Plan Review Notes For Permit 08090333 |
Permit Number |
08090333 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2008-11-24 14:08:12 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | | | 1. CONTRACTOR CHANGED DESIGN PRESSURES SINCE LAST | | REVIEW. THIS IS EXPOSURE C; CONTRACTOR PRINTED SOFTWARE | | GENERATED WIND LOADS, USED THE CORRECT WIND LOADS FOR | | THE OTHER REVIEWS, BUT THEN REDUCED THE DESIGN | | PRESSURES. PLEASE REVISE THE DESIGN PRESSURES AND | | ANCHOR SPACING AS NEEDED. THE CONTRACTOR HIGHLIGHTED | | THE COLUMN FOR 60PSF, BUT DID NOT USE THIS DESIGN | | CRITERIA FOR ALL OPENINGS. IT IS NOT CLEAR WHY, AFTER | | USING THE CORRECT DESIGN PRESSURES FOR TWO REVIEWS, | | THIS WOULD BE CHANGED ON THIRD REVIEW. | | | | PLEASE CONTACT ME IF YOU NEED ASSISTANCE. | | | | |
|