2008-10-01 09:38:33 | ***DENIED*** | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | SAFETY SHALL COMPLY WITH NFPA 101, 2003. PLEASE ADD TO | | CODE TABULATION. | | | | 2) PLEASE ILLUSTRATE THE LOCATIONS OF ILLUMINATED EXIT | | SIGNS AND EMERGENCY LIGHTING FACILITIES. (NEW OR | | EXISTING) | | | | 3) PLEASE SHOW LOCATION(S) OF REQUIRED 2A-10B,C RATED | | FIRE EXTINGUISHERS. | | | | 4) IF SPACE IS PROTECTED BY AUTOMATIC FIRE SPRINKLER | | SYSTEM, SHOW SPRINKLER HEAD LAYOUT. ADDITIONALLY, | | SEPARATE SHOP DRAWINGS AND PERMIT WILL BE REQUIRED | | PRIOR TO FIRE SPRINKLER REMODEL IF APPLICABLE. | | | | 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. PLEASE ADD TO CODE TABULATION. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|