2008-10-17 10:52:23 
  
  
 BUILDING PLAN REVIEW
 PERMIT: 08090375
 ADD: 307 EVERNIA AVE#200
 CONT: RAYMOND H. NORDINE
 TEL: (561)655-1912
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 10-17-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) OK
  
 NOTED: HOWEVER, SHEET A-2 FAILS TO INDICATE THE
 LOCATION OF THE SPRKILER HEAD IN THE NEW BATHROOM AND
 REMODELED SUPPLY CL. ROOM.
 3) IF THIS BUILDING HAS A SPRINKLER SYSTEM, PLEASE
 STATE THIS INFORMATION ON THE PLANS. NOW THE SPACE IS
 ALTERED SHOW THE LAYOUT AND LOCATION OF THE SPRINKLER
 HEADS IN RELATION TO THE NEW ROOMS; THIS INFORMATION
 CAN BE SHOW ON THE CEILING PLANS WHICH IS ALSO MISSING
 FROM THE DRAWINGS. FBC 106.3.5.1.1(5) FS 553.79(2).
  
 4) OK
  
 THE TOP TRACK WAS ADDRESSED HOWEVER; NO INFORMATION WAS
 GIVEN FOR THE BOTTOM TRACK.
 5) WALL TYPES W-1 AND W-2 FAIL TO INDICATE HOW THE TOP
 AND BOTTOM TRACK WILL BE FASTEN TO THE RESPECTIVE
 STRUCTURE. STATE THE TYPE OF FASTENERS TO BE USED TO
 HOLD THE TRACK IN PLACE AND THE SPACING OF THE
 FASTENERS. ADDITIONAL INFORMATION REQUIRED 106.1.2
  
  
 **NO RESPONSE NOT ADDRESSED**
 6) THE CLAIMED VALUATION THE PERMIT APPLICATION IS LOW.
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST EXCLUDING
 LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD)
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER FBC
 108.3*.
  
 7) OK.
 8) OK
 NEW: (A) THE NEW BATHROOM ADDED ON THE PLANS NEEDS TO
 INDICATE THE WALL AND FLOOR FINISHES IN COMPLIANCE WITH
 FBC 1210. WALLS WITHIN 2 FEET OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FINISH FLOOR.
 NOTE: PAINT ON DRYWALL IN NOT CONSIDERED A HARD
 SURFACE.
  
 (B) BATHROOMS SHALL BE MECHANICALLY VENTILATED IN
 ACCORDANCE WITH THE FLORIDA BUILDING MECHANICAL CODE.
 1203.4.2.1. INDICATE THE VENTILATION SYSTEM FOR THE
 BATHROOM.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  