2008-10-22 15:29:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) AS REQUESTED IN LAST REVIEW 9-19-08, SUBMIT
 MECHANICAL (A/C) PLANS FOR REVIEW, SEE 2004 FBC/M
 401.2. (AS THE FLOOR PLAN IS BEING ALTERED AND ROOM
 SIZES CHANGED THE EXISTING SUPPLY AND RETURN GRILL
 LOCATIONS WILL NEED TO BE ALTERED AND AMOUNT OF AIR
 CFM'S TO EACH ROOM. PLEASE SUBMIT MECHANICAL PLAN
 SHOWING NEW REQUIREMENTS OR MECHANICAL PLAN SHOWING THE
 EXISTING LOCATIONS ARE MEETING THE NEW REQUIREMENTS AND
 CODES).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]