Plan Review Notes For Permit 08090276 |
Permit Number |
08090276 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-11-22 10:13:10 | MECH REVIEW STATUS CHANGED TO FAIL. | | | | NOTE: EVEN THOUGH MECH PLANS PASSED PREVIOUS REVIEW, | | THEY ARE NOW IN FAIL STATUS. THE HOUSE ARCHITECTURAL | | FLOOR PLAN HAS BEEN REVISED TO SHOW THE GUEST ROOM AS | | ACCESSIBLE FROM THE MAIN HOUSE WITH ONE BATHROOM IN | | THIS AREA. PAGE M1 STILL SHOWS THEM SEPARATED WITH TWO | | BATHROOMS, TWO EXHAUST FANS AND THE RETURN GRILL IS | | SHOWN IN A LOCATION THAT WOULD BE OUTSIDE THE HOUSE | | ACCORDING TO ARCHITECTURAL PLANS. PLEASE COORDINATE | | MECHANICAL AND ARCHITECTURAL PLANS, SHOWING ANY CHANGES | | TO THE MECHANICAL SYSTEMS WHICH ARE NEEDED AS A RESULT | | OF THE RE-DESIGN OF THIS AREA AND RESUBMIT FOR REVIEW. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|