SECTION 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER
 FLOW IN TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL
 TO FRONT OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON
 AN ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS
 WITHIN 3" OF THE FRONT OF FOUNTAIN.
  
 SECTION 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR
 SIDE MOUNTED NEAR FRONT EDGE.
  
 SECTION 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X
 48" FLOOR SPACE.
  
 SECTION 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING
 FOUNTAIN IS PROVIDED ON A FLOOR, THERE SHALL BE A
 DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO INDIVIDUALS
 WHO USE WHEELCHAIRS IN ACCORDANCE WITH SECTION 11-4.15
 AND ONE ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY BENDING
 OR STOOPING.(THIS CAN BE ACCOMMODATED BY THE USE OF A
 HI-LO FOUNTAIN OR BY SUCH OTHER MEANS AS WOULD ACHIEVE
 THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON EACH
 FLOOR).
  
 4. SHEET A-1 PROPOSED FLOOR PLAN IS INDICATING A NEW
 BATHROOM. PLEASE PROVIDE THE FOLLOWING FBC-2004 CHAPTER
 11, FLORIDA ACCESSIBILITY CODE REQUIREMENTS FOR THE
 WATER CLOSET PER THE FOLLOWING CODE SECTIONS.
  
 **SECTION 11-4.16 WATER CLOSETS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
  
 SECTION 11-4.16.2 CLEAR FLOOR SPACE. (SEE FIGURE 28,
 18" SIDE- 36" MIN. TOTAL.
  
 SECTION 11-4.16.3 HEIGHT. 17" TO 19".
  
 SECTION 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE
 MAX. 44" HIGH.
  
 5. SHEET A-1 PROPOSED FLOOR PLAN DOES NOT CLEARLY
 INDICATE THE SINK NEXT TO THE NEW BATHROOM AS EXISTING
 OR PROPOSED NEW. PLEASE CLARIFY THIS ON THE RESUBMITTAL
 (PER FBC-2004 CHAPTER 1, W.P.B. AS AMENDED SECTION
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS) AND
 PLEASE KNOW THAT IF THIS IS A NEW PROPOSED BREAK ROOM
 SINK THAT IT SHALL BE ACCESSIBLE PER THE FBC-2004
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 ** SECTION 11-4.24 SINKS (ELEVATION DETAIL REQUIRED
 WITH THE FOLLOWING INFORMATION)
  
 SECTION 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
  
 SECTION 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30"
 WIDE, AND 19" DEEP.
  
 SECTION 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
  
 SECTION 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND
 CLEAR FLOOR SPACE SHALL EXTEND A MAXIMUM OF 19"
 UNDERNEATH THE SINK.
  
 SECTION 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE
 TO PROTECT AGAINST CONTACT.
  
 SECTION 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE,
 OR ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 6. SHEET A-2 SANITARY PLUMBING RISER IS INDICATING A
 "SV" FOR THE VENT. PLEASE CLARIFY IF THIS IS AN AIR
 ADMITTANCE VALVE (A.A.V.) AS NO LEGEND WAS PROVIDED.
 PER FBC-2004 PLUMBING SECTION 901.1 SCOPE.
  
 7. NOTE: IF "SV" IS AN AIR ADMITTANCE VALVE CLEARLY
 INDICATE ON THE RESUBMITTED PLANS HOW MANY FLOORS THE
 BUILDING HAS AND HOW MANY FLOORS ARE LOCATED ABOVE THE
 AIR ADMITTANCE VALVE. PLEASE KNOW THAT PER FBC-2004
 PLUMBING SECTION 917.3.1 LOCATION OF BRANCH. THE
 HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE DRAINAGE
 STACK OR BUILDING DRAIN A MAXIMUM OF FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK. WHICH MEANS THAT
 THERE CAN ONLY BE FOUR FLOORS ABOVE THE PROPOSED AIR
 ADMITTANCE VALVE FOR THE NEW BATHROOM.
  
 8. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3), (5), (8), (10), AND (13): AN ISOMETRIC
 POTABLE WATER RISER DIAGRAM IS REQUIRED FOR THE
 PROPOSED WORK FOR BOTH THE HOT AND COLD WATER
 INDICATING THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF
 THE WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608,
 THERMAL EXPANSION CONTROL FOR THE WATER HEATER (IF
 APPLICABLE) **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS (IF APPLICABLE) WHERE QUICK CLOSING VALVES
 ARE UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS,
 ICE MAKERS) **604.9.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved