Plan Review Notes
Plan Review Notes For Permit 08090276
Permit Number 08090276
Review Stop P
Sequence Number 1
Notes
Date Text
2008-09-17 12:00:25PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A6, SANITARY PLUMBING RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET A2. AT A MINIMUM THE
 SANITARY RISER SHOULD REFLECT THE FLOOR PLAN. PLEASE
 CORRECT THE FOLLOWING PER THE FBC-2004 PLUMBING CODE
 SECTION 701.1 SCOPE.
  
 A} UTIL. WASHING MACHINE AND LAUNDRY TRAY ARE BEING
 INDICATED IN THE WRONG PLACE.
  
 B} BATH 3, LAVATORY IS MISSING FROM THE SANITARY RISER.
  
 C} POWDER ROOM BATH IS BEING SHOWN IN THE WRONG PLACE
 DUE TO THE LOCATION OF ITS BRANCH FITTING OFF THE MAIN.
 CLEARLY INDICATE THE REQUIRED OFFSET TO THE POWDER ROOM
 DUE TO ITS BRANCH FITTING LOCATION.
  
 D} HER BATH, LAVATORY IS BEING INDICATED IN THE WRONG
 PLACE.
  
 E} MORNING BAR SINK BY THE GUEST SUITE IS MISSING FROM
 THE SANITARY RISER.
  
 2. SHEET A6, SANITARY RISER: THE KITCHEN DOUBLE BOWL
 SINK WITH DISPOSAL AND DISHWASHER ARE BEING INDICATED
 WITH A WASTE ARM AND VENT THRU THE ROOF. PLEASE KNOW
 THAT PER TABLE 906.1, MAXIMUM DISTANCE OF FIXTURE TRAP
 FROM VENT WITH AN 1-1/2 TRAP AND 2" WASTE ARM CAN ONLY
 BE 6' FROM THE VENT. IT IS SUGGESTED THAT THE DOUBLE
 BOWL SINK WITH DISPOSAL AND DISHWASHER BE VENTED WITH
 AN AIR ADMITTANCE VALVE (STUDOR VENT) PER FBC-2004
 PLUMBING SECTION 917, AIR ADMITTANCE VALVES. ALSO
 PLEASE CLEARLY INDICATE THE DISHWASHER DRAIN TO
 DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER. PER FBC-2004 PLUMBING SECTION 802.1.6
 DOMESTIC DISHWASHING MACINES.
  
 3. SHEET A2 SANITARY PLUMBING RISER INDICATES BUILDING
 SEWER DISCHARGE TO A SEPTIC TANK. PLEASE DELETE "SEPTIC
 TANK" AND ADD IN ITS PLACE "SEWER SYSTEM". PER
 MUNICIPAL CODE SECTION 90-123 USE OF SANITARY
 SEWERS.(C) SEPTIC TANKS ARE PROHIBITED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  